GILBARCO VEEDER-ROOT PA0261 User manual

MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016 Page 1
Introduction
Purpose This manual provides installation information for the Universal Distribution Box (D-Box)
PA0261. The D-Box provides an interface between Gilbarco®consoles with Two-wire Current
Loop Interface (TWI) and dispensing units or Passport®controllers with RS-422 interface and
dispensing units, CRIND®s, or G-CAT™s. This D-Box works with all Gilbarco electronic fuel
dispensing consoles and controllers.
This manual also provides the installation instructions for the Expansion Kit [K93717 (only
for T17651 Board)]. The kit allows you to add a second distribution board to the D-Box.
Intended Users
This manual is intended for Gilbarco-trained and certified Authorized Service Contractors
(ASCs).
Do not install this equipment unless you have proper training for installing equipment in a
hazardous location.
WARNING
Table of Contents
Topic Page
Introduction 1
Important Safety Information 4
Before You Begin 6
Installing Universal D-Box 6
Required Tools and Materials
Following tools and materials are required for installing the universal D-Box:
• Drill
• Multimeter
• Needle Nose Pliers
• Flat-blade and Phillips®-head Screwdriver #2
• Wire Nuts
•WireStripper
MDE-2713C
Universal Distribution Box (D-Box)
Installation Manual
August 2016

Introduction
Page 2 MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016
Parts List Following table lists the parts included in the Expansion Kit (K93717) for D-Box with single
T17651 Printed Circuit Assembly (PCA):
Item # Description Part Number Quantity
1Printed Circuit Board (PCB) Assembly, D-Box T17651-G1 1
2Assembly, Cable Expansion PCB R19262-G1 1
3Assembly, Cable Two-wire J905/J102 D-Box R18810-G1 1
4Support, Circuit Board Q10651-02 4
5Assembly, Screw Lock [Connector, D-Subminiature (D-Sub)] Q10437-07 2
6Assembly, Cable, Mass Terminal Assembly (MTA) Pigtail R19263-G1 2
7Assembly, Cable, RS-422 J103/J905, D-Box R19249-G1 1
Related Kits
Kit Number Description
K9339-01 Pigtail Cable Kit for Transac®System 1000™and PAM™1000 installation using field
wiring to connect to D-Sub connectors for TWI inputs.
*Not for use with Passport.
Required Reading
Where fuels are involved, you are working in a dangerous environment of gasoline,
gasoline vapor, and electricity. Failure to install this equipment in accordance with
National Fire Protection Association (NFPA) 30A and NFPA 70®could result in severe
injury or death.
WARNING
Before installing the kits, read, understand, and follow:
• This manual.
• The National Electrical Code [NEC®(NFPA 70)].
• The automotive and marine service code (NFPA 30A).
• Any national, state, and local codes that may apply.
Failure to install the equipment in accordance with NFPA 30A and NFPA 70 may adversely
affect the safe use and operation of the system.
For installation in Canada the installer must read and understand this manual, Canadian
Standards Association (CSA) C22.1 Canadian Electrical Code and applicable federal,
provincial, and local codes and regulations.

MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016 Page 3
Introduction
Related Documents
Document
Number Title GOLDSM Library
MDE-2072 Transac 12-G Communications Console Installation Manual Transac Products
MDE-2383 Transac System 1000 Installation Manual Transac Products
MDE-2531 Gilbarco Pump and Dispenser Start-up and Service • Pump and Dispenser Start-up and
Service
• Service Manual
MDE-2537 PAM 1000 System Controller Installation Transac Products
MDE-2538 Pigtail Two-wire Cable Kit K93391-01 Transac Products
MDE-2714 Universal Distribution Box [D-Box (PA0261XXXXXXX)] Service
Manual• Advantage®and Legacy®Models
• POS Peripheral
MDE-2755 STP Control and Dispenser Isolation Relay Box (PA0287) • Advantage and Legacy
• Encore®and Eclipse®
• Encore and Eclipse Installers
Note: Ensure to read and understand the installation documentation for the dispensers being connected to the D-Box.
Abbreviations and Acronyms
Term Description
ASC Authorized Service Contractor
AWG American Wire Gauge
CRIND Card Reader in Dispenser
CSA Canadian Standards Association
D-Box Distribution Box
D-Sub D-Subminiature
ESD Electrostatic Discharge
GOLD Gilbarco Online Documentation
MTA Mass Terminal Assembly
NEC National Electrical Code
NFPA National Fire Protection Association
PAM Pump Access Module
PCA Printed Circuit Assembly
PCB Printed Circuit Board
POS Point of Sale
RFI Radio Frequency Interference
RGA Returned Goods Authorization
STP Submersible Turbine Pump
TWI Two-wire Current Loop Interface
UL®Underwriters Laboratories

