GENTRON GG10020C User manual

www.jdna.com
1-888-896-6881

10000W Generator
Topic Page
3ytnarraWdetimiL
5senilediuGytefaS
6snoituacerPlareneG
Battery 15
Assembly 16
Spark Plug Service 22
Operation 17
Inspection, Cleaning, Maintenance and Storage 23
Installation 29
Compliance 31
Specifications 32
33gnitsiLstraPlareneG
2

Gentron/UPC
Gentron/UPC will repair or replace, at Gentron/UPC’s sole option, products or components which have
failed within the warranty period. Service will be scheduled according to the normal work flow and
business hours at the service center location, and the availability of replacement parts. All decisions of
Gentron/UPC with regard to this limited warranty shall be final.
This warranty gives you specific legal rights, and you may also have other rights which vary from
state to state.
RESPONSIBILITY OF ORIGINAL PURCHASER (initial User):
To process a warranty claim on this product, DO NOT return item to the retailer. The product must
be evaluated by an Authorized Warranty Service Center. For the location of the nearest Authorized
Warranty Service Center contact the retailer or place of purchase.
Retain original cash register sales receipt as proof of purchase for warranty to work.
Use reasonable care in the operation and maintenance of the product as described in the Owner’s
Manual(s).
Deliver or ship the product to the Authorized Warranty Service Center. Freight costs, if any must be
paid by the purchaser. If the purchaser does not receive satisfactory results form the Authorized
Warranty Service Center, the purchaser should contact toll free 800-894-1179.
THIS WARRANTY DOES NOT COVER:
Merchandise sold as reconditioned, used as rental equipment, or floor or display models.
Merchandise that has become damaged or inoperative because of ordinary wear, misuse, cold, heat,
rain, excessive humidity, freeze damage, use of improper chemicals, negligence, accident, failure to
operate the product in accordance with the instructions provided in the Owner’s Manual(s) supplied
with the product, improper maintenance, the use of accessories or attachments not recommended
by Gentron/UPC, or unauthorized repair or alterations.
• Repair and transportation costs of merchandise determine not to be defective.
•Costs associated with assembly, required oil, adjustments or other installation and start-up costs.
Expendable parts or accessories supplied with the product which are expected to become inoperative
or unusable after a reasonable period of use.
( Example: Battery, Spark Plug, Air Filter)

10000W Generator
Merchandise sold by Gentron/UPC which has been manufactured by and identified as the product of another
company, such as gasoline engines. The product manufacturer’s warranty, if any, will apply.
ANY INCIDENTAL, INDIRECT OR CONSEQUENTIAL LOSS, DAMAGE, OR EXPENSE THAT MAY RESULT
FROM ANY DEFECTS, FAILURE OR MALFUNCTION OF THE PRODUCT IS NOT COVERED BY THIS
WARRANTY. Some states do not allow the exclusion, so it may not apply to you.

5
Owner’s Manual
Safety Guidelines - Definitions
This manual contains important information that you need to know and
understand in order to protect YOUR SAFETY and to PREVENT
EQUIPMENTPROBLEMS.Thefollowingsymbolshelpyourecognizethis
information. Please read the manual and pay attention to these sections.
Save These Important Safety Instructions!
Readandunderstandallofthesesafetyinstructions.Be
sure to retain them for future use.
WARNING! WARNINGS INDICATE A CERTAINTY OR STRONG
POSSIBILITYOFPERSONALINJURYORDEATHIF
INSTRUCTIONS ARE NOT FOLLOWED.
CAUTION: CAUTIONS INDICATE A POSSIBILITY OF
EQUIPMENT DAMAGE IF INSTRUCTIONS ARE NOT
FOLLOWED.
NOTE: NOTES GIVE HELPFUL INFORMATION
WARNING! IMPROPER OPERATION OR MAINTENANCE
OFTHISPRODUCTCOULDRESULTINSERIOUSINJURY
AND PROPERTY DAMAGE. READ AND UNDERSTAND ALL
WARNINGS AND OPERATING INSTRUCTIONS BEFORE USING
THIS EQUIPMENT. WHEN USING AIR TOOLS, BASIC SAFETY
PRECAUTIONS SHOULD ALWAYS BE FOLLOWED TO REDUCE
THERISKOFPERSONALINJURY.

