GEZE E 260 N4 User manual

grn
rot
rot blinkend
Notstromsteuerzentrale
Emergency Power Control System
E 260 N
O
Störung
Netzausfall
O
Fault
Power outage
grün
gelb
gelb blinkend
green
yellow
yellow flashing
Installation and Operating Manual
RWA-Emergency Power Control System
E260 N2/N4/N8/N12
GB Id. No. 113959-04
DE Material-Nr. 104361 IT N. mat. 113961
FR N° de suite 113960

2
Symbols and conventions
Danger and information symbols
Conventions within the text
•Enumeration mark
➮Introduces an action to be executed
Multi-stage activities are numbered:
1. First activity
2. Second activity
3. ...
DANGER
Indication of danger which can lead to death or injury.
Indication of danger which can lead to material damages.
Tips for optimum working.

3
Contents
1 Operation ............................................................................................................. 4
1.1 Safety instructions for the operator and the user .................................................... 4
1.2 Overview of the RWA-Emergency Power Control System ...................................... 5
1.2.1 The electrical components of the RWA-Emergency Power Control System ........... 6
1.2.2 Components for ventilation operation ...................................................................... 8
1.2.3 Components used in the case of alarm ................................................................... 8
1.3 Ventilation operation ................................................................................................ 9
1.4 Fire alarm .............................................................................................................. 10
1.5 Power outage and fault ......................................................................................... 13
1.6 What to do when …? ............................................................................................. 14
2 Installation and maintenance ....................................................................... 15
2.1 Safety instructions for installation and maintenance ............................................. 15
2.2 Storage .................................................................................................................. 16
2.3 Components of the RWA-Emergency Power Control System ............................... 17
2.4 Connection options and configurations ................................................................. 19
2.4.1 Alarm group ........................................................................................................... 20
2.4.2 Ventilator groups ................................................................................................... 21
2.4.3 External equipment ............................................................................................... 25
2.4.4 Complete the configuration table ........................................................................... 27
2.4.5 Summary of the jumper settings ............................................................................ 27
2.5 Installation ............................................................................................................. 28
2.5.1 Preparation ............................................................................................................ 28
2.5.2 Assembly ............................................................................................................... 28
2.5.3 Configuration ......................................................................................................... 29
2.5.4 Electrical connection ............................................................................................. 29
2.6 Function test .......................................................................................................... 32
2.7 Operating states and faults ................................................................................... 33
2.8 What to do when …? ............................................................................................. 34
2.9 Testing and maintenance ...................................................................................... 35
3 Appendix ............................................................................................................ 36
3.1 Technical data ....................................................................................................... 36
3.2 Fuses ..................................................................................................................... 37
3.3 Configuration table ................................................................................................ 38
4 Index .................................................................................................................... 39

4
1 Operation
1.1 Safety instructions for the operator and the user
Intended use The RWA system is used to ventilate and, in the event of a fire, automatically extract
smoke from rooms.
Your RWA-Emergency Power Control System is a state of the art system and
complies with the valid safety regulations. GEZE shall not be responsible for damage
resulting from changes made to the RWA-Emergency Power Control System arbit-
rarily.
Obligations of the user As the user, you must ensure that the person operating the RWA-Emergency Power
Control System has been instructed in the operation of the system as described in
Chapter 1 of this manual. Please ensure that the key for the RWA switch can only be
accessed by authorised persons.
Check the display of the RWA-Emergency Power Control System on a regular basis
- at least every 4 days. In the event of a fault, read Section 1.6, What to do when …?
In the event of a fire The emergency functions of the RWA-Emergency Power Control System can be
triggered in the event of a fire from a smoke extractor.
Instruction The client or the owner-operator has to be instructed in proper use of the RWA system
during commissioning or handing over.
The client or the owner-operator has to confirm in writing that the instruction has been
carried out.
Maintenance As needed - but at least once a year - you must have a specialist approved by GEZE
inspect the system and perform any necessary maintenance. You will receive a
written report regarding the inspection. The two batteries must be replaced after no
more than 4 years.
Please keep this manual and the connection diagram where it can be easily
accessed.
To reset a fire alarm, the RWA-Emergency Power Control System may only be
operated by an operator who has read Chapter 1, Operation in this manual. In
particular, the safety instructions in Section 1.4, Fire alarm must be complied
with.

