
VENTING
1. The Easy Radiant tube system has been approved for vented and un-vented applications.
When installed un-vented it must be electrically interlocked to an exhaust fan with an air
proving switch. The exhaust fan must provide exhaust in the amount of 300 c.f.m. for
every 100,000 BTU input in Canada and the amount of 400 c.f.m. for every 100,000 BTU
input in the USA. When installed un-vented provision must be made to supply adequate
combustion air from outside the space. Combustion air openings must be in the amount
of one (1) square inch or more of free area for each 10,000 BTUH. When installed
vented, installations must comply with all governing codes.
2. When installed in a large and adequately ventilated space (agricultural building used only
for brooding purposes) the heater may be installed un-vented without interlocking, and
may be operated by discharging the combustion products directly into the space, subject
to the approval of the authority having jurisdiction and provided that the maximum input
of the appliance does not exceed 20 BTUH/ft3(0.2 kW/m3) of the space in which the
heater is located. An appliance designed to produce a controlled atmosphere need not be
subject to these conditions.
3. All venting material shall be CGA/AGA approved and minimum 4” diameter.
4. The maximum allowable length of vent pipe is 60 feet. This length includes the
combination of inlet air vent for combustion and exhaust venting. THE RADIANT
TUBE IS NOT INCLUDED IN THE MEASUREMENT. For every 90-degree bend in
the system, 5 feet must be deducted from the total.
5. When venting through a combustible wall or roof, type “B” vent must be used for that
portion of the vent that passed through the wall or roof. For wall venting, the
manufacturer’s approved vent spout or exhaust cap must be used. See page 20. All
models vented through a side wall to be connected to a 4” diameter type “B” or “L” vent.
The maximum equivalent vent length is 30 ft. For each 90 degree elbow 5 ft must be
deducted from the equivalent maximum. The use of any wall vent terminal other than
that supplied by EASYRADIANT will void warranties. EASYRADIANT WORKS
accepts no responsibility for damages created by other vent terminals. Exceeding
the allowable lengths noted may create condensation problems and will void Design
Certification and the heater warranty.
6. All vent pipe used with a slip fit connection must be mechanically secured, and all vents
must be supported every 3 feet.
7. Vent pipe of single wall construction shall not run through unheated spaces unless
insulated.
8. All vent pipes longer than 10 feet must be insulated or have insulated type vent materials.
9. Vents for products of combustion shall not terminate less than three (3) feet from a
combustion air inlet of any other appliance, or be less than three (3) feet from a building
opening or be directly above a gas utility meter or service regulator.
10. The exhaust vent terminal must be installed not less than 7 feet above grade.
11. Air intakes terminals shall not be located less than three (3) feet above grade.