FujiFilm FRENIC HVAC Series User manual

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
Fuji FRENIC HVAC Drives
Quick Start Guide
Q
U
I
C
K
S
T
A
R
T
G
U
I
D
E
10 Columbia Way
Baulkham Hills NSW 2153
1800 987 616
Email: industrial@cse-uniserve.com.au
Web: www.cse-uniserve.com.au

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
Table of Contents
Disclaimer …………………………………………………………………………………………………………………………. 2
1. Keypad Layout and Functions
1.1 Keypad Layout ………………………………………………………………………………………………. 3
1.2 Keypad Functions …………………………………………………………………………………………..4
1.3 Navigate Mode Menus ...………………………………………………………………………………. 5
2. Menus
2.1 Menu Hierachy …………………………………………………………………………………………..…. 6
2.2 Programming Mode Menus …………………………………………………….……………………. 6
3. Function Code Programming ……..……………………………………………………………………………… 8
3.1 How to Change and Store VSD Settings …………...…………………………………………… 8
4. Application Examples ………………………………………………………………………………………………… 9
4.1 Terminal Control with 0-10Vdc Speed Reference …………………………………………… 9
4.1.1 Application Parameters ………………………………………………………………………10
4.2 Terminal Control with 0-10Vdc +1 Preset Speed Override ……………………………. 11
4.2.1 Application Parameters …………………………………………………………………..…. 12
4.3 Terminal Control with 4-20mA ……………………………………………………………………… 13
4.3.1 Application Parameters ………………………………………………………………………. 14
4.4 Terminal Control with Fire Mode Fixed Speed ………………………………………………. 15
4.4.1 Application Parameters ………………………………………………………………………. 16
4.5 Fire Mode using continous PID control (0-10Vdc ………………………………………….. 17
4.5.1 Application Parameters ……………………………………………………………………… 18
Disclaimer
This short form Quick Start Guide is for use with the Fuji FRENIC HVAC Series Drives.
For Complete information, please refer to the FRENIC HVAC installation manual and FRENIC
HVAC usermanual located in soft copy on the CD supplied with the drive.

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
1. Keypad Layout and Functions
1.1 Keypad Layout

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
1.2 Keypad Functions

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
1.3 Navigate Mode Menus

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
2. Menus
2.1 Menu Hierachy
2.2 Programming Mode Menus
The hierarchical structure for each screen is “Main menu” → “Sub-menu” → “Detailed
menu” → “Data revision screen”. Make each menu selection to move to the data revision
screen.

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
2.2 Programming Mode Menus

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
3. Function Code Programming
3.1 How to Change & Store VSD Settings

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
4. Application Examples
4.1 Terminal Control with 0-10Vdc Speed Reference

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
4.1.1 Application Parameters for Terminal Control with
0-10Vdc Speed Reference
F 11
Minimum requires function code setting:
Code Name Description Set
F 01 Frequency command
0-10Vdc voltage input to
terminal 12 1
F 02 Operation method
External signals—Terminal
forward 1
F 03 Maximum frequency 50Hz
F 04 Base frequency 50Hz
F 05 Rated voltage at base frequency
415V
F 06 Maximum output voltage 415V
F 07 Acceleration time 30 Sec
F 08 Deceleration time 30 Sec
F 11 Overload level Motor current rating plate Amps
F 37 Load selection Variable torque load 0
F 43 Current limiter Disabled 0
P 01 Number of poles As per motor rating plate 4
P 02 Motor rated capacity As per motor rating plate kW
P 03 Motor rated current As per motor rating plate Amps
P 99 Motor selection Other motors 4

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
4.2 Terminal Control with 0-10Vdc +1 Preset Speed Override