5
1.2 Overview of the RWA-Emergency Power Control System
Function The RWA-Emergency Power Control System controls the extraction of smoke and
heat (RWA) from staircases, factory halls, etc. Windows and smoke extraction vents
are controlled for normal ventilation operation.
If a fire alarm is triggered, the windows and smoke extraction vents are automatically
opened or closed, depending on the configuration of your RWA-Emergency Power
Control System.
The RWA-Emergency Power Control System controls the components, supplies
them with current and provides backup in mains failure conditions.
1 RWA-Emergency Power Control System
2 Drives for the windows and smoke extraction vents
3 Ventilator switch
4 Timer switch
5 Rain and wind control/sensor
6 Window Open signal (optional)
7 Fault signal (optional)
8 Alarm from external fire alarm system
9 Alarm signal (retransmission of alarm signal) (optional)
10 Smoke sensors and heat differential sensors
11 RWA switch
INFO
INFO
2
3
4
5
10
6
8
9
7
11
1
Notstromsteuerzentrale
Emergency Power Control System
E 260 N
O
Störung
Netzausfall
O
Fault
Power outage
grün
gelb
gelb blinkend
green
yellow
yellow flashing

6
1.2.1 The electrical components of the RWA-Emergency Power Control
System
E 260 N2
E 260 N4
L1 P
E
N
12
3
5
3
F3 F4
43
251
3343
3

7
E 260 N8
E 260 N12
1 Main circuit board
2 Batteries
3 Fuses
4 Terminal compartment
5 Transformer
2
1
5
3
3
F2
F8
F7
F6
F5F4
F3
F1
343
F1
F2
F3 F4 F6
F8
1
5
3
343
2
3

8
1.2.2 Components for ventilation operation
Drives The drives open and close windows and/or smoke extraction vents.
Ventilator switches The user can operate the window drives using the ventilator switches.
Timer switch If a timer switch is connected, windows can be opened or closed at preset times.
Rain/wind sensor If a rain/wind sensor is connected, all windows will be closed in the event of rain or
strong wind. The ventilator switches are then disabled.
Window Open signal The Window Open signal lamp is lit when a window is open or not completely closed.
1.2.3 Components used in the case of alarm
RWA switch In the event of a fire, you can manually trigger an alarm by pressing the RWA switch.
The RWA-Emergency Power Control System then initiates the alarm program set by
the service technician.
See Section 1.4, Fire alarm for details on how to clear the alarm.
The 4 signal lamps on the RWA switch signify the following:
The controller sets this signal based on the switching signals from the ventilator swit-
ch.
The windows are not directly monitored.
Symbol LED Meaning
red Illuminates when the fire alarm is triggered by a
RWA switch, smoke sensor or an external fire
alarm system.
yellow Illuminates when a window is open or not fully
closed.
Flashes for 60 seconds when a window is
opened or closed.
green Illuminates when the RWA switch and the
RWA-Emergency Power Control System are
functioning properly.
yellow Illuminates in the event of a fault.

9
Smoke sensor and heat differential
sensor
If a smoke sensor detects smoke or a heat differential sensor registers a sharp incre-
ase in temperature, the fire alarm is triggered.
See Section 1.4, Fire alarm, for details on how to clear the alarm.
Alarm signal (optional) The RWA-Emergency Power Control System transmits an external alarm signal if the
fire alarm is triggered. This can be used, for example, to trigger an audible alarm or
the alarm can be relayed to the fire station.
External fire alarm system If your RWA-Emergency Power Control System is connected to an external fire alarm
system, this can also trigger the fire alarm.
See Section 1.4, Fire alarm, for details on how to clear the alarm.
Fault signal (optional) The RWA-Emergency Power Control System transmits an external signal in the event
of a fault. This can, for example, be connected to a warning lamp.
1.3 Ventilation operation
Opening and closing windows The windows are divided into ventilator groups. For each ventilator group, there are
one or more ventilator switches which can be used to open or close all the windows
in that ventilator group at the same time.
➮Press the Open button to open a window.
➮Press the Close button to close a window.
➮Press the Stop button to stop the opening or closing of a window.
The opening and closing of the windows is indicated by LEDs on the RWA switches
and ventilator switches in the following manner:
The signal on the ventilator switch only applies for the windows in its ventilator group,
while the signal on the RWA switch refers to all the attached ventilator groups.
Therefore, the yellow Window Open signal lamp on an RWA switch is not ex-
tinguished until the windows in all the ventilator groups in its alarm group are closed.
Window RWA switch
yellow signal lamp
Window OPEN
Ventilator switch
green signal lamp
Ventilator switch
red signal lamp
fully closed off on off
opens flashes (for 60 s) off flashes (for 60 s)
fully or partly
open
on off on
closes flashes (for 60 s) flashes (for 60 s) off

