Features
• 5 year warranty
• Damp location rated
AlbeoTM LED Luminaire
Prepare Electrical Wiring
Electrical Requirements
• The LED driver must be supplied with 120-480 VAC, 50/60 Hz per product label and connected to an individual
properly grounded branch circuit, protected by a 15 or 20 ampere circuit breaker.
Grounding Instructions
• The grounding and bonding of the overall system shall be done in accordance with National Electric Code
(NEC) Article 600 and local codes.
BEFORE YOU BEGIN
Read these instructions completely and carefully.
WARNING/AVERTISSEMENT
RISK OF ELECTRIC SHOCK
• Turn power off before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL or IEC approved wire for input/output connections.
Minimum size 18 AWG.
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisez que des ls approuvés par UL ou IEC pour les entrées/sorties de
connexion. Taille minimum 18 AWG.
Save These Instructions
Use only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may cause undesired operation. CAN ICES-3 (A)/NMB-3(A)
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the
interference at his own expense.

ALC5 Fixture Weight
Size 120-277V 347/480V
4 ft. xture 8.5 lbs. 11.5 lbs.
8 ft. xture 17 lbs. 20 lbs.
Attach to
structural
member
Attach to
structural
member
Attach to
structural
member
Attach to
structural
member
Mounting
brackets
Fasten
with nuts
Attach to
structural
member
1
Unit Installation
Choose a mounting method: chain, cable, rod, or surface mount.
2
3
NOTE: Please follow all UL, NEC and minimum load rating
guidelines when selecting and installing a cable, chain, or rod.
Hang two chains/cables from a structural member of the ceiling. Fixture must be supported independently of an outlet
box. Loop chain/cable through the two mounting brackets.
The mounting brackets come pre-installed. Loosen the screws
to move the brackets to a desired location, then re-tighten.
Each mounting bracket can connect to a chain, cable, rod, or
be surface mounted.
Chain or Cable Mounting
Carefully unpack unit and properly inspect for defects before
installing. Wear work gloves to prevent dirt and oil from being
transferred to the luminaire.
Secure two 1/2” threaded rods into structural members in ceiling. Place a nut on each threaded rod where xture should
hang. Slide mounting brackets onto threaded rods and tighten second nut onto rods to secure xture.
Rod Mounting

1 2
Loosen screws to remove endcap. Option: power input from top – Remove knockout
in top and A) install 1/2” conduit, or B) install AC
power cord with strain relief.
Surface Mounting
2
3 4
1Loosen screws on side of xture and unhinge LED
lightbar from xture.
Run power through one of the 0.875” holes in
top of xture and into a junction box. Connect
AC wires from junction box to xture wires (see
Step 4 under Electrical Connections for details).
Reattach lightbar to xture and tighten screws.
Position the two mounting brackets at the ends of
the xture and tighten. Attach the xture to ceiling
using appropriate hardware (not supplied).
Ceiling
Fixture wires
Junction box
Junction box AC line
Open LED lightbar
Move mounting
brackets to ends
Loosen screws
Electrical Connections
Note: Please see additional wiring instructions if installing multiple xtures in a Continuous Run.
A) Conduit B) Power cord

3 4
Option: power input from side – Remove knockout
in endcap and A) Install 1/2” conduit, or B) install
AC power cord with strain relief. Plug unused hole
on top with appropriate tting.
120-277V: Connect the green (ground), black (line)
and white (neutral) wires of the AC line to the
similarly colored wires of the xture’s power supply
using UL listed wire connectors. Re-attach endcap.
347-480V: Connect the green (ground), red (line)
and black (neutral) wires of the AC line to the
similarly colored wires of the xture’s power supply
using UL listed wire connectors. Re-attach endcap.
When ordered as an option, continuous run xtures use quick-connectors and keyhole fasteners to properly
wire and align the joining xtures.
A) Conduit B) Power cord
3 4
Push the quick-connect assembly and excess
wiring into the open end of one xture end plate
so only a small length of wire remains between
joining xtures.
Align keyholes with corresponding tabs and push
xtures together.
Continuous Run Installation
1 2
Completely hang the rst xture in the run. One
end should be closed while the other end has
quick-connect wiring. Using two people, hang the
next xture in the run, making sure to properly
align quick-connectors.
Make all wiring connections between xtures using
the provided quick-connectors.
Closed end
First xture in run
Open end

5 6
7
Shift xtures until keyhole tabs lock in place and
xtures are horizontally aligned.
Install two #8-32 screws with nuts (provided) to
fasten the end plates of the joined xtures together.
Continue to add xtures as needed to complete
the continuous run.
Note: If there are unused quick-connectors at the
end of a run, cut off the connectors and cap the
ends with wire connectors to terminate the wires.
Replace open end plate with a solid end plate.
Note: The current though the continuous xture run
cannot exceed 20A. See maximum xture run length
listed below.
Output
Voltage
Total Run Length (ft.)
T H V
120V 369 234 164
208V 640 406 284
277V 852 540 379
347V 1028 646 463
480V 1239 835 635
Troubleshooting
Symptom Solution
Luminaire will
not turn on
• Check that the color of the supply side wires match the color of the wires they are connected to.
• Check that all wire connectors are properly connected.
• Verify that your input voltage is within specs.
• If you are using any additional controls (i.e. wireless controls or motion sensors), please
also verify that those are working properly and that the unit is setup to interface with the controllers.
Mounting bracket slides
from side to side
• Check that the mounting bracket is properly tightened using the adjustment screws provided.
ALB021-050115
GE Lighting • 1-888-MY-GE-LED (1-888-69-43-533) • www.gelighting.com
GE Lighting Solutions, LLC is a subsidiary of the General Electric Company. The GE brand, logo, and Albeo are trademarks of the General Electric Company.
© 2015 GE Lighting Solutions, LLC. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions.
Table of contents
Popular Lantern manuals by other brands

Winsome house
Winsome house WHSL474 instruction manual

Buki
Buki 9006 quick start guide

MELINERA
MELINERA 317141 Instructions for use

Learning Resources
Learning Resources Primary Science LER 2763 user guide

Saxby Lighting
Saxby Lighting 75271 Instruction leaflet

Philips
Philips WT202W Installation instruction