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
4.2.1 Application Parameters Terminal Control with 0-10Vdc +1
Preset Speed Override
Minimum requires function code setting:
Code Name Description Set
F 01 Frequency command
0-10Vdc voltage input to
terminal 12 1
F 02 Operation method
External signals—Terminal
forward 1
F 03 Maximum frequency 50Hz
F 04 Base frequency 50Hz
F 05 Rated voltage at base frequency
415V
F 06 Maximum output voltage 415V
F 07 Acceleration time 30 Sec
F 08 Deceleration time 30 Sec
F 11 Overload level Motor current rating plate Amps
F 37 Load selection Variable torque load 0
F 43 Current limiter Disabled 0
E 01 Terminal XI Function Multi step frequency SS1 0
C 05 Multi Step Frequency 1 Set required frequency Hz
P 01 Number of poles As per motor rating plate 4
P 02 Motor rated capacity As per motor rating plate kW
P 03 Motor rated current As per motor rating plate Amps
P 99 Motor selection Other motors 4

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
4.3 Terminal Control with 4-20mA

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
4.3.1 Application Parameters for Terminal Control
with 4-20mA
Minimum requires function code setting:
Code Name Description Set
F 01 Frequency command
Current input to terminal
C1 2
F 02 Operation method
External signals—Terminal
forward 1
F 03 Maximum frequency 50Hz
F 04 Base frequency 50Hz
F 05 Rated voltage at base frequency
415V
F 06 Maximum output voltage 415V
F 07 Acceleration time 30 Sec
F 08 Deceleration time 30 Sec
F 11 Overload level Motor current rating plate Amps
F 37 Load selection Variable torque load 0
F 43 Current limiter Disabled 0
P 01 Number of poles As per motor rating plate 4
P 02 Motor rated capacity As per motor rating plate kW
P 03 Motor rated current As per motor rating plate Amps
P 99 Motor selection Other motors 4

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
4.4 Terminal Control with Fire Mode Fixed Speed

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
4.4.1 Application Parameters for Terminal Control with
Fire Mode Fixed Speed
Code Name Data setting range Set
F 01 Frequency Command 1 2
F 02 Operation Method Terminal command FWD 1
F 03 Maximum Frequency 1 50Hz
F 04 Base Frequency 1 50Hz
F 05
Rated Voltage at Base
Frequency 1 415V
F 06 Maximum Output Voltage 1 415V
F 07 Acceleration Time 1 30 sec
F 08 Deceleration Time 1 30 sec
F 11 Overload detection level As per motor rating plate Amps
F 37 Load Selection Variable torque load
0
F 43 Current Limiter Disabled 0
E 07 Terminal [X7] Function Switch to fire mode (FMS) 134
P 01 Number of poles As per motor rating plate 4
P 02 Rated capacity As per motor rating plate kW
P 03 Rated current As per motor rating plate Amps
P 99 Motor Selection Other motors 4
H1 16 Fire Mode FMS-on 0
H1 17 Confirmation time 3.0
H1 18 Reference frequency Set frequency required for fire mode Hz
H1 19 Rotation direction Forward rotation 2
H1 20 Start method Auto search 1
H1 21 Reset interval 5.0

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
4.5 Fire Mode using continous PID control (0-10Vdc)

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
4.5.1 Application Parameters for vTerminal Control with Fire
Mode Using PID Control with 0-10Vdc
Code Name Data setting range Set
F 01 Frequency Command 1 2
F 02 Operation Method Terminal command FWD 1
F 03 Maximum Frequency 1 50Hz
F 04 Base Frequency 1 50Hz
F 05
Rated Voltage at Base
Frequency 1 415V
F 06 Maximum Output Voltage 1 415V
F 07 Acceleration Time 1 30 sec
F 08 Deceleration Time 1 30 sec
F 11 Overload detection Level As per motor rating plate
F 37 Load Selection Variable torque load
0
F 43 Current Limiter Disabled 0
E 07 Terminal [X7] Function Switch to fire mode (FMS) 134
E 24 Terminal [Y5A/C] Function Inverter running (RUN) 0
E 61
Terminal [12] Extended
Function External PID feedback value 1 42
C 58
Analog Input Adjustment for
Terminal
[12] (Display Unit)
Set according to pressure transducer
Pascals (Pa) –40
Pascals (kPa) - 41
C 59 Maximum scale Set to maximum range of transducer
C 60 Minimum scale Set to minimum range of transducer
P 01 Motor 1 (No. of poles) Set as per motor nameplate 4
P 02 Rated capacity Kilowatts Set as per motor nameplate kW
P 03 Rated current Set as per motor nameplate Amps
P 99 Motor 1 Selection Other motors 4