6
10000WGenerator
WARNING! THE EXHAUST CONTAINS POISONOUS CARBON MONOXIDE
GAS THAT CAN CAUSE LOSS OF CONSCIOUSNESS AND MAY LEAD TO
DEATH.
Gasoline and Oil
This product requiresoil and fuel. Attempting to start the enginewithout oilwill ruin
the engine and void the warranty. Work in well ventilated area. Keep cigarettes,
flames or sparks away fromthe work area or wheregasoline is stored.
WARNING! GASOLINE IS EXTREMELY FLAMMABLE AND IS EXPLOSIVE
UNDER CERTAIN CONDITIONS. KEEP OUT OF REACH OF CHILDREN.
• Gasoline fuel and fumes are flammable and potentially explosive. Use proper fuel storage and
handling procedures. Always have multiple ABC class fire extinguishers nearby.
General Precautions
WARNING! FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN
SEVERE INJURY OR DEATH.
CAUTION: FAILURE TO FOLLOW THESE INSTRUCTIONS CAN ALSO
RESULT IN DAMAGE TO THE TOOL AND/OR THE ITEM YOU ARE WORKING
ON.
DANGER
CARBON MONOXIDE
Using a generator indoors WILL KILL YOU IN MINUTES.
Generator exhaust contains high levels of carbon monoxide (CO), a poisonous gas you cannot
see or smell. If you can smell the generator exhaust, you are breathing CO. But even If you
cannot smell the exhaust, you could be breathing CO.
· NEVER use a generator inside homes, garages, crawlspaces, or other partly enclosed areas.
Deadly levels of carbon monoxide can build up in these areas. Using a fan or opening windows
and doors does NOT supply enough fresh air.
· ONLY use a generator outdoors and far away from open windows, doors, and vents. These
openings can pull in generator exhaust.
Even when you use a generator correctly, CO may leak into the home. ALWAYS use a battery-
powered or battery-backup CO alarm in the home.
If you start to feel sick, dizzy, or weak after the generator has been running, move to fresh air
RIGHT AWAY. See a doctor. You could have carbon monoxide poisoning.
• Keepthegenerator and surrounding area clean at alltimes.

Owner’s Manual
7
General Precautions (cont’d)
Gasoline and Oil (cont’d)
• Do not smoke, or allow sparks, flames or other sources of ignition around the engine and fuel
tank. Fuel vapors are explosive.
• Keep grounded conductive objects, such as tools, away from exposed, live electrical parts and
connections to avoid sparking or arcing. These events could ignite fumes or vapors.
• Do not refill the fuel tank while the engine is running or while the engine is still hot. Do not
operate the generator with known leaks in the fuel system
• Excessive buildup of unburned fuel gases in the exhaust system can create a potentially
explosive condition. This buildup can occur after repeated failed start attempts, valve testing, or
hot engine shutdown. If this occurs, open exhaust system drain plugs, if equipped, and allow the
gases to dissipate before attempting to restart the generator.
• Use only engine manufacturer recommended fuel and oil.
Hot Components
WARNING! ENGINE AND EXHAUST SYSTEM PARTS BECOME VERY
HOT AND REMAIN HOT FOR SOME TIME AFTER THE ENGINE IS RUN. WEAR
INSULATED GLOVES OR WAIT UNTIL THE ENGINE AND EXHAUST SYSTEM
HAVE COOLED BEFORE HANDLING THESE PARTS.
Power Output
This generator is not designed to power sensitive electronic equipment (including computers
and medical devices) without the addition of an approved line conditioner, which is sold separately.
CAUTION: ATTEMPTING TO POWER SENSITIVE ELECTRONIC EQUIPMENT
WITHOUT THE USE OF AN APPROVED LINE CONDITIONER MAY CAUSE
DAMAGE TO THE EQUIPMENT. GENTRON/UPC IS NOT RESPONSIBLE
FOR ANY DIRECT OR INDIRECT DAMAGE CAUSED BY FAILURE TO USE AN
APPROVED LINE CONDITIONER.
• Fuel or oil spills must be cleaned up immediately. Dispose of fluids and cleaning materials as per
any local, state, or federal codes and regulations. Store oily rags in a covered metal container.
• Never store fuel or other flammable materials near the generator.
Fuel:
Fuel capacity is 8 gallons(30 L). Use regular
unleaded gasoline with a minium octane rating of 90.
Oil:
Oil capacity is 1.16 qt(1.1 L)

