
9
6. CONTROLLER SETTINGS
Menu Description Factory setting and
(max. / min values
A1 - Reheating If there is a reheater fitted to the system, you can choose if the
reheater should operate. If the set point is set to OFF, the heater will
not operate, even when this is necessary. If the set point is set to ON,
the heater will start, as required. It regulates in ac-cordance with the
temperature set in item 1 of the User Menu.
A1: Off
(On - Off)
A2 - Humidity
control
Here you turn on humidity control. It must be set to ON in order to be
active.
A2: Off
(On/Off)
A3 – DHW
temperature
Here the domestic hotwater temperature controlled by the heatpump
can be set. The temperature setpoint is related to the bottom
temperature sensor of the DHW cylinder
A3: 52 °C
(0-60 °C)
A4 – DHW element Here the domestic hotwater temperature controlled by the electrical
immersion heater can be set. The temperature setpoint is related to the
temperature sensor located in the middle of the DHW cylinder.
A4: 50 °C
(0-65 °C)
A5 - Boost time Set the desired time for temporarily increased fan speed, activated via
the boost button on the main display.
A5: 30 min
(1 - 120 min)
A6 - Timer levels 3
and 4
- on/off
When switching the ventilation unit to fanspeed 3 and 4, the system
will automatically return to fanspeed 2 after the number of hours set
in A5 when adjusting this set point to ON. If the set point is set to OFF,
the system will run at speed 3 or 4 until the fanspeeds are manually
changed.
A6 : Off (On - Off)
A7 - Timer levels 3
and 4 - hours
If A6 is set to on , you can enter how many hours the system should run
on level 3 or 4 before it automatically returns to level 2.
A7: 3 hours
(1 - 9 hours)
B1- Fan scheduler Here four seperate timers per day can be set for change of fanspeeds.
The scheduler can be adjusted seperately for each weekday if required.
If the same values shall be used for all weekdays - the schedule can be
copied by touching the button "apply to all days"
B1: Not used
(Not used / level 1-4 /
Standby)
B2 - Temperature
scheduler
Here four seperate timers per day can be set for change to a low-ered
setpoint temperature (eg. for earlier opening of bypass in summertime
in nighttime). The scheduler can be adjusted seper-ately for each
weekday if required. If the same values shall be used for all weekdays -
the schedule can be copied by touching the button "apply to all days"
B2: Not used
(Not used /
Alternative temp (B5)
/ Normal)
B3 – DHW scheduler Here four seperate timers per day can be set for change to a low-
ered setpoint temperature. The scheduler can be adjusted seperately
for each weekday if required. If the same values shall be used for all
weekdays - the schedule can be copied by touching the button "apply to
all days"
B3: Not used /
Alternative DHW temp
(B6) / Normal