FW Murphy TDX6 User manual

In order to consistently bring you the highest quality, full-featured products, we reserve the right to change our specifications and designs at any time.
FW MURPHY product names and the FW MURPHY logo are proprietary trademarks. This document, including textual matter and illustrations, is copyright
protected with all rights reserved. (c) 2019 FW MURPHY. A copy of our typical warranty may be viewed or printed by going to www.fwmurphy.com/warranty.
sect. 10 00-02-0169
rev. 2019/12/06
TDX 9110N
TDX6 Temperature Scanner/Pyrometer
Installation and Operation Instructions
The TDX6 is an advanced design 6-point temperature
scanner and pyrometer. It continually scans six
groundedtt or ungrounded thermocouples, displays
the temperature of the thermocouple selected and has
adjustable trip points for each input. A trip point read/
scan knob provides for display and check/adjustment of
the thermocouple temperature trip point. If any trip point
is reached, its output turns ON and can be used as a
control signal or to initiate alarms and/or shutdown.
Specifications
Power Requirements (Operating Voltages): 120 VAC or 80-250 VDC,
CD ignition or 24 VDC
Outputs:
Models TDX6-B and TDX6-D:
Six (6) isolated Field-Effect Transistor (F.E.T.) outputs; 0.1 A@ 250 VDC;
switches on (applies ground) above trip point and switches off (removes
ground) below trip point
Operating Temperature: -4 to 158° F (-20 to 70° C)
Storage Temperature: -40 to 300° F (-40 to l50° C)
Case: ABS 1/4 DIN (90 x 90 mm)
Scanning Speed: Complete scan in 30 seconds
Reset Differential:
F.E.T. Models: Decreases 3° F or (C)
Display Update Time: Updates temperature every 0.3 seconds
Start-up Time Delay: Unit is locked out for 10 seconds after ignition
voltage is sensed
Ambient Cold Junction Compensation Range:
2° F from 32° F to 122° F (1° C from 0° C to 50° C )
Measurement Range: Monitor Range 0-1999° F or (C)
Accuracy:
With J-type thermocouple: from 50-150° F (J0-66° C) +3° F ( +2° C),
from 150-1200° F (66-649° C) ±1.0% of reading
With K-type thermocouple: from 400-2000° F (204-1076° C) ±1.0% of
reading
Trip Point Accuracy: ±3° F (±2° C) of reading
Trip Point Adjustment Range: 0-1999 Degrees
Open Thermocouple Input: A number 1 appears in the display to the
right of the channel number and the trip point operates
TDX6 Interface Capabilities
Model Power Source Rating
LCDT CD Ign., 120 VAC, 12/24 VDC C C1.I, Div.1, Gr. D, Haz. areas*
S5101 120 VAC, 12/24 VDC C1.I, Div.1, Gr. D, Haz. areas*
TTD™CD Ign., negative ground, 12/24 VDC C1.1, Div.2, Gr. D, Haz. areas**
TATTLETALE®CD Ign., 120 VAC, 12/24 VDC Non-Hazardous areas
PLC’s and various annunciators not listed, contact factory
*An isolation barrier is needed between the TDX6 and an Annunciator rated for Class I, Division I, Group D, Hazardous Areas.
** When used with approved ignition. Contact FW Murphy Production Controls for details.
tWhen power requirements are used as stated in Specifications section.
tt Using grounded thermocouples introduces the risk of odd currents or voltages being imposed on the thermocouple signal which can affect the accuracy of the reading. This is
an inherent problem of grounded thermocouples, and the reason why we prefer ungrounded thermocouples.
Description
Dimension
Before beginning installation of this product:
• Disconnect all electrical power to the machine
• Make sure the machine cannot operate during installation
• Follow all safety warnings of the machine manufacturer
• Read and follow all installation instructions
Please read the following instructions and warnings before installation. Visually inspect the product for any damage that may have occurred
during shipping. It is your responsibility to have a qualified person install this unit and make sure it conforms to NEC and local codes.
t