8
10000WGenerator
General Precautions (cont’d)
Work Area
• Keep your work area clean and welllit. Cluttered benches and dark areas invite accidents.
• Do not operate power tools in explosive atmospheres, such as in the presence of flammable
liquids, gases,ordust.Generators create sparkswhich may ignite thedust or fumes.
• Keep bystanders, children, and visitors away while operating a generator. Provide barriers or
shields as needed.
Electrical Safety
• Grounded tools must be plugged into an outlet properlyinstalledand
grounded in accordance with all codes and ordinances. Never remove the
grounding prong or modify theplug in any way. Do not use any adapter
plugs.
• Grounding provides a low-resistance path to carry electricity away from the
user in the event of an electrical malfunction.
• Double insulated tools are equipped with a polarized plug where one blade is wider than the
other. This plug fits in a polarized outlet only one way. If the plug does not fit fully in the outlet,
reverse the plug. If it still does not fit, contact a qualified electrician to install a polarized outlet.
Do not change theplug in any way. Doubleinsulation eliminates the need for the three-wire
grounded power cord and grounded power supply system.
• Avoid body contact with grounded surfaces such as pipes, radiators, ranges, and refrigerators.
There is an increasedrisk of electric shock if your body is grounded.
• Do not expose generator to rain or wet conditions. Water entering a generator will increase the
risk of electricshock.
• Do not abuse the power cord. Keep power cords away from heat, oil, sharp edges, or moving
parts. Replace damaged power cordsimmediately. Damaged power cords increase the risk of
electric shock.
• When operating a power tool outside, use an outdoor extension cord marked “W-A” or “W”.
These extension cords are rated for outdoor use, and reduce the risk of electricshock.

9
Owner’s Manual
General Precautions (cont’d)
Electrical Safety (cont’d)
• All connections and conduits from the generator to the load must only be installed by trained and
licensed electricians, and in compliance with allrelevantlocal,state,andfederalelectrical
codes and standards, and other regulations where applicable.
• The generator must be earth-grounded for fixed installations in accordance with all relevant
electricalcodesandstandardsbeforeoperation.
•Donotattempttoconnectordisconnectloadconnectionswhilestandinginwater,oronwetor
soggy ground.
•Donottouchelectricallyenergizedpartsofthegeneratorandinterconnectingcablesor
conductorswithanypartofthebody,orwithanynon-insulatedconductiveobject.
•Connectthegeneratoronlytoaloadorelectricalsystem(120volt)thatiscompatiblewiththe
electrical characteristics and rated capacities of the generator.
• Before servicing equipment powered by the generator, disconnect the equipment from its power
input.
•Keepallelectricalequipmentcleananddry.Replaceanywiringwheretheinsulationiscracked,
cut abraded or otherwise degraded. Replace terminals that are worn, discolored, or corroded.
Keep terminals clean and tight.
• Insulate all connections and disconnected wires.
•Guardagainstelectricshock.Preventbodycontactwithgroundedsurfacessuchaspipes,
radiators, ranges, and refrigerator enclosures.
Personal Safety
•Stayalert.Watchwhatyouaredoing,andusecommonsensewhenoperatingagenerator.Do
notusegeneratorwhiletiredorundertheinfluenceofdrugs,alcohol,ormedication.Amoment
of inattention while operating generators may result in serious personal injury.
•Dressproperly.Donotwearlooseclothingorjewelry.Containlonghair.Keepyourhair,clothing,
andglovesawayfrommovingparts.Looseclothes,jewelry,orlonghaircanbecaughtin
moving parts.