10
Rain/wind sensor If a rain/wind sensor is installed, the windows will close automatically in the event of
rain or strong wind. As long as the rain/wind sensor is active, the windows cannot be
opened with the ventilator switch.
In the event of a fire alarm, the windows will also open when the rain/wind sensor is
active.
Power outage In the event of a power outage, ventilation operation is disabled, which saves the bat-
teries for use in the event of a fire. It is only possible to close the windows which are
already open.
1.4 Fire alarm
Triggering the fire alarm To manually trigger the fire alarm:
1. Break the glass on the RWA switch.
2. Depress the pushbutton until it clicks into place.
The fire alarm is triggered automatically in the following situations:
•A smoke sensor detects smoke.
•A heat differential sensor detects a sharp increase in temperature.
•A fire alarm system transmits an alarm signal to the RWA-Emergency Power
Control System.
Procedures and signals during the fire
alarm
If a fire alarm is triggered, the alarm program of the RWA-Emergency Power Control
System executes:
•Windows and smoke extraction vents open (normal configuration) or close.
•The red fire alarm signal lamp on the RWA switch is illuminated.
•The RWA-Emergency Power Control System transmits external signals, for
example to an audible signal or the fire station.
•The ventilator switches are disabled.
•The rain/wind sensor is ignored.

11
Stopping the fire alarm You can clear the alarm condition in two ways:
•Reset the RWA-Emergency Power Control System.
or
•Reset any RWA switch.
When the alarm condition has been cleared, the audible alarm signal stops and the
ventilator switches are again useable.
Resetting the system fully The way in which the RWA-Emergency Power Control System is prepared for another
alarm is dependent on the cause of the alarm:
•If the fire alarm has been triggered by an RWA switch, reset this RWA switch (see
next section).
•If the fire alarm was triggered by a smoke sensor or a heat differential sensor,
reset the RWA-Emergency Power Control System (see next but one section).
•If the fire alarm was triggered by an external fire alarm system, please ensure that
the alarm signal from this fire alarm system is switched off.
Resetting an RWA switch
1. Open the RWA switch using the key.
2. Release the black pushbutton (2) using the slider (1).
3. Reset the fire alarm by pressing the green Close button "ZU" (3).
The windows and smoke extraction vents Close again, the alarm is cleared and
the RWA-Emergency Power Control System is reset.
4. Replace the broken glass (4).
5. Lock the RWA switch again.
GEFAHR
If the system is not fully reset (the red fire alarm LED is still lit), the system will not
function properly if a new alarm is triggered!
➮Always reset the system fully after an alarm.
12 3 4
Geprüft
nach
VdS 2592

12
Reset the RWA-Emergency Power
Control System
1. Unscrew the lid that covers the terminal compartment of the control panel case.
2. Press the white Reset button (1).
The alarm is cleared, the RWA-Emergency Power Control System and the smoke
sensors are reset.
3. Relock the control panel case.
4. Close the windows and smoke extraction vents using the ventilator switches.
Checking the reset After the alarm is reset, the red fire alarm signal lamp on the RWA switches is ex-
tinguished, the audible alarm stops and the windows can again be opened and closed
with the ventilator switches. The RWA-Emergency Power Control System is ready for
another alarm.
If the red fire alarm signal lamp is not extinguished, there is at least one of the
following alarm signals on the RWA-Emergency Power Control System which you
must clear:
•Alarm signal from an RWA switch
•Alarm signal from a smoke sensor
•Alarm signal from an external fire alarm system
765432198765412121213 321
L1 PEN
1
Notstromsteuerzentrale
Emergency Power Control System
E 260 N
O
Störung
Netzausfall
O
Fault
Power outage
grün
gelb
gelb blinkend
green
yellow
yellow flashing
DANGER
Risk of death through electrical shock!
➮Do not touch anything inside the control panel case of the RWA-Emergency
Power Control System except the white Reset button (1).
➮Relock the control panel case immediately after use.

