
Figure 16: Device Configuration window: WC45i-Gateway
6. In the Settings area (#5), change these settings:
Note: The Network settings are used to create separate networks using
multiple Gateways (that are in close proximity to one another).
Important!: The Radio Network and Radio Network Group settings
are selected by the user but MUST MATCH the existing Gateway
network for successful communication between the Gateway and
Endpoint.
a. Click the Radio Network list box arrow and select 0 (zero) to 7 for the
assigned number.
b. Click the Radio Network Group list box arrow and select 0 (zero) to 29
for the network group assigned number.
c. Click the Set button to save the information.
7. In the Set Encryption Key area (#6), change these settings:
a. In the Key text box, enter the encryption key for the device using 6 to 16
characters.
b. Click the Set button to save the information.
Important!: A Key CANNOT contain spaces or angle brackets.
The Gateway and Endpoints only communicate if they are configured
with the same Key.
When setting up a new network, use this same encryption Key on all the
devices.
Note: When the WC45i-GW-485 drops its network, it attempts to join
networks using the same encryption Key.
Caution: It is possible to hide the encryption Key so it cannot be
read. This is the most secure option, but if the Key is forgotten,
there is no way to recover it.
The Key must be reset on every device on the network.
8. Optional: Click the Settings menu and select Set Encryption Key
Unrecoverable to permanently hide the key.
Figure 17: Settings menu > Set Encryption Key Unrecoverable
9. Click Refresh List button to update the Modbus Slaves Reporting table
with all connected remote Endpoints.
Figure 18: Modbus Slaves Reporting table
10. Configure the Endpoints attached to the WC45i-GW-485.
Note: Use the Configuration procedure in the User Manual for these
WAVECONTACT Endpoints:
WC15i Multi-Input C1D1 Endpoint, WC20i Endpoint,
WC30i Wireless Pressure Sensor, WC40i Modbus Endpoint,
WC40i-COUNT Counter Endpoint, or WC40i-MB-RSD Modbus
Endpoint.
11. Optional: On the WC20i or WC45i-GW-485Endpoint, press the Check-in
button to apply power to the configured sensor, read the sensor values, and
send the collected sensor data to the Gateway.
12. Verify the Gateway is communicating with the Endpoints.
Note: A successful connection on the WAVECONTACT Endpoint is
indicated with Green blinking TX and ACT lights and a Red blinking
light for RX.
If the connection is NOT successful, a Green blinking TX light
appears for 10 seconds.
13. Close the WC Toolkit software.
14. Remove the WC-USB-DB9 USB to Serial DB9 programming cable from the
computer and the WC45i-BB.
15. As applicable, replace the Endpoint cover.
16. Mount the Gateway device.
Learn More
For additional product information about the WC45i-GW-485 Modbus Gateway, visit www.freewave.com.
For additional product information or assistance, contact a local reseller, or contact FreeWave Technologies,
Inc. at 303-381-9200 or 1-866-923-6168, or by email at moreinfo@freewave.com.
FreeWave Technologies, Inc. reserves the right to make changes to this document or the product described
within it without notice. FreeWave assumes no responsibility or liability for the use of this document or the
infringement of any copyright or other proprietary right.
The WC45i-GW-485 complies with FCC Part 15 rules. Operation is subject to the following two conditions:
1) This device may not cause harmful interference and 2) this device must accept any interference received,
including interference that may cause undesired operation.
The WC45i-GW-485 must be professionally installed and is only approved for use when installed in devices
produced by FreeWave or third party OEMs with the express written approval of FreeWave Technologies,
Inc. Changes or modifications should not be made to the device.
FreeWave Technologies, Inc.
5395 Pearl Parkway, Suite 100
Boulder CO 80301
www.freewave.com
Local: 303-381-9200
Toll Free: 1-866-923-6168
Fax: 303-786-9948
QSG0035AA Rev Mar-2018 Page 4 of 4 Copyright © 2018FreeWave