Important Safety Information
Page 4 MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016
Important Safety Information
!
!
!
Notes: 1) Save this Important Safety Information section
in a readily accessible location.
2) Although DEF is non-flammable, Diesel is
flammable. Therefore, for DEF cabinets that are
attached to Diesel dispensers, follow all the
notes in this section that pertain to flammable
fuels.
This section introduces the hazards and safety precautions
associated with installing, inspecting, maintaining, or servicing
this product. Before performing any task on this product, read
this safety information and the applicable sections in this
manual, where additional hazards and safety precautions for
your task will be found. Fire, explosion, electrical shock, or
pressure release could occurand cause death or serious injury,
if these safe service procedures are not followed.
Preliminary Precautions
You are working in a potentially dangerous environment of
flammable fuels, vapors, and high voltage or pressures. Only
trained or authorized individuals knowledgeable in the related
procedures should install, inspect, maintain, or service this
equipment.
Emergency Total Electrical Shut-Off
The first and most important information you must know is how
to stop all fuel flow to the pump/dispenser and island. Locate
the switch or circuit breakers that shut off all power to all fueling
equipment, dispensing devices, and Submerged Turbine
Pumps (STPs).
Total Electrical Shut-Off Before Access
Any procedure that requires access to electrical components or
the electronics of the dispenser requires total electrical shut off
of that unit. Understand the function and location of this switch
or circuit breaker before inspecting, installing, maintaining, or
servicing Gilbarco equipment.
Evacuating, Barricading, and Shutting Off
Any procedure that requires access to the pump/dispenser or
STPs requires the following actions:
• An evacuation of all unauthorized persons and vehicles
from the work area
• Use of safety tape, cones, or barricades at the affected
unit(s)
• A total electrical shut-off of the affected unit(s)
Read the Manual
Read, understand, and follow this manual and any other labels
or related materials supplied with this equipment. If you do not
understand a procedure, call the Gilbarco Technical Assistance
Center (TAC) at 1-800-743-7501. It is imperative to your safety
and the safety of others to understand the procedures before
beginning work.
Follow the Regulations
Applicable information is available in National Fire Protection
Association (NFPA) 30A; Code for Motor Fuel Dispensing
Facilities and Repair Garages, NFPA 70; National Electrical
Code (NEC), Occupational Safety and Health Administration
(OSHA) regulations and federal, state, and local codes. All
these regulations must be followed. Failure to install, inspect,
maintain, or service this equipment in accordance with these
codes, regulations, and standards may lead to legal citations
with penalties or affect the safe use and operation of the
equipment.
Replacement Parts
Use only genuine Gilbarco replacement parts and retrofit kits on
your pump/dispenser. Using parts other than genuine Gilbarco
replacement parts could create a safety hazard and violate
local regulations.
Safety Symbols and Warning Words
This section provides important information about warning
symbols and boxes.
Alert Symbol
This safety alert symbol is used in this manual and on
warning labels to alert you to a precaution which must be
followed to prevent potential personal safety hazards. Obey
safety directives that follow this symbol to avoid possible injury
or death.
Signal Words
These signal words used in this manual and on warning labels
tell you the seriousness of particular safety hazards. The
precautions below must be followed to prevent death, injury, or
damage to the equipment:
DANGER:Alerts you to a hazard or unsafe practice
which will result in death or serious injury.
WARNING: Alerts you to a hazard or unsafe practice
that could result in death or serious injury.
CAUTION with Alert symbol: Designates a hazard or
unsafe practice which may result in minor injury.
CAUTION without Alert symbol: Designates a hazard or
unsafe practice which may result in property or
equipment damage.
Working With Fuels and Electrical Energy
Prevent Explosions and Fires
Fuels and their vapors will explode or burn, if ignited. Spilled or
leaking fuels cause vapors. Even filling customer tanks will
cause potentially dangerous vapors in the vicinity of the
dispenser or island.
DEF is non-flammable. Therefore, explosion and fire safety
warnings do not apply to DEF lines.
The EMERGENCY STOP, ALL STOP, and
PUMP STOP buttons at the cashier’s station
WILL NOT shut off electrical power to the
pump/dispenser. This means that even if you
activate these stops, fuel may continue to flow
uncontrolled.
You must use the TOTAL ELECTRICAL
SHUT-OFF in the case of an emergency and not
the console’s ALL STOP and PUMP STOP or
similar keys.
!
WARNING
!

MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016 Page 5
Important Safety Information
No Open Fire
Open flames from matches, lighters, welding torches,
or other sources can ignite fuels and their vapors.
No Sparks - No Smoking
Sparks from starting vehicles, starting, or using power tools,
burning cigarettes, cigars, or pipes can also ignite fuels and
their vapors. Static electricity, including an electrostatic charge
on your body, can cause a spark sufficient to ignite fuel vapors.
Every time you get out of a vehicle, touch the metal of your
vehicle, to discharge any electrostatic charge before you
approach the dispenser island.
Working Alone
It is highly recommended that someone who is capable of
rendering first aid be present during servicing. Familiarize
yourself with Cardiopulmonary Resuscitation (CPR) methods, if
you work with or around high voltages. This information is
available from the American Red Cross. Always advise the
station personnel about where you will be working, and caution
them not to activate power while you are working on the
equipment. Use the OSHA Lockout/Tagout procedures. If you
are not familiar with this requirement, refer to this information in
the service manual and OSHA documentation.
Working With Electricity Safely
Ensure that you use safe and established practices in working
with electrical devices. Poorly wired devices may cause a fire,
explosion, or electrical shock. Ensure that grounding
connections are properly made. Take care that sealing devices
and compounds are in place. Ensure that you do not pinch
wires when replacing covers. Follow OSHA Lockout/Tagout
requirements. Station employees and service contractors need
to understand and comply with this program completely to
ensure safety while the equipment is down.
Hazardous Materials
Some materials present inside electronic enclosures may
present a health hazard if not handled correctly. Ensure that
you clean hands after handling equipment. Do not place any
equipment in the mouth.
In an Emergency
Inform Emergency Personnel
Compile the following information and inform emergency
personnel:
• Location of accident (for example, address, front/back of
building, and so on)
• Nature of accident (for example, possible heart attack, run
over by car, burns, and so on)
• Age of victim (for example, baby, teenager, middle-age,
elderly)
• Whether or not victim has received first aid (for example,
stopped bleeding by pressure, and so on)
• Whether or not a victim has vomited (for example, if
swallowed or inhaled something, and so on)
IMPORTANT: Oxygen may be needed at scene if gasoline has
been ingested or inhaled. Seek medical advice immediately.
Lockout/Tagout
Lockout/Tagout covers servicing and maintenance of machines
and equipment in which the unexpected energization or
start-up of the machine(s) or equipment or release of stored
energy could cause injury to employees or personnel.
Lockout/Tagout applies to all mechanical, hydraulic, chemical,
or other energy, but does not cover electrical hazards. Subpart
S of 29 CFR Part 1910 - Electrical Hazards, 29 CFR Part
1910.333 contains specific Lockout/Tagout provision for
electrical hazards.
The pump/dispenser contains a chemical known to the
State of California to cause cancer.
WARNING
!
The pump/dispenser contains a chemical known to the
State of California to cause birth defects or other
reproductive harm.
WARNING
!
Gasoline/DEF ingested may cause
unconsciousness and burns to internal organs.
Do not induce vomiting. Keep airway open.
Oxygen may be needed at scene. Seek medical
advice immediately.
WARNING
!
DEF generates ammonia gas at higher temperatures.
When opening enclosed panels, allow the unit to air out to
avoid breathing vapors.
If respiratory difficulties develop, move victim away from
source of exposure and into fresh air. If symptoms persist,
seek medical attention.
WARNING
!
Gasoline inhaled may cause unconsciousness
and burns to lips, mouth, and lungs. Keep airway
open. Seek medical advice immediately.
WARNING
!
Gasoline/DEF spilled in eyes may cause burns to
eye tissue. Irrigate eyes with water for
approximately 15 minutes. Seek medical advice
immediately.
WARNING
!
Gasoline/DEF spilled on skin may cause burns.
Wash area thoroughly with clear water.
Seek medical advice immediately.
WARNING
!
DEF is mildly corrosive. Avoid contact with eyes, skin, and
clothing. Ensure that eyewash stations and safety
showers are close to the work location. Seek medical
advice/recommended treatment if DEF spills into eyes.
WARNING
!