13
1.5 Power outage and fault
The operating condition of the RWA-Emergency Power Control System is indicated
by an LED on the front door:
Power outage The RWA-Emergency Power Control System has an integrated emergency power
supply, that can bridge a power outage of at least 72 hours, for example during main-
tenance work or in the event of a fire. The prerequisite is that the batteries are in pro-
per working order.
The emergency functions of the RWA-Emergency Power Control System are susta-
ined during a power outage. However, the normal operation of the ventilation using
the ventilator switch is disabled to maintain the capacity of the battery for as long as
possible. It is only possible to close already open windows.
Rectify the cause of the power failure:
➮Check the power supply to which the RWA-Emergency Power Control System is
connected and, if necessary, replace the fuse.
If the power supply is in order:
➮Contact a GEZE-approved specialist.
Fault In the event of a fault with an LED illuminated yellow, work is required in the control
panel case.
➮Contact a GEZE-approved specialist.
LED operating condition
illuminated green normal operation, no fault
yellow flashing power outage
illuminated yellow other fault
DANGER
Risk of death through electrical shock!
➮Any work on the power supply should only be performed by a qualified
electrician.

14
1.6 What to do when …?
Problem Cause Action
Yellow signal lamp is
illuminated on the RWA-
Emergency Power Control
System.
Fault Contact a GEZE-approved
specialist.
Yellow signal lamp is
flashing on the RWA-
Emergency Power Control
System.
Mains power
outage
Check the power supply to
which the RWA-Emergency
Power Control System is
connected and, if necessary,
replace the fuse.
If the power supply is in order:
Contact a GEZE-approved
specialist.
Depressing the ventilator
switch does not move the
windows.
Mains power
outage or other
fault
Check whether the signal lamp
on the RWA-Emergency Power
Control System is flashing or
illuminated yellow.
Rain/wind sensor
active
The windows can only be
opened again once the rain or
wind has subsided.

15
2 Installation and maintenance
2.1 Safety instructions for installation and maintenance
Authorised personnel • Installation may only be performed by qualified electricians or GEZE-approved
specialists.
•Repair and maintenance work, however, may only be performed by GEZE-
approved specialists.
Working with safety in mind • Before any maintenance or installation work is carried out on the RWA-
Emergency Power Control System, disconnect the power supply.
•Comply with the regulations, standards and guidelines and, in particular, the latest
version of the VDE 0833/0815 guidelines.
•Consult the local approval authorities to determine the type of cable (for example
fire protection cable) and the required type of protection.
•Use only original GEZE parts for repair and retrofitting work.
•When replacing the batteries, use only batteries recommended by GEZE.
Disclaimer If any changes are made to the system by an unauthorised person, or if components
other than GEZE original parts or GEZE recommended batteries are used, GEZE
shall not be liable for any resultant damage.

16
2.2 Storage
Storing the RWA-Emergency Power
Control System
•Store the RWA-Emergency Power Control System in a protected area.
•If the unit has already been in use:
➮Disconnect the RWA-Emergency Power Control System from the mains and
remove the battery fuse (see Section 2.5.4, Electrical connection).
Storing lead gel batteries The lead gel batteries will discharge automatically when stored. Therefore:
•Minimise the storage time.
•Store batteries or packed RWA-Emergency Power Control System protected from
heat at temperatures of less than 30 °C.
•If the system is not operated in the meantime, recharge the batteries no later than
7 months after the previous charge (for the charging date, see the label).
Recharging the batteries For recharging the batteries, there are two options:
1. Disconnect or remove the batteries from the RWA-Emergency Power Control
System and recharge them using a standard charger.
or
1. Charge the batteries in the RWA-Emergency Power Control System.
Connect the RWA-Emergency Power Control System to the mains, insert the
battery fuse and charge the battery for about 36 hours (see Section 2.5.4,
Electrical connection).
2. Note the new charging date on the battery.

