Frecon FIA-L18 User manual

FRECON, spol. s r.o. Hodkovická 115, 142 00 Praha 4, CZECH REPUBLIC
tel.: +420-241 71 32 44-45 fax: +420-241 72 10 52 E-mail: info@frecon.cz http://www.frecon.cz
FRECON
FIA-L18, 37, 55, 75, 110, 150, 220, 250
PROGRAMMABLE SPEED DRIVES
FOR
STANDARD AC INDUCTION MOTORS
0,18kW TO 2,5kW
INSTALLATION AND USER MANUAL

1
Dear user,
This manual has been designed to provide you with all the information you need
to install and use your FRECON SPEED DRIVE. Feel free to contact us for any
further information you may require concerning special applications beyond the
scope of this manual.
Please keep this manual in a safe place for future reference.
FRECON
SAFETY PRECAUTIONS
DANGER: The voltages present in the supply cables, the output cables and terminals, the control
power supply wiring and in certain internal parts of causing severe electric shock and
may be lethal !
WARNING: Whenever the drive has been energised
;
it must be isolated before work may continue.
A period of five minutes must elapse after isolation to allow the internal capacitors to
discharge fully. Until the discharge period has passed dangerous voltages may be
present within the drive.
Persons supervising and performing electrical installation must be suitably qualified and
competent in these duties, and should be given the opportunity to study this manual before work is
started.
TESTED
Committed to quality, FRECON individually test each FRECON SPEED DRIVE to ensure reliable
performance for the user. All units have passed FRECON´S quality control standards and conform
within tolerance to the enclosed specifications.
ENTIRE CONTENS COPYRIGHT FRECON s.r.o. ALL RIGHTS RESERVED, REPRODUCTION IN WHOLE OR IN PARTS WITHOUT PERMISSION IS PROHIBITED.
FRECON FIA-L IS A PRODUCT OF FRECON

2
1. Introduction
•Small, light-weight and compact
•IGBT output bridge for high speed switching and low power consumption
•Motor speed continuous - controlled from 0Hz to 125Hz (option - up to 500Hz)
•Logic and analogue inputs for remote control
•FRECON MINITERMINAL - control pod : combines keypad and display, operational functions of
the drive can be changed from the keypad.
•FRECON TELECONTROL: remote control and indication unit
•External braking unit
•External RFI filter
2. General characteristics
Type: FIA-L: 18 37 55 75 110 150 220 250
Nominal motor rating (kW) 0,18 0,37 0,55 0,75 1,1 1,5 2,2 2,5
Input:
Voltage 1x 230V ±10%
Nominal current (A) 2,6 4,4 6,1 7,0 9,6 12,2 17,5 20,0
Frequency 47 ÷63 Hz
Output:
Voltage 3 x 0 ÷input voltage
Frequency 0 ÷125Hz, (with spec. SW up to 500Hz)
Apparent power (kVA) 0,6 1,0 1,4 1,6 2,2 2,8 4,0 4,5
Overload 150%, 30 sec
Nominal current (A) 1,4 2,4 3,0 4,0 5,5 7,0 10,0 11,3
Modulation PWM - 18kHz
V / f - characteristic adjustable
Control:
logic inputs - control switch or PLC output
function - START/STOP, FORWARD/REVERSE
analogue inputs: 0÷20mA (4÷20mA), 0÷10V (2÷10V), potentiometer (2÷20kΩ)
function - SPEED CONTROL
Protections:
low voltage, overvoltage, overcurrent, I x t, short-circuit (phase-phase, phase-earth)
Environmental conditions:
Ambient temperature / Ambient humidity 0 ÷400C / max. 90% (non condensing)
Enclosure IP 00 or IP 20 or IP 54
Design criteria:
Safety EN 61 010-1 / 95
Electromagnetic compatibility - emission: EN 55 011/A1,B1; EN 50 081-1, 2 (with external RFI filter)
- immunity: EN 50 082-1, 2
Dimensions: Height (mm) 180 200
(IP 20) Width (mm) 153 160
Depth (mm) 97 145
Weight: (kg) 1,3 2,5
3. Description
status LED
indication
- power
-
failure
control and power
cables lead-in
heat sink FRECON MINITERMINAL
connector