10000WGenerator
General Precautions (cont’d)
Personal Safety (cont’d)
• Avoid accidental starting. Make sure the power switch is in its “OFF” position, and disconnect
the sparkplugwirewhen not in use.
• Remove adjusting keys or wrenches before turning the generator on. A wrench or a key that is
left attached to a rotating part of thegenerator may result in personalinjury.
• Do not overreach. Keep proper footing and balance at all times.
• Use safety equipment. Always wear eye protection. Wear ANSI approved safety impact eye
goggles. Dust mask, non-skid safety shoes, hard hat, or hearing protection must be used for
appropriate conditions.
• Do not force the generator. Use the correct generator for your application. The correct generator
willdothejob better and safer at the rate for which it is designed.
• Do not use the generator if the power switch does not turn it on or off. Any generator that cannot
be controlledwiththe power switch is dangerous and must be replaced.
Generator Use andCare
Make sure the power switch is in its “OFF” position and disconnect the spark plugwire before
making any adjustment, changing accessories, or storing thegenerator. Such preventive safety
measures reduce the risk of starting thegenerator accidentally.
Store idle generators out of reach of children and other untrained persons. Generators are
dangerous in the hands of untrained users.
Maintain generators with care. Do not use damaged generator. Tag damaged generators “Do not
use” until repaired.
Check for misalignment or binding of moving parts, breakage of parts, and any other condition that
may affect the generator’s operation. If damaged, have the generator serviced before using. Many
accidents are caused by poorlymaintainedgenerators.
Use only accessories that are recommended by the manufacturer for your model. Accessories that
may be suitable for one generator may become hazardous when used on another generator.
10

Owner’s Manual
General Precautions (cont’d)
Servicing
Maintain labels and name plates on the generator and engine. These carry important information.
If unreadable or missing, contact our service center toll free at 800-894-1179 immediately for a
replacement.
Generator service must be performed only qualified repair personnel. Service or maintenance
performed by unqualified personnel could result in a risk of injury.
When servicing a generator, use only identical replacement parts. Follow all appropriate
instructions in this manual. Use of unauthorized parts or failure to follow maintenance instructions
may create a risk of electric shock or injury.
Heart Pacemakers
WARNING! PEOPLE WITH PACEMAKERS SHOULD CONSULT THEIR
PHYSICIAN(S) BEFORE USING THIS PRODUCT. ELECTROMAGNETIC
FIELDS IN CLOSE PROXIMITY TO A HEART PACEMAKER COULD CAUSE
INTERFERENCE TO OR FAILURE OF THE PACEMAKER.
Installation
• Ensure installation meets all applicable safety, and local and national electrical codes. Have
installation performed by a qualified, licensed electrician and building contractor.
• All electrical work, including the earth-ground connection, should be completed by a licensed
electrician.
• Any separate fuel storage or generator supply facility must be built or installed in full compliance
with all relevant local, state, and federal regulations.
11

12
10000W Generator
General Precautions (contíd)
Installation (contíd)
• If the generator is installed outdoors, it must be weatherproofed and should be soundproofed. It
should not be run outdoors without protection to the generator and wiring conduit.
• The generator weighs 220lbs(approx). Two or more people should assist when moving or lifting
this product. Never lift the generator using the engine or alternator lifting lugs. Connect lifting
equipment to the frame of the generator
• Before lifting the generator, ensure the lift rigging and supporting structure are in good
condition, and are rated to lift suchaload.
• Keep all personnel away from the suspended generator during relocating.
• The supporting floor/ground surface should be level and strong enough to safely hold the weight
of the generator. If thefloor/grounded surface is not level, strong cross members should be
placed under the full length of the generator frame at its low side.
• For trailer installation, the generator should be mounted on the center point of the trailer, over
the wheels. The trailer must be capable of supporting the weight of the generator and all
contents(tools, etc.)
• Install sound-and weather-proofing only when it is not raining or snowing to avoid trapping
moisture within the generatorís area.
Mechanical
• Always make sure the power switch is in its ì OFFî position. Disconnect the spark plug wire, and
allow the engine to completely cool before carrying out maintenance.
• Check for damaged parts. Before using the generator, any part that appears damaged should
be carefully checked to determine that it will operate properly and perform its intended function.
Check for alignment and binding of moving parts, any broken parts or mounting fixtures, and any
other condition that may affect proper operation technician.
• The generator is designed with guards for protection from moving parts. In any case, care must
still be taken to protect personnel and equipment from other mechanical hazards when working
around the generator.

