CONTENT
Warning 2
I. Brief Introduction 2
II. Electrical Symbol 3
III .Technical Specifications 4
IV. Structure 6
V. Operation Method 6
1. Phase sequencedetection 6
2. Live line detection, simple power detection 7
3. Missingphasejudgment, disconnection search 7
VI. Battery Replacement 8
VII.Accessories 8

-2-
Warning
Thankyou for purchasing our FR2060non-contactphasedetector.In orderto
use this productbetter,please besure to:
—— Read this user manual indetail.
—— Strictly follow thesafety rules and precautions listedin this manual.
uIn anycase,specialcare shouldbe taken whenusing thisinstrument.
uPayattentiontothelabeltextand symbolsoftheinstrumentpanelandback
panel.
uBeforeuse,makesurethattheinsulationoftheinstrument,leads,and clamps
is not damaged, exposed,orbroken.
uNever touch bareexposed wires duringthe test。
uDonotplaceandstoretheinstrumentforalongtime underhightemperature
and humidity,inaplacewith condensation and direct sunlight.
uNotuse the instrument fora longtime, pleaseremove thebattery。
uReplace the battery, pleasepay attention tothe polarity of the battery.
Itisforbiddentoreplacethebatterywhentheclampisnotremoved fromthe
tested line.
uUse,disassembly,andrepairofthisinstrument mustbeperformedby
authorizedpersonnel。
uDuetothereasonofthisinstrument,ifitisdangeroustocontinueusing
it, itshouldbe stopped immediately and sealed immediately, and handledby an
authorizedinstitution.
u“”warningsign ontheinstrument,theuser muststrictly followthe
instructions forsafeoperation.
uThe “”hazard symbol in the manual must be operated safelyby the user
in strict accordance with the instructions.
I. BriefIntroduction
FR2060non-contactphasedetectorisamajorbreakthroughintraditional
phasesequencedetectionmethods.Thetraditionalphasesequencedetectionmust
betoopen the three-phasewire terminal, the phase sequencetable of thethree
exposedclipsortest pinsareconnectedtothe exposedthreefirelines.Ituses
clamp-typenon-contactinductive measurement.It doesnot needtoopen the wire,
and does not needtotouch the high voltageexposed live wire. Itcan directly
detect thephasesequenceby sandwiching thethreesuper induction

-3-
high-insulation clamps to clamp the three-phase live wire insulation sheath.,
It issafe and reliable, andis widely used in electric power,communication,
meteorology, railway,oilfield, construction,measurement,scientificresearch
andteachingunits,industrial andmining enterprisesandotherfields.Atthe
sametime,theacousto-opticindicates thenormalor reversephasestateofthe
phase sequence ofthethree-phasepower supply
Non-contactphasedetector alsohas functionssuchas livelineinspection,
easypowerinspection,open circuitsearch, breakpointlocation,and line
maintenance.。
Non-contact phase detector detects quickly andeasily, shows ata glance,
greatly improves the safety of field tests, effectively protects the personal
safetyofoperators,and increasesproductivity!Itisasafetyinstrumentfor
phasesequence,motordetectionandlinemaintenanceofthree-phasepowersupply!
II. Electrical Symbol
Extremelydangerous!Theoperatormuststrictlyabidebythesafety
rules, otherwise thereisadangerofelectricshock,resultingin
personal injury orcasualtyaccident.
Warning!
Theoperatormuststrictlyabide bythesafetyrules,
otherwise it willcause personal injury or equipmentdamage.
Double insulation
AC
DC

-4-
III .TechnicalSpecifications
Function
Phasedetection(normal phase,reversephase),live line
inspecti
on,simpleelectricity inspection,phaseloss
judgment,circuit breakersearch,breakpointlocation,and
linemaintenance.
Power 9V battery, continuous use time isabout 70 hours.
Measuremode Non-contact clipping method
Wire position The measured wireis in thecenterof thejaw
Frequency 50Hz/60Hz Automatic Identification
Live
electricity
range
AC70~1000V,45/65Hz(Sine wavecontinuousinput),
Conducted
electrostaticdetection
Measuring the
highest voltage
AC1000V
Clamp wire size
Outsidediameter ø1.5mm~ø48mm
Display
【Positivephase】
4phasedetectorlightsareturnedonin
aclockwise direction;
【Reverse phase】
4 4 phase detectionlights areturned on
counterclockwise;
【Live electricity】
L1, L2, L3lightsin the voltagesetting
range;
【Lack of phase】L1 or L2 or L3 lightsare not lit;
【Open circuit】L1orL2orL3lights arenot lit
Beep 【Positive phase】
The instrumentemitsintermittent short
beep;