3
4. Mechanical installation
4.1. Location
The installation must be located in a place free from dust;corrosive vapours;gases and all liquids.
Care must also be taken to avoid condensation of vaporised liquids, including atmospheric moisture.
4.2. IP rating
IP 20 or IP 00 (e.g. location in a switchboard ) or IP 54
4.3. Mounting
•The unit must be mounted vertically, and sufficient clearance must be allowed around the unit to
allow adequate flow of cooling air over the fins of the heat sink. A minimum of 50 mm is required
above and below the unit, and some clear space should also be allowed at the sides and front.
•Location within the cubicle (e.g. switchboard) without any ventilation of the air inside :
Heat can escape only by conduction through the skin of the cubicle, which is cooled by radiation to
the external air.
A minimum distance from the enclosure boundaries : 50 mm
Heat dissipation power : approx. 4% of the real output power.
5. Electrical installation
SAFETY PRECAUTIONS
DANGER: The voltages present in the supply cables, the output cables and terminals, the control
power supply wiring and in certain internal parts of the drive are capable of causing
severe electric shock and may be lethal !
WARNING: Whenever the drive has been energised
;
it must be isolated before work may continue.
A period of five minutes must elapse after isolation to allow the internal capacitors to
discharge fully. Until the discharge period has passed dangerous voltages may be
present within the drive.
Persons supervising and performing electrical installation must be suitably qualified and
competent in these duties, and should be given the opportunity to study this manual before work is
started.
5.1. Power connections
CHECK THAT
•the unit is disconnected from the input power before making connections to the terminals
- AC input power circuit breaker, installed upstream on the low voltage switchboard, is in "off"
position
5.1.1. Connection procedure
•FOR PROTECTION OF LIFE AND PROPERTY, EARTH WIRES SHOULD ALWAYS BE
CONNECTED FIRST !
•remove the front panel that is secured with screws
•connection cables should enter at the bottom
•connect the 1 PHASE mains supply to the terminals N;L.
•connect the motor terminals to the U, V, W terminals of the drive
•refit the front panel
Never connect the input power to the U, V, W terminals of the drive !!!

4
The layout of the power terminals and connections is shown in FIG 1.
L N U V W
-B +B
3~
M
PE
1phase 230V/50Hz
Braking unit
(option)
N
FIG 1
5.1.2. Recommended protection devices installed upstream of the drive and cabling
Drive model FIA-L 18 37 55 75 110 150 220 250
fuse ratings* 6A 10A 16A 20A 25A
cable size (for 3-core)** mm
2
1,5 2,5 4,0
* The use of slow protection devices (curve C) is recommended because a current surge may appear at power on.
**Cable sizes are recommendations only. Cabling should conform to local codes of practice and regulations.
5.1.3. Motor connection
•No protection devices between the drive and the motor are recommended. The power connections
from the drive output to the motor may be switched, for isolation purposes;but not for control
purposes.
•Connection between the drive and the motor as short as possible are recommended to prevent
emissions from the motor cable.
If it is not possible, screened or armoured cable may be used . The screen or armour should be
connected in the same way as for standard cable (to both the motor earth terminal and the drive
earth terminal).
•Installations with long cable runs to the motor (i.e. above approx. 30 m), may need the addition of
motor line chokes to prevent nuisance tripping of the drive caused by capacitative leakage effects.
Output voltage of the drive FRECON FIA - L : 3 x 230 V !
MOTOR WINDING CONNECTION MUST BE COMPATIBLE WITH THIS VOLTAGE !
IN THE MOST CASES : DELTA CONNECTION
5.2. Motor speed
•Standard squirrel-cage ac induction motors are designed as single speed machines. If it is intended
to use the capability of the drive to run the motor at speeds above its designed maximum, it is
strongly recommended that the motor manufacturer is consulted first.
•The principal risks due to overspeeding are the destruction of the rotor by centrifugal force, or of the
bearings by vibration or heat.
•Low speed is liable to result in overheating of the motor because the effectiveness of the internal
cooling fan reduces in proportion to the square of the reduction of speed. Motors should be
equipped with thermistor protection, and if full benefit of the use of low speeds is to be gained from
a variable speed drive it may be necessary to arrange additional cooling for the motor.

5
5.3. Control connections
5.3.1. Connection procedure
•remove the front panel that is secured with screws.
•for control connections use cable of 0,5 mm2screened
•connection cable should enter at bottom.
•connect screen to earth at the drive only .
•connect control cable to terminals
(connections are shown in FIG 2).
•refit the front panel
NOTE : always segregate control and power cabling !
5.3.2. Specifications of control inputs and outputs
Complete isolation between control and power electronic circuits.
•Analogue inputs
- speed control
current input : 0 ÷20 mA (4 ÷20 mA)
120 Ωinput impedance
voltage input : 0 ÷10 V (2 ÷10 V)
67 kΩinput impedance
potentiometer : 2 ÷20 kΩ
recommended value 10 kΩ
•Logic inputs
- run/stop : control switch or PLC output
- forward/reverse : control switch or PLC output
Input voltage : min : 15 VDC Input current : approx. 8,5 mA (24 VDC)
nominal : 24 VDC
max : 30 VDC
Input signal delay : max 5 ms
•Logic output
- drive status : volt-free change-over relay contact - 250 VAC ;8 A
6. Drive status indication
6.1. On the front panel of the drive
•LED "POWER" (red) : input voltage is present, all internal voltage levels are correct
•LED "FAILURE" (red) : internal or external trip (e.g. overvoltage, overcurrent, short-circuit ...)
the drive is stopped (disconnected from the load)
6.2. Remote indication
•Volt-free change-over relay contact
Control terminals : 5- normally open
6- common
7- normally closed
Relay energised when : drive healthy
Relay de - energised when : power off or drive tripped (disconnected from the load)
FIG. 2