Before You Begin
Page 6 MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016
Before You Begin
Read and understand all the safety information in “Important Safety Information” on page 4.
A properly grounded Electrostatic Discharge (ESD) wrist strap must be worn
while servicing any electronic devices or components. Failure to use
electrostatic precautions may damage electronic components and void
warranty.
CAUTION
To prepare the site and dispenser for the installation, proceed as follows:
1Inform the store manager at the site that the power will be shut down.
2Turn off circuit breakers to the unit being serviced.
3Barricade the unit to be worked on.
4Match the parts received in the kit with “Parts List” on page 2.
Failure to turn off the unit during installation may cause injury or bodily harm from
electrical shock. Ensure that all power to the unit is switched off before opening the door
to the unit and during kit installation.
WARNING
Installing Universal D-Box
The D-Box provides an interface between Gilbarco consoles with TWI and third-party
controllers with RS-422 interface and dispensing units, CRINDs, or G-CATs. The PCB(s)
inside the D-Box includes jumper jacks which are used to select either the TWI or the
RS-422 configuration. The required interface connector(s) to the controller is provided, with
the D-Box.
Note: Interface cables between the D-Box and the console/controller are not included, and
must be ordered separately. For proper length and type of cable required, refer to
“Data Cabling Requirements” on page 17.
The D-Box houses the power supply transformer and a removable tray with either one or two
PCBs. Each PCB contains a power supply, an opto-coupled current loop interface, an RS-422
interface, eight dispenser current loops, and automatic isolation circuitry.
Two four-channel MTA connectors are provided for each circuit board for field wiring
(see Figure 8 on page 20). These are required only for T17651-G1 Boards. For M14301AXXX
Board, field wires are directly terminated on box type connectors on board.
The Transac System 1000 and PAM 1000 controllers require this D-Box. One D-Box is
needed for every 12 fueling positions (Transac System 1000 systems with three or four
consoles require an additional D-Box).

MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016 Page 7
Installing Universal D-Box
D-Box - Controller Interface
D-Box with T17651 PCA
There are eight individual current data loops for dispensing units on each distribution board
(see Figure 1 on page 8 to Figure 6 on page 13). D-Box with two boards can be configured as
either:
• Two separate inputs with each input controlling eight data loops [see Figure 1 (iii) on
page 8 and Figure 3 (iii) on page 10], or
• One input controlling 16 data loops [see Figure 1 (ii) on page 8 or Figure 3 (ii) on
page 10].
Each data loop has both current regulation and automatic isolation circuitry. The dispenser
data loop drivers operate from an unregulated 12 VDC supply at 45 mA for Gilbarco
dispensers and CRINDs, or 20 mA for G-CATs. The applicable configuration is set by jump
jacks on the distribution board(s) (see Figure 9 on page 20 to Figure 24 on page 20).
Each distribution board must be dedicated for use with either Gilbarco dispensing units,
CRINDs, G-CATs, or consoles (for Transac System 1000 multiple consoles). Do not mix
different current loop equipment on one distribution board.
D-Box with M14301 PCA
There are 16 current data loops for dispensing units on each board. This board can be
configured as either:
• Two separate inputs with each input controlling eight data loops [see Figure 2 (iii) or
Figure 4 (iii)], or
• One input controlling 16 data loops [see Figure 1 (ii) or Figure 4 (ii)].
When installing equipment, ensure that the boards are configured for 20 mA current loops if
connecting G-CATs to the D-Box. Damage to the G-CAT MPU boards will occur if the jump
jacks are not set correctly.
When installing equipment, connect only one dispenser or card reader to any one data loop
channel. The wiring length between the D-Box and dispensers must not exceed 2600 feet, and
requires stranded or solid 14 American Wire Gauge (AWG) wire. Do not use daisy chaining
with this unit.
For Transac System 1000multiple console installation, refer to MDE-2538 Pigtail Two-wire
Cable Kit K93391-01.