17
2.3 Components of the RWA-Emergency Power Control
System
The RWA-Emergency Power Control System controls the extraction of smoke and
heat (RWA) from staircases, factory halls, etc. Windows and smoke extraction vents
are controlled for normal ventilation operation. In the event of a fire alarm, the
windows are automatically opened or closed.
The RWA-Emergency Power Control System offers several configuration and expan-
sion options which are described in the following sections.
1. RWA-Emergency Power Control System
2. Alarm group
3. Ventilator group 1
4. Ventilator group 2 (maximum of 4 ventilator groups with E 260 N8/4)
5. Rain/wind sensor and signals Window Open, Fault and Alarm
3
2
1
5
4

18
RWA-Emergency Power Control
System
The RWA-Emergency Power Control System is the central control unit to which all the
other components are connected. The RWA-Emergency Power Control System cont-
rols the components and supplies them with power.
The type designation of the RWA-Emergency Power Control System specifies the
maximum permissible output current for the drives and the number of ventilator
groups that can be connected:
* or 2 x E205/206 drives, E212-24 V
The number before the slash specifies the power group, the number following the
slash gives the number of ventilator groups which can be connected.
Alarm group The RWA-Emergency Power Control System has one alarm group. The alarm group
consists of two lines:
•An RWA switch line
•A smoke/heat differential sensor line
If either of these lines triggers the alarm, the drives of all of the ventilator groups will
be actuated in accordance with the set alarm program.
Moreover, the alarm group can be connected to an external fire alarm system. If the
external fire alarm system triggers a fire alarm, it starts the same alarm program as
for an alarm from an RWA switch or smoke/heat differential sensor.
Ventilator groups Depending on the version, the RWA-Emergency Power Control System supports one,
two, three or four ventilator groups. Each ventilator group has two lines:
•A drive line
•A ventilator switch line
All drives for a ventilator group are controlled jointly by one of the associated ventilator
switches or by the optional timer switch.
Rain/wind sensor You can connect a rain/wind sensor, which closes all the windows in the event of rain
or strong winds. The ventilator switches are disabled as long as the rain/wind sensor
is active.
Signals An optional daughter card provides 3 additional contacts for signals or alarm lines:
•Alarm: On which you can, for example, connect an audible alarm or an alarm line
to the fire station.
•Fault: On which you can, for example, connect a warning lamp.
• Window Open: On which you can, for example, connect a warning lamp.
Type designation Maximum output
current to the drives
Maximum number of
ventilator groups
E 260 N2/1 2.0 A * 1
E 260 N4/1 to E 260 N4/2 4.0 A 1–2
E 260 N8/1 to E 260 N8/4 7.5 A 1–4
E 260 N12/1 to E 260 N12/2 12 A 1–2
Ventilator groups cannot be retrofitted.

19
2.4 Connection options and configurations
Before the installation, plan all the connections and the configuration of the RWA-
Emergency Power Control System. The various options are explained in the following
sections.
Discuss the design with the operator. Afterwards, complete the configuration table
found in the Appendix. The configuration table is an important reference aid for future
maintenance and repair.
Carry out the installation and commissioning work in the sequence described in Sec-
tion 2.5, Installation.
Main circuit board The components of the RWA-Emergency Power Control System are connected to the
main circuit board (1).
321
L1 PEN
765432198765412121213
1
Notstromsteuerzentrale
Emergency Power Control System
E 260 N
O
Störung
Netzausfall
O
Fault
Power outage
grün
gelb
gelb blinkend
green
yellow
yellow flashing

20
2.4.1 Alarm group
The alarm group consists of a smoke/heat differential sensor line, an RWA switch line
and an input for an external fire alarm system.
E 260 N2/N4/N8/N12
The alarm from the alarm group acts on all the ventilator groups of the RWA-Emer-
gency Power Control System.
RWA switch A maximum of four (E 260 N2/1) or ten (E 260 N4/1 to N12/2) RWA switches of type
FT 4/24 V DC can be connected in line to the alarm group. With the exception of the
last RWA switch, remove both terminating resistors from each RWA switch.
Smoke/heat differential sensor Optical smoke sensors of type RM 1003/24V DC or heat differential sensors of type
WM 1005/24V DC can be connected to the alarm group - either a max. total of 10 sen-
sors (E 260 N2/1 to N8/4) or a max. total of 20 sensors (E 260 N12).
Both types can be used in any combination since they have the same socket. The ter-
minating resistor, which is delivered with the RWA Emergency Power Control System
clamped in the terminal strip, has to be installed in the last socket in the line.
External fire alarm system An external fire alarm system with a floating (potential-free) make contact can be con-
nected to the alarm group.
321
L1 PEN
765432198765412121213
This manual suits for next models
10
Table of contents