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
4.5.1 Application Parameters for vTerminal Control with Fire
Mode Using PID Control with 0-10Vdc
Code Name Data setting range Set
H1 16 Fire Mode (Mode selection) FMS - ON 0
H1 17 Confirmation time
Set ON/OFF setting time for FMS
signals follow 3.0
H1 18 Reference frequency Follow transducer signal Inherent
H1 19 Rotation direction in fire mode Forward rotation 2
H1 20 Start method Auto search 1
H1 21 Reset interval 3.0
J5 01 External PID Control 1
Enable process control (Normal
operation) 1
J5 02 Remote command selection S.V using keypad 0
J5 03 Feedback selection External PID feedback value 1 51
J5 05
External PID Control 1
(Display unit)
Pascals (Pa) –40
Pascals (kPA) - 41
Set as per C58
J5 06 Maximum scale Set as per C59
J5 07 Minimum scale Set as per C60
J5 10 P (Gain)
Arbitrary Setting –Adjust to suit
application 0.5
J5 11 I (Integral time)
Arbitrary Setting –Adjust to suit
application 0.1
U 00
Customizable Logic
( Mode selection) Enable (Customizable logic operation)
1
U 01
Customizable Logic: Step 1
(Control function)
Analog input
2005
U 02 Input 1 External PID final input (EPID1-out) 8065
U 71
Customizable Logic Output
Signal 1 (Output selection)
Output of step 1
1
U 81
Customizable Logic Output
Signal 1 (Function selection)
Auxiliary frequency command 1
8001
K 10
Main Monitor
(Display item selection)
External PID control 1 command S.V
60
K 16 Sub Monitor 1 External PID Control 1 Feedback P.V 61
K 17 Sub Monitor 2 Output Frequency 1 (K11=1) Hz 0

Ph: 1800 987 616 Email: industrial@cse-uniserve.com.au Website: www.cse-
Notes:
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
__________________________________________________________________________________________________________
CSE Uniserve Technical Services
The CSE Uniserve Technical Services team offers high quaity service and is staffed by factory trained
technicians with formal qualifications in their area of expertise.
The CSE Uniserve Technical Services team offer high quality service and support, is staffed by factory trained
technicians with formal qualifications in their area of expertise and aim to meet and then exceeed our
customer’s expectations.
With a commitment to provide our valued customers with the availability of 24 hour service, our Technical
Services team can deliver:
•Global Onsite Support Services •Repairs & Maintenance •Spare Parts Management
•Compliance Audits •Testing & Commissioning •Planning & Scheduling
•Implementation •Procurement •Supplier & Service Level
Agreements
For all your After Hours Technical Services requirements please call 1300 551 670.
10 Columbia Way
Baulkham Hills NSW 2153
1800 987 616
Email: industrial@cse-uniserve.com.au
Web: www.cse-uniserve.com.au
Table of contents
Popular DC Drive manuals by other brands

Moog
Moog DM2020 Series Installation and startup

Dietz
Dietz DSV 5444 / ML 2 Commissioning instructions

Danfoss
Danfoss VLT DriveMotor FCP 106 operating instructions

Speck pumpen
Speck pumpen BADU Eco Drive II manual

Danfoss
Danfoss VLT HVAC Basic Drive FC 101 Programming guide

Danfoss
Danfoss FC103-110-250Kw operating instructions