Wiring
Even though the TDX6 is a six-channel temperature monitor, it will
monitor and display from 1 to 6 thermocouples with equal results.
When monitoring less than six temperature channels, always jumper
the unused thermocouple terminals on the back of the TDX6 with the
factory-installed jumper provided. The unused channel will display
approximate ambient temperature.
1. Connect the thermocouple leads to the thermocouples. (See
Using Thermocouple Extension Wire for details if extension wire
is needed.) NOTE: Attach wire markers to each thermocouple
lead identifying polarity and thermocouple number.
2. Remove factory-installed jumper on the TDX6 for each
thermocouple to be installed.
3. Connect positive lead of thermocouple TCl to the positive (+)
terminal of terminal strip TCI (see wiring diagram below).
4. Connect negative lead of thermocouple TCI to the negative (-)
terminal of terminal strip TCl.
5. Repeat steps 2 thru 4 with each thermocouple to be monitored.
If the thermocouple leads are not long enough, you will need
to use thermocouple extension wire. Thermocouple exten-
sion wire must be of the same material as the thermocouple
lead wires (see chart). Metallic-shielded thermocouple wire
is recommended. It provides electrical shielding as well as
protection against wear and abrasion.
CAUTION: The use of non-thermocouple wire will cause inaccurate temperature sensing and erratic operation. KEEP ALL HIGH VOLTAGE WIRING
SUCH AS SPARK PLUG OR IGNITION WIRES AWAY FROM THERMOCOUPLES AND EXTENSION WIRING.
Using Thermocouple Extension Wire
Thermocouple Extension Wire Color Code Chart
Thermocouple Wire Color Code / Material
Type P/N Extension P/N Positive Lead Negative Lead
J (I 0-00-0526) Jx (00-00-3271) White/Iron Red/Constantan
K (I 0-00-0527) Kx (00-00-3272) Yellow/Chromel Red/Alumel
To prevent problems of interference from electrical noise, DO NOT route thermocouple wires in the same conduit or within 12 in. (305 mm) of
ignition wires or alternating current conductors. When connecting the thermocouple leads, twist the wire connections, then install wire nuts,
such as ceramic, which have no metal insert.
Operation Test
Connecting Power Wires
1. Be sure power is OFF.
2. Connect the power input leads to the small terminal block locat-
ed on back of the TDX6. (TDX6 connections have no polarity.)
Perform the Operation Test after the TDX6 is installed and wired
appropriately.
1. Slowly rotate each trip point potentiometer clockwise until
detent is felt.
2. Apply power to the monitor.
3. Verify that the TRIP POINT READ knob is in the SCAN mode.
The left side of the display will show the thermocouple number.
The right side of the display will show the temperature of that
thermocouple.
NOTE: When the TRIP POINT READ knob is in the SCAN mode, depressing the
THERMOCOUPLE READ push button will stop the scan sequence at the next chan-
nel and display the thermocouple number and its reading. Scanning will resume
approximately 3 seconds after the push button is released. With TRIP POINT READ
knob selecting a number, the push button should not be depressed.
4. Set the TRIP POINT READ knob to the number 1 setting. On
the right side of the display window, you will see the trip point
reading of the TCI thermocouple. The left side of the display will
continue to scroll 1 to 6 indicating that the unit is still scanning
all channels.
5. Rotate the TPl trip point potentiometer counterclockwise until
trip point TPl turns on and trips the shutdown device or alarm.
Verify by observation.
6. Rotate the trip point potentiometer TPl clockwise several turns
to tum off TPl.
7. Reset alarm or shutoff device.
8. Set TRIP POINT READ knob to the TP2 position to display the
TP2 temperature trip point.
9. Repeat steps 4 thru 7 with each thermocouple to be tested.
Grounded or Ungrounded Thermocouples
1. Apply power to the temperature monitor.
2. Set TRIP POINT READ knob to the 1 position.
3. Rotate the trip point adjustment potentiometer TPI until the dis-
play indicates the desired trip point temperature for TPl.
4. Repeat steps 2 and 3 for each thermocouple to be set. Turn
TRIP POINT READ knob to SCAN position to resume operations.
Trip Point Adjustment
NOTE: We prefer ungrounded thermocouples. Using grounded thermocouples
introduces the risk of odd currents or voltages being imposed on the thermocouple
signal which can affect the accuracy of the reading.
Other FW Murphy Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Tektronix
Tektronix S-4 instruction manual

CDL
CDL 210100U owner's manual

WATANABE ELECTRIC INDUSTRY
WATANABE ELECTRIC INDUSTRY A2200 Series Operation manual

Hubbell
Hubbell CIRCUIT- LOCK HBLDS3P manual

Strainrite
Strainrite Fault Finder manual

Michell Instruments
Michell Instruments Easidew Portable HP user manual

Industrial Fiber Optics
Industrial Fiber Optics IF 535 Instruction guide

DAKOTA ULTRASONICS
DAKOTA ULTRASONICS PVX-B Operation manual

CyberVisuell
CyberVisuell LDW-6093K Operation manual

GLI International
GLI International Accu4 Operating instructions manual

BGS technic
BGS technic 8427 instruction manual

VECTECH
VECTECH 496 Operation manual