6
7. Operating procedures
CHECK THAT :
* The motor rating is compatible with the drive rating
* The motor winding connection is compatible with the drive output voltage
(refer to chapter 5;section 1.3.)
* AC input power circuit breaker of the correct rating is installed upstream on the low voltage
switch - board (refer to chapter 5, section 1.2.)
* the drive is firmly attached in an upright position and is properly ventilated
7.1. Procedure I - remote (external) control, without using MINITERMINAL (control pod)
and TELECONTROL (remote control unit)
•connect the control cable to terminal board (shown in FIG 2)
•put the AC input power circuit breaker in "ON" position - the red "POWER" light goes on.
In the event of a fault, the red "FAILURE" light goes on.
7.1.1. Speed control
•potentiometer : terminals 8, 9, 11
or
•voltage signal : terminals 9, 11
or
•current signal : terminals 10, 11
7.1.2. "Run/stop"
•connect 24 V DC to the terminal 3(control switch or PLC output) :
The motor will start and run up to the set speed.
Acceleration is set by parameter "ACC" (refer to chapter 9.;section 1.)
•disconnect 24 V DC from the terminal 3:
The motor will ramp or coast to a stop.
Deceleration is set by parameter "DEC", stopping mode is set by parameter " CSTP "
(refer to chapter 9;section 1. and user manual for the MINITERMINAL - control pod)
7.1.3. " Fwd/rev" - Forward/reverse
•connect 24 V DC to the terminals 4 and 3 simultaneously (control switch or PLC output) :
Running motor - motor will ramp by set decel time to a stop and then will run up by set accel time
in a reverse direction to the required speed
Motor is stopped - motor will start and run up by set accel time in a reverse direction to the
required speed
•disconnect 24 V DC from the terminal 4(24V DC is connected to the terminal 3) :
The motor will ramp to a stop and then will run up in a forward direction to the set speed.
7.2. Procedure II - remote (external) control, using TELECONTROL - remote control unit (option)
•connect the control cable to the terminal boards at the drive and the TELECONTROL (shown in FIG
3)
FIG 3
•put the AC input power circuit breaker in "on" position - the red "Power" light goes on.
In the event of a fault;the red "FAILURE" light goes on.
FRECONTELECONTROL/FIA
FRECONFIA-L

7
7.2.1. Speed control
•potentiometer
7.2.2. "Run/stop"
•change-over switch
function (refer to chapter 7;section 1.2.)
7.2.3. "Forward/reverse"
•change - over switch
function (refer to chapter 7;section 1.3.)
7.2.4. Drive status indication
•LED " FAILURE " (red) : internal or external trip;the drive is stopped (disconnected from the load)
7.3. Procedure III - local control, using MINITERMINAL (control pod)
•remove the connector cover on the front panel of the drive
•connect the control cable from the control pod to the connector on the front panel of the drive
•put the AC input power circuit breaker in "ON" position - the red "POWER" light goes on.
In the event of a fault;the red "FAILURE" light goes on.
•press the CONTROL MODE SELECTION key (LOC/REM) on the control pod - select local (keypad)
control.
The red "LOC" light on the control pod goes on.
•all operational functions of the drive and motor can be controlled and all parameter values can be
changed from the keypad (refer to user manual for the MINITERMINAL)
8. Reset of the drive after a trip signal
Two modes are available :
•short time disconnecting of the drive from the supply and reconnecting
•STOP signal activation
Reset mode is set by parameter "CRTR" (refer to user manual for the MINITERMINAL)
NOTE : restart of the drive ("START" signal activation) is recommended when the motor is stopped !
9. Options
9.1. FRECON MINITERMINAL (control pod)
Combines keypad and display functions :
•local /remote control selection
•local control (run/stop, forward/reverse, output freq. control
resolution : 0,01 Hz)
•drive parameter values adjustment and display (LCD screen)
•user sets programming possibility (i.e. storing all functional
parameters into EEPROM for automatic or manual restore)
•required and actual output frequency monitoring (LCD screen)
•operational status LED indication : run, fwd, rev, local (keypad)
control
•fault codes display
•MOUNTING : externally anywhere convenient at a distance
permitted by a maximum cable length of 6 m from the drive to the pod.