Installing Universal D-Box
Page 8 MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016
D-Box Configurations
Following illustrations show the various D-Box interface configurations:
Figure 1: TWI Consoles and Controllers - 1
(i)
Note: Refer to console installation manual for maximum number of fueling positions allowed.
Up to 8 Duals or 8 Single-sided Dispensers
Up to 8 Duals or 16 Single-sided Dispensers
Up to 8 Duals or 8 Single-sided Dispensers Up to 8 Duals or 8 Single-sided Dispensers
TS 1000
PAM 1000
PAM
TCR-G2
T-12G
TS 1000
PAM 1000
PAM
TS 1000
PAM 1000
PAM
TCR-G2
T-12G
(iii)
(ii)
PC
Board
T17651
PC
Board
T17651
PC
Board
T17651
PC
Board
T17651
PC
Board
T17651
Two Boards
D-Box Console/Controller
Console/Controller
Console/Controller
One Board
D-Box
One Input
One Input
Two Boards
D-Box
Two Inputs

MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016 Page 9
Installing Universal D-Box
Figure 2: TWI Consoles and Controllers - 2
Up to 8 Duals or 8 Single-sided Dispensers
Up to 8 Duals or 16 Single-sided Dispensers
Up to 8 Duals or 8 Single-sided Dispensers Up to 8 Duals or 8 Single-sided Dispensers
(i)
(iii)
(ii)
Console/Controller
One Board
D-Box
One Input
PC Board
M14301
Note: Refer to console installation manual for maximum number of fueling positions allowed.
PC Board M14301
Console/Controller
One Board
D-Box
One Input
PC Board M14301
Console/Controller
One Board
D-Box
Two Inputs
TS 1000
PAM 1000
PAM
TS 1000
PAM 1000
PAM
TS 1000
PAM 1000
PAM
TCR-G2
T-12G
TCR-G2
T-12G

Installing Universal D-Box
Page 10 MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016
Figure 3: Passport with Dispensers - 1
(i)
(iii)
(ii)
PC
Board
T17651
Console/Controller
One Board
D-Box
One Input
Passport
Passport
Passport
PC
Board
T17651
Console/Controller
D-Box
PC
Board
T17651
Two Boards One Input
PC
Board
T17651
Console/Controller
D-Box
PC
Board
T17651
Two Boards Two Inputs
Up to 8 Duals or 8 Single-sided Dispensers or 8 Dual CRINDs Up to 8 Duals or 8 Single-sided Dispensers or 8 Dual
CRINDs
Up to 8 Duals or 16 Single-sided Dispensers or 16 Dual CRINDs
Up to 8 Duals or 8 Single-sided Dispensers or 8 Dual CRINDs

MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016 Page 11
Installing Universal D-Box
Figure 4: Passport with Dispensers - 2
Up to 8 Duals or 8 Single-sided Dispensers or 8 Dual CRINDs
Passport
PC Board M14301
Console/Controller
One Board
D-Box
One Input
Up to 8 Duals or 8 Single-sided Dispensers or
8 Dual CRINDs Up to 8 Duals or 8 Single-sided Dispensers or
8 Dual CRINDs
Up to 8 Duals or 16 Single-sided Dispensers or 16 Dual CRINDs
Passport
PC Board M14301
Console/Controller
One Board
D-Box
One Input
Passport
PC Board M14301
Console/Controller
One Board
D-Box
Two Inputs
(i)
(iii)
(ii)

Installing Universal D-Box
Page 12 MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016
Figure 5: Passport with Dispensers, CRINDs, or G-CATs - 1
Up to 8 Duals or 8 Single-sided
Dispensers or 8 Dual CRINDs Up to 4 G-CAT
(i)
(ii)
Passport
PC
Board
T17651
Console/Controller
D-Box
PC
Board
T17651
Two Boards Two Inputs
Up to 8 Duals or 8 Single-sided
Dispensers or 8 Dual CRINDs Up to 4 G-CAT
Passport
Console/Controller
D-Box
One Board Two Inputs
PC Board M14301

MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016 Page 13
Installing Universal D-Box
Figure 6: Passport with Dispensers, CRINDs, and G-CATs - 2
Up to 8 Duals or 8 Single-sided
Dispensers or 8 Dual CRINDs Up to 8 Duals or 8 Single-sided
Dispensers or 8 Dual CRINDs
Up to 4 G-CATS
(ii)
Passport
Console/Controller
D-Box
PC Board M14301
Up to 4 G-CAT
D-Box
PC
Board
T17651
PC
Board
T17651
PC
Board
T17651
Passport
Console/Controller
D-Box
PC Board M14301
Up to 8 Duals or 8 Single-sided
Dispensers or 8 Dual CRINDs Up to 8 Duals or 8 Single-sided
Dispensers or 8 Dual CRINDs
(i)