-5-
【Reverse phase】Theinstrument emitsacontinuouslong beep。
Batterycheck
Afterthepoweristurnedon,thepowerindicatoris on;the
batteryislow; the LOW BATTERY lamp is on。
Clamp lead
length
0.6m
Instrument size
L117.6mm×W81mm×T25mm
Automatic
shut-down
Afterabout6minutesofpower on, themeter automatically
shuts downtoreduce battery consumption.
Battery voltage
When the battery voltage drops to about5.2V, the battery
voltageislow symboltoremind toreplace the battery
Instrument
weight Instrument:260g(including battery)
Maximumrated
power 300mVA
Working
temperature and
humidity
-10℃~55℃;below80%rh
Storage
temperature and
humidity
-20℃~60℃;below90%rh
Insulation
strength 3.7kVrms
Suitable for
Safety
Regulations
EN61010-1:2001、EN61010-031:2002、pollutiongrade2 、
CAT
Ⅲ(600V)、Instantovervoltage 6000V。

-6-
IV. Structure
1. Upper andlower cover screws
2. Batterycover
3. Clampwire indication
4. Clamphandle
5. Power inspection indicatorlight
6. Phasesequence indicatorlight(4)
7. Power indication
8. Lowbatteryvoltageindication
9. Switchbutton
V. Operation Method
1Phase sequencedetection
Danger! There is high pressure! Please pay special attention
to safety!
(1).Detectconnection
Holdthepre-testedthree-phaselinewith three clamps (see picture)。
(2).Thewire to beinspectedisatthe “”markoftheclamp.

-7-
(3).Presstheblack “ONOFF”to turnit on, andthepower indicatoraboveitison. If the
power-on indicatorisoff,thebatterymaybeout ofpower ortheinstrument maybe
checked. Pleasefollow theinstructions in themanualto replace thebattery.
(4).After thepoweris turnedon,ifthefourphasesequence indicatorsare turnedon ina
clockwisedirectionand theinstrument emitsintermittentshortbeeps,theclampphase
lineispositivephasesequence L1-L2-L3 (ie UVW)(leftpicture);If thefourphase
sequence indicatorsare turnedon inthecounterclockwisedirectionandtheinstrument
emits acontinuous long beep,theclampphaselineisreversephasesequence
L3-L2-L1 (ie WVU)(rightpicture).
(5) .Press theblack “ON OFF”button toshut down.Theinstrument willautomatically
shutdownafter about 5minutesofpower ontoreducebatteryconsumption..
2.Live line detection, simplepower detection
Danger!There is high pressure! Please pay special attention to
safety!
(1).Useanyclampto clampthewire tobetested.If thewireis energized(AC70~1000V
withinthelivelinevoltagesetting range),theL1/U,L2/VorL3/Wlampwill beon,and itcan
bedetectedwhether thewire is live.
(2).Clampandlightcorrespondence table
Clampidentification Corresponding lighting symbol
L1/U(yellow)L1/Ulighting
L2/V(green)L2/Vlighting
L3/W(red)L3/Wlighting
3.Phaselossjudgment, open circuit search, breakpoint positioning
Danger!There is high voltage! Please payspecial attention to
safety!
(1).Usethree clamps to clampthethree-phaselineseparately.If there is nophase,theL1,
L2orL3lightswillnot light.。

-8-
(2).Useanyclampto clampthewirealongthelinebeingrepaired. If theclamppointL1, L2
orL3is notlit,thelineisatthelinebreak.Shortenthepositionoftheclamppoint,and
accuratelyfind thelinebreakposition(breakpoint position),whichisveryconvenient and safe
forlineinspection.。
Note:Thisfunction isverysuitable fortheopencircuitfaultin the
maintenance line, safe and fast.!
VI. BatteryReplacement
Pleasepay attentiontobatterypolarity!
1. Beforereplacing thebattery, theclampmust beremovedfrom
thewire tobeinspected. Donotreplace thebatteryduring thetest.
2. Pressthe “ON OFF”buttontoshut down.
3. Loosentheinstrument batterybackcover.
4. Replacewithanewqualifiedbattery, pleasepayattention to the
batterypolarityand specifications(9V6F22model).
5. Closethebatterybackcover.
6. Pressthe “ON OFF”buttontocheckiftheinstrument canbeturnedonnormally. If it
cannotbeturnedon, pleasecheckifthebatterylevelis enoughorfollowstep3to
re-operate.
VII.Accessories
Instrument 1PC
Instrument bag 1PC
Detectorbattery 9VAlkalinebattery1PC
Manual, certificate
1SET
Table of contents
Popular Security Sensor manuals by other brands

AGI
AGI CMC MRS Series Technical manual

System Sensor
System Sensor B114LPBT Installation and maintenance instructions

Mier products
Mier products Drive-Alert DA-606LK quick start guide

Visonic
Visonic SD-304C PG2 installation instructions

Sperian
Sperian MILLER TWIN TURBO User instruction manual

Mini Gadgets
Mini Gadgets CDRFAD user manual