Operation limits
2003 Max current
Setup the max allowed current. In many cases this is the same
as indicated on the motor nameplate. For example 2,6A
2007 Minimum freq
Setup minimum allowed frequency. Set at 15Hz. If set lower,
both fan and inverter may suffer damage.
2008 Maximum freq
Set maximum frequency.
Set maximum allowed frequency for the selected fan.
9905 Motor nom volt
9906 Motor nom curr
9907 Motor nom freq
9908 Motor nom speed
9909 Motor nom power
Setup the motor´s rated voltage as indicated on the motor
nameplate. For exampel 400V
Setup the motor´s rated current as indicated on the motor
nameplate. For exampel 2,6A
Setup the motor´s rated frequency as indicated on the motor
nameplate. For exampel 50Hz
Setup the motor´s rated speed as indicated on the motor
nameplate. For exampel 2830 rpm
Setup the motor´s rated power comsumption as indicated on
the motor nameplate. For exampel 4Kw
Motor data setup