
Section 7. ProtectionSection 7. Protection
current sensors are required; Entellisys uses thecurrent sensors are required; Entellisys uses the
same current sensors that are provided in eachsame current sensors that are provided in each
breaker cubicle for overcurrent protection andbreaker cubicle for overcurrent protection and
metering functions. The current sensors used inmetering functions. The current sensors used in
Entellisys will permit accurate identification of theEntellisys will permit accurate identification of the
faulted circuit with as little as 1 ampere differencefaulted circuit with as little as 1 ampere difference
between the pulsed current and the ground currentbetween the pulsed current and the ground current
on an 800A frame feeder breaker. The pulsing sys-on an 800A frame feeder breaker. The pulsing sys-
tem can also be operated manually from the HMItem can also be operated manually from the HMI
to faclitate location of a ground fault in equipmentto faclitate location of a ground fault in equipment
downstream of the downstream of the
Entellisys switchgearEntellisys switchgear
Zone Selective Interlocking (ZSI) - short time andZone Selective Interlocking (ZSI) - short time and
The Entellisys system provides a zone-selectiveThe Entellisys system provides a zone-selective
interlocking function similar to that offered in manyinterlocking function similar to that offered in many
electronic trip systems. electronic trip systems.
based ZSI system offers significant improvementsbased ZSI system offers significant improvements
the traditional the traditional
capabilities icapabilities i
the following:the following:
ng with time bandng with time band
Full functionality Full functionality
extra wiring oextra wiring o
on at any programmeon at any programme
d delay for faultsd delay for faults
within a zone of protection.within a zone of protection.
Changing ZSI circuit Changing ZSI circuit
breaker relationsbreaker relations
depending on which mains and ties are closed.depending on which mains and ties are closed.
Delay increments of Delay increments of
100 ms per level 100 ms per level
selectivity and maintain good backup protection.selectivity and maintain good backup protection.
The zones for ground-fault protection are the sameThe zones for ground-fault protection are the same
multi-source multi-source
Within each zone and for each different topology,Within each zone and for each different topology,
the circuit breakers are divided into tiers. Each tierthe circuit breakers are divided into tiers. Each tier
represents the time-delay hierarchy required torepresents the time-delay hierarchy required to
optimum protecoptimum protec
selectivity. Eacselectivity. Eac
circuit breaker may be assigned to one of four tierscircuit breaker may be assigned to one of four tiers
within a zone. The top tier is always labeled tier 0.within a zone. The top tier is always labeled tier 0.
Next is tier 1, then tier 2, with the last and lowestNext is tier 1, then tier 2, with the last and lowest
defined as tier 3. Hence, in a simple radial two-tierdefined as tier 3. Hence, in a simple radial two-tier
system, the feeders are labeled tier 1 and the mainsystem, the feeders are labeled tier 1 and the main
For substations that are operated with the tieFor substations that are operated with the tie
normally-open, the tie and the mains could be setnormally-open, the tie and the mains could be set
tier 0. This witier 0. This wi
ll allow the ll allow the
tie and the mains tie and the mains
operate at minimum (or set) delay for a fault in theiroperate at minimum (or set) delay for a fault in their
zone of protection or feeder set delay plus 100mszone of protection or feeder set delay plus 100ms
if the fault is below a feeder. If the substation is runif the fault is below a feeder. If the substation is run
from one transformer with the tie closed it may befrom one transformer with the tie closed it may be
preferable to set the tie at tier 1 and the mains atpreferable to set the tie at tier 1 and the mains at
tier 0 to achieve tie to main selectivity.tier 0 to achieve tie to main selectivity.
How short-time ZSI worksHow short-time ZSI works
In the Entellisys ZSI model, the highest-level mainIn the Entellisys ZSI model, the highest-level main
circuit breaker is labeled tier 0. So in a simple double-circuit breaker is labeled tier 0. So in a simple double-
ended substation, the mains are each tier 0, the tieended substation, the mains are each tier 0, the tie
is tier 1, and the feeders are all tier 2. In the followingis tier 1, and the feeders are all tier 2. In the following
explanation, the terms lower- or higher-numberedexplanation, the terms lower- or higher-numbered
tier indicate in which direction the action is intended.tier indicate in which direction the action is intended.
Whenever the CPU detects that a breaker in oneWhenever the CPU detects that a breaker in one
or more of the defined ZSI zones has gone into STor more of the defined ZSI zones has gone into ST
pickup, it performs the following actions:pickup, it performs the following actions:
1. Based on the tier to which the circuit breaker1. Based on the tier to which the circuit breaker
belongs, it sets the short-time delays for allbelongs, it sets the short-time delays for all
breakers with the next-lower tier number to thebreakers with the next-lower tier number to the
short-time delay time of the circuit breaker inshort-time delay time of the circuit breaker in
pickup plus 100ms. Thus a breaker with a tierpickup plus 100ms. Thus a breaker with a tier
number of 2 sets the short-time delays of thenumber of 2 sets the short-time delays of the
breakers with tier number 1. Note that a breaker,breakers with tier number 1. Note that a breaker,
for example a tie, can reside in multiple zones.for example a tie, can reside in multiple zones.
However unless a circuit breaker is detecting faultHowever unless a circuit breaker is detecting fault
current, it will not trip regardless of tier setting.current, it will not trip regardless of tier setting.
2. Each circuit breaker whose short-time delay2. Each circuit breaker whose short-time delay
setting was changed in step 1, sets the short-timesetting was changed in step 1, sets the short-time
delays for all delays for all
with the nextwith the next
tier number to the new delay, plus 100ms. Fortier number to the new delay, plus 100ms. For
example; each tier 1 breaker whose short-timeexample; each tier 1 breaker whose short-time
delay was changed will, in turn, change thedelay was changed will, in turn, change the
short-time delay for tier 0 breakers in the sameshort-time delay for tier 0 breakers in the same
zone (or zones) by adding 100ms to its ownzone (or zones) by adding 100ms to its own
delay and making that the new tier 0 delay.delay and making that the new tier 0 delay.
3. Continue this process of changing the short-time3. Continue this process of changing the short-time
in the zone witin the zone wit
lower-tier number until tier 0 is reached. (Tier 0lower-tier number until tier 0 is reached. (Tier 0
breakers are typically mains.)breakers are typically mains.)
4. All modifi4. All modifi
ed short-time delays ed short-time delays
of the breakersof the breakers
the zone are set to their original values, after allthe zone are set to their original values, after all
short-time elements cool off completely.short-time elements cool off completely.
It should be noted that the ZSI system never lowersIt should be noted that the ZSI system never lowers
the time delay of a circuit breaker, but only increasesthe time delay of a circuit breaker, but only increases
the delays of circuit breakers with lower tier numbersthe delays of circuit breakers with lower tier numbers
than the breaker for which the short-time faultthan the breaker for which the short-time fault
current was identified by the CPU within the samecurrent was identified by the CPU within the same
zone. The time delay of a circuit breaker is neverzone. The time delay of a circuit breaker is never
increased past a maximum time delay of 400ms.increased past a maximum time delay of 400ms.
How ground-fault ZSI worksHow ground-fault ZSI works
The algorithm for ground-fault protection is theThe algorithm for ground-fault protection is the
same as short-time ZSI, except for multi-sourcesame as short-time ZSI, except for multi-source