Owner’s Manual
General Precautions (cont’d)
Mechanical (cont’d)
• Do not operate the generator with safety guards removed. While the generator is running, do not
attempt to reach around the safety guard for maintenance or any other reason.
• Keep hands, arms, long hair, loose clothing, and jewelry away from moving parts. Be aware that
when engine parts are moving fast they cannot be seen clearly.
• Keep access doors on enclosures closed and locked when access is not required.
• When working on or around the generator always wear protective clothing including ANSI
approved safety gloves, safety eye goggles, and safety hat.
• Do not alter or adjust any part of the generator that is assembled and supplied by the
manufacturer.
• Always follow and complete scheduled engine and generator maintenance.
Chemicals
• Avoid contact with hot fuel, oil, exhaust fumes, and hot solid surfaces.
• Avoid body contact with fuels, oils, and lubricants used in the generator. If swallowed, seek
medical treatment immediately. Do not induce vomiting if fuel is swallowed. For skin contact,
immediately wash with soap and water. For eye contact, immediately flush eyes with clean water
and seek medical attention.
Noise
• Prolonged exposure to noise levels above 55 DBA is hazardous to hearing. Always wear ANSI
approved ear protection when operating or working around the generator when it is running.
13

10000WGenerator
General Precautions (cont’d)
Extension Cord
If an extension cord (not included) is used, make sure to use only UL approved cords having the
correct gauge and length according to the following table:
Cord LengthsNameplate Amps (@ full load)
0 - 5
16 16 12 12
5.1 - 8
16 14 10 -
8.1 - 12
14 12 - -
12.1 - 15
12 10 - -
15 - 20
10 10 - -
14
0 ft.- 50 ft. 50 ft.-100 ft. 100 ft.-150 ft. 150 ft.-200 ft.
AWG AWG
AWG
AWG
AWG
AWG
AWG
AWG
AWG
AWG
AWG
AWG
AWG

Owner’s Manual
15
Battery
To start generator with electric start you will need a battery (not included). You can use a 12v lawn
tractor battery with the following specifications: The dimensions are Wx3” Dx7.1” Hx6.4” (including
terminals). A rated cranking amperage of 200. Terminals are regular, not reversed. Note: Using a
battery not designed for this unit may void warranty. Also this generator can also be started with
the pull start.
Photos below demonstrate battery plate attachment.
Please have the battery assembled with the provided accessories as shown.

10000W Generator
16
Assembly
Unpacking
1. Remove the generator and loose parts box from the carton.
2. Compare the accessory with the inventory list below.
Loose Parts (Wheel kit and handle)
Check all loose parts against the following list. Contact your dealer toll free at 800.894.1179
if any of the loose parts shown are not included with your generator
Hardware Check:
Your Hardware Kit should include:
1) Two Handles with bolts, nuts, pin with chain and brackets
2) One axle shaft with bolts and nuts
3) Two washers
4) Two cotter pins
5) One generator leg with bolts and nuts
6) Two wheels
3
4
2
5
1
6

17
Owner’s Manual
Operation
NOTE: THE PARTS LISTED ABOVE ARE HELPFUL FOR LOCATING THE
CONTROLS MENTIONED BELOW.
CAUTION: PRIOR TO FIRST USING THE GENERATOR, THE ENGINE MUST BE
FILLED WITH OIL OF A HIGH QUALITY SAE 10W-30 GRADE ENGINE OIL.
TO DO SO, UNSCREW AND REMOVE THE ENGINE’S OIL DIPSTICK LOCATED
AT THE BOTTOM OF THE ENGINE CRANKCASE. FILL THE ENGINE’S
CRANKCASE UNTIL THE OIL LEVEL IS LEVEL WITH THE UPPER MARKED
LINE ON THE DIPSTICK. THEN SCREW THE DIPSTICK BACK INTO
THE OIL FILL HOLE.
Before Starting the Generator
1. Check that the engine power switch is in its
Fuel tank capacity:30L(8 gallons)
“OFF” position.
2. Before the first use, remove the fuel
tank cap and fill the fuel tank with unleaded
gasoline. When fueling, be sure that the
fuel strainer is in place. Replace the fuel
tank cap. Thereafter, check the engine’s
fuel gauge for the amount of unleaded
gasoline in the fuel tank. If necessary,
refill the fuel tank with unleaded gasoline;
the generator must be turned off and
cooled down before refilling the fuel tank.
Use gasoline with a pump octane rating of 90 or higher.
We recommend unleaded gasoling because it produces
fewer engine and spark plug deposits and extends
exhaust system life.
Never use stale or contaminated gasoline or oil/gasoline
mixture. Avoid getting dirt or water in the fuel tank.
Battery
Handle
Control Panel
Oil plug
Recoil Start
Air filter
Choke lever