8
Displayed values and adjustable drive parameters.
MENU Adjustment range Description
FOUT 0 ... fma
x
(Hz) actual output frequency
FSET 0 ... fma
x
(Hz) required output frequency
F0 0 - 125 Hz required output frequency
(0% analogue input signal)
F100 0 - 125 Hz required output frequency
(100% analogue input signal)
FERR 0 -125 Hz required output frequency
(analogue input signal non-present)
ACC 0,5 - 500 Hz/s FOUT acceleration
DEC 0,5 - 500 Hz/s FOUT deceleration
FBAS 25 - 241 Hz base frequency
U0 0 - 22% VMAX output voltage
(FOUT = 0 Hz)
U1 1 - 30% VMAX output voltage
(FOUT = 1/8 FBAS)
U2 2 - 40% VMAX output voltage
(FOUT = 2/8 FBAS)
U3 4 - 50% VMAX output voltage
(FOUT = 3/8 FBAS)
U4 6 - 60% VMAX output voltage
(FOUT = 4/8 FBAS)
U5 10 - 70% VMAX output voltage
(FOUT = 5/8 FBAS)
U6 16 - 81% VMAX output voltage
(FOUT = 6/8 FBAS)
U7 32 - 93% VMAX output voltage
(FOUT = 7/8 FBAS)
CINP 0, 1, 2, 3 reference input selection
CSTP 0,1 stopping mode selection
CRTR 0,1 reset mode selection
SET support parameter for user set programming
For more information: refer to user manual for the MINITERMINAL.
9.2. FRECON TELECONTROL - remote control unit
•Functions:
- fault LED indication
- speed control : potentiometer
- run/stop : change-over switch
- forward/reverse : change-over switch
•Dimensions : 110 x 80 x 55 mm (h x w x d)
•Mounting: externally anywhere convenient at a distance permitted by a maximum cable length of
50m from the drive to the TELECONTROL.
9.3. Braking unit
A decelerating AC motor regenerates energy into the inverter drive. This energy can only be dissipated
within the drive, it cannot be returned to the AC supply by the FRECON unit. If the regenerated power
is less than approx. 4% of rated drive power, the braking unit is not necessary to use.
Connection: terminals -B, +B (FIG. 1)

9
9.4. External RFI filter
To conform to EMC standards, external RFI-filter is necessary to use.
RFI - filter is located in the separate cubicle with enclosure IP 44 or IP00 (on request) or IP20
Dimensions:
•EMC emission according to EN 50 081-1, ČSN EN 55 011/B1:
FIA-L18 ÷ 75 : - enclosure IP00: 92 x 60 x 49 mm
FIA-L18 ÷ 75 : - enclosure IP44: 160 x 90 x 70 mm
FIA-L110 ÷ 220 : - enclosure IP00: 92 x 60 x 56 mm
FIA-L110 ÷ 220 : - enclosure IP44: 160 x 90 x 70 mm
FIA-L250 : - enclosure IP20: 138 x 56 x 50 mm
•EMC emission according to EN 50 081-2, ČSN EN 55 011/A1:
FIA-L250 : - enclosure IP20: 138 x 56 x 50 mm
9.4.1. Installation
To install the filter, follow the instructions in FIG 4
FIG 4
The filter cubicle is necessary to install near of the drive.
NOTE: Connections must be made with the short length of screened cables. If these cables are
altered in any way the filter will operate, but compliance with any emission standard is
no longer assured.
Input cable into the filter (filtered cable) and no control circuit should be run parallel to an unscreened
motor cable or unfiltered supply cable with a spacing less than 0,3 m and over a distance exceeding 1m.
9.5. PI controller: refer to user manual for the speed drive FRECON FIA-L/PI
9.6. Output frequency range extension : With spec. software is possible to extend output
frequency range up to 500 Hz (on request)
9.7. Motor line choke
filter cubicle
keep cables as
short as possible
2,5 mm
2
This manual suits for next models
7
Table of contents
Popular Engine manuals by other brands

WEICHAI
WEICHAI WP10NA Installation and application manual

Briggs & Stratton
Briggs & Stratton 190000 Series Operator's manual

Siemens
Siemens H-compact PLUS operating instructions

Baumuller
Baumuller DA 100 Commissioning and Maintenance

Raider
Raider 50 HP TLDI Service manual

Lenze
Lenze IE2 g500-S Mounting and switch on instruction