18
10000W Generator
Operat ion (cont’d)
Starting
1. Turn the engine switch to t he “RUN” positio n.
The engine switc h enables and disables the ignition
system.
STOP: To stop the engine
RUN: To run the engine
2. The fuel valve is located under the fuel tank . When
the valve lever is in the ON position , fuel is allowed
to flow from the fuel tank to the carburetor. Be sur
to return the fuel valve lever to the OFF position after
stoppi ng the engine.
STOP
RUN
ON
OFF
3. To start a cold engine, move the choke lever to th e
CLOSED position. To restart a warm engine, leave the
choke lever in the OPEN position.
The choke lever opens and closes the choke valve in
the carburetor.
The CLOSED position enric hes the fuel mixture from
starting a cold engine.
The OPEN position provides the correct fuel mixture
for operation after starting, and fo r restarting a warm
engine.

ON
OFF
19
Operatio n (cont’d)
Starting
Stop pi ng Engin e
4. Operate the Recoil Start:
Pull the starter grip lightly until you feel resistance,
then pull briskly. Return the starter grip gently.
Pulling the starter grip operates the recoil start to
crank the engine
Operate the Electric start:
Push and hold the engine switch on the “START”
position for 3~5s and crank the engine.
5. If the choke has been moved to the “Start” po sition
to start the engine, gradually move it to the “RUN”
position as the engine warms up.
1. Turn the engine switch to the “STOP” position.
2. Turn the fuel valve lever to the “ OFF” positio n.
When the engine is not in use, leave the fuel valve in
the “OFF” position to prevent carburetor flooding
and to reduce the possibility of fuel leakage.
S tarterGrip
Owner’s Manual
STOP

20
Operation (cont’d)
Powering 120 Volt AC Tools And Equipment:
1. Prior to powering tools and equipment, make sure the generator’s rated voltage, and amperage
capacity (120 V AC @ 66.7 AMPs) is adequate to supply all electrical loads that the unit will
power. If powering exceeds the generator’s capacity, it may be necessary to group one or more
of the tools and/or equipment for connection to a separate generator.
CAUTION: ATTEMPTING TO POWER SENSITIVE ELECTRONIC EQUIPMENT
WITHOUT THE USE OF AN APPROVED LINE CONDITIONER MAY CAUSE
DAMAGE TO THE EQUIPMENT. GENTRON/UPC PRODUCTS ARE NOT
RESPONSIBLE FOR ANY DIRECT OR INDIRECT DAMAGE CAUSED BY FAILURE
TO USE AN APPROVED LINE CONDITIONER.
2. Once the generator is running, simply connect the power cords of 120 volt AC powered
tools and equipment into the 120 volt AC dual outlets.
NOTE: THE GENERATOR FEATURES AN AC NON-FUSE THERMAL PROTECTOR
TO PROTECT THE AC CIRCUIT IN CASE OF AN OVERLOAD. SHOULD
AN OVERLOAD OCCUR, THE BREAKER WILL POP.
3. Disconnect all electrical powered tools and equipment from the generator’s 120 volt AC
duel outlets.
4. After the engine and generator have completely cooled, store generator in a safe, clean, dry
location (if not already installed).
10000W Generator
Table of contents
Other GENTRON Portable Generator manuals

GENTRON
GENTRON 1200W Generation User manual

GENTRON
GENTRON Pro2 GG7500 User manual

GENTRON
GENTRON GG12000GL User manual

GENTRON
GENTRON 950W Series User manual

GENTRON
GENTRON 2000W Digital Generator User manual

GENTRON
GENTRON GG3500P User manual

GENTRON
GENTRON GG10020 User manual

GENTRON
GENTRON PRO2 Series User manual

GENTRON
GENTRON GG3500D User manual

GENTRON
GENTRON G6000LPG User manual