Installing Universal D-Box
Page 14 MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016
Model Number Breakdown
PA0261X00X0XX
Model Number
Prefix Voltage Not Used Housing Not Used Type of Board Data Input
PA0261
Universal D-Box 0 - 115 VAC 50/60 Hz
1 - 230 VAC 50/60 Hz 00 0 - Standard 03 - One PCB (M14301)
16 Loops
2 - Two PCBs (T17651)
16 Loops
1 - One PCB (T17651)
8 Loops
0 - Two wire
1 - RS-422
2 - Configurable
Two-wire/RS-422
Configurations
Interface #Boards # Inputs Factory Configured As
TWI 1 2 See Figure 2 (iii) on page 9 and Figure 14 on page 25
RS-422 1 2 See Figure 4 (iii) on page 11 and Figure 20 on page 31
Specifications
Dimensions
Height 7 and 13/16”
Width 16 and 9/32”
Depth 5 and 15/32”
Weight 5 lbs
Dedicated Isolated Ground Receptacle
USA/Canada 115 VAC nominal, 50/60 Hz
International 230 VAC nominal, 50/60 Hz
Current
0.5 A @ 115 VAC
0.25 A @ 230 VAC
Operating Environment
Minimum Temperature +32 °F (0 °C)
Maximum Temperature +130°F (+55 °C)
Humidity 5-95% Rh (non-condensing)

MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016 Page 15
Installing Universal D-Box
Preparing for Installation
Unpacking Equipment
When the equipment arrives at the installation site, each unit should be unpacked and
inspected for possible shipping damage. If damage is evident, it must be reported to the carrier.
Shipping damage is not covered under Gilbarco’s warranty policy. After visual inspection,
place the unit back in its shipping carton to prevent undue exposure to the elements, and store
indoors until ready for installation.
Returning of Components
Components returned to Gilbarco under warranty or for repairs are subject to severe shipping
damage if not packaged properly. If original packing materials are unavailable, use a durable
reinforced corrugated box and obtain suitable packing material such as “PAKON” polyfoam
chips, polyurethane foam chips, or polystyrene foam chips. Fill bottom of box with at least
2 inches of packing material. Ensure that the component is firmly packed. It is also
recommended that the package be fully insured.
All returned items must be accompanied by a Returned Goods Authorization (RGA) form.
Remember to include return shipping information and a description of the malfunction.
Note: If the component arrives at Gilbarco in a damaged condition and it is ascertained that
the damage was a direct result of improper packing, such damage will not be covered
under the original factory warranty and the customer will be held responsible for the
cost of the repair necessary to correct said damage.
Basic Site Criteria
Installation of the D-Box must be in accordance with the NEC NFPA 70, the Automotive and
Marine Service Station Code NFPA 30A, and any state or local electrical requirements.
For Canadian installations use the Canadian Electrical Code CSA C22.1.
The site must be equipped with electric service allowing compliance with all installation
requirements of a complete fueling system.
An enclosed weather-protected structure must be located on the site for housing the D-Box.
Room ambient temperature must not exceed 130 °F (55 °C). This maximum temperature is
allowed only if the equipment is allowed free air flow.
Megger testing of field wiring must be completed prior to connecting wires to the D-Box.
The data cabling between the D-Box and the system controller must be kept separate from all
other power and control lines.

Installing Universal D-Box
Page 16 MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016
Physical Placement
Locate the D-Box in an area not subjected to extreme temperature variations. The ambient
temperature must remain relatively constant. Do not install the D-Box in a position subject to
direct sunlight. If conditions dictate, provide a suitable sunscreen.
The PA0261 D-Box is suitable for use over hazardous locations. The box must be installed at
least 18 inches above the floor. Locate the D-Box in an area which minimizes the possibility of
liquids being spilled onto it.
Allow several inches clearance on the left side of the D-Box for the AC power cord. Allow
2 inches clearance above the box for removing the cover.
Electrical Wiring Requirements
The receptacle providing power to the D-Box must be a properly installed isolated ground
receptacle (Hubbell #IG5261 or equivalent). This type of receptacle is easily identified by its
bright orange color and by the triangle embossed into the face of the outlet. The green
grounding screw must be attached to the grounding conductor.
• All electrical wiring must conform to NEC and local wiring codes, as well as the criteria in
this manual.
• One conduit from the breaker panel to the D-Box location is required. The conduit must
contain three 14 AWG wires: 115 VAC Hot, Neutral, and Ground; or 230 VAC L1, L2, and
Ground. Do not use the electrical conduit to provide earth ground.
• The circuit powering the D-Box must not power other devices. This circuit must not share
a conduit with wiring for devices drawing high amperage (compressor, freezer, etc.) or
devices that are sources of Radio Frequency Interference [RFI (TV, microwave, intercom,
etc.)].
• The AC outlet must be within 6 feet of the D-Box (see Figure 7 on page 17). Do not use
extension cords.
Note: For 230 VAC operation, a 9 feet detachable line cord is provided. It is the customer’s
responsibility to supply a plug for the cord, that meets local electrical codes and
Underwriters Laboratories (UL) requirements.

MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016 Page 17
Installing Universal D-Box
Data Cabling Requirements
Following table lists the correct controller to D-Box data cable connections:
Interface Controller Cable Part # Cable Length
TWI PAM 1000 or Transac
System 1000Q11542-52 10’
TWI PAM 1000 or Transac
System 1000Q11542-53 50’
TWI PAM 1000 or Transac
System 1000Q11542-54 100’
TWI PAM 1000 or Transac
System 1000K93391-01 Pigtail cable kit (use with 14 ga field wiring to extend to 2600’
maximum
TWI Transac 12-G Console R19000-02 6’ (use with 14 ga field wiring to existing channel on PA0133
D-Box)
Install all cables so that they are protected from damage or accidental disconnection. Route the
cables along a wall or under a counter and secure with cable ties or suitable cable clamps.
Do not route data wires over fluorescent light, compressor wiring, etc., or near other sources of
interference.
Figure 7: Cable Requirements
Line Cord
Q11736-02
Line Cord
Q11121-01
115 VAC
Console/Controller
Cables
One inch conduit knock-outs (3) are
provided on bottom for field wiring.
230 VAC
Q11736-02 (User supplies
proper plug for 230 VAC.)
Note: An isolated receptacle that meets the local electrical code requirements is supplied by the user.
The receptacle providing power to the PA0261 must be a properly isolated ground receptacle
(Hubbell #IG 5261 or the equivalent). The green grounding screw must be attached to the
grounding conductor.

Installing Universal D-Box
Page 18 MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016
Field Wiring Requirements
A wiring trough will be required in the vicinity of the D-Box for terminating the conduit runs
from the dispensers. Three 1-inch knockouts are provided on the bottom of the D-Box for
running conduit between the box and the wiring trough.
Use 14 AWG stranded wire for data wires to Gilbarco dispensing equipment. Leave plenty of
wire exposed as a service loop in the wiring trough. 16 inches of exposed wire will be needed
inside the D-Box.
When pulling wires, be careful to avoid damage to the insulation.
Installing D-Box
To install the D-Box, proceed as follows:
1Loosen two screws on bottom front of D-Box and lift lid.
2Carefully remove and discard any packing material from D-Box.
3Disconnect cable from the distribution board(s) T17651 at P101 and P102 (or P103). Also
disconnect wiring pigtails from P106 and P107. In case of M14301 Board, cables will be at
P101 and P102A/B (or P103A/B). For connector locations, refer to Figure 10 on page 21.
Working on PCBs without connecting to a ground or discharging static can damage
electronic parts. Use a wrist strap and store parts in antistatic storage bags.
CAUTION
4Slide mounting tray [with circuit board(s)] up and out of the D-Box.
Note: The boards are removed to avoid unnecessary damage to components while mounting
the unit to the wall.
5Mount D-Box to the wall.
• Allow clearance on left side to connect AC cable.
• Allow clearance above the D-Box so that the cover can be removed.
6Mount AC receptacle within 6 feet of the D-Box.
7Install conduit for data wires between the wiring trough and the D-Box. Pull data wires up into
the D-Box leaving 16 inches of wire inside the D-Box. This allows for easy installation of
wiring pigtails.
8Connect data wires to wiring pigtails. In case of M14301 Board, wires will be directly
terminated on box type connectors whereas in case of T17651 to wiring pigtails (see Figure 8
on page 20).
9Replace mounting tray [with circuit board(s)]. Reconnect cables as required to the circuit
board(s). For T17651 Board, reconnect P101, P102 or P103, P106, P107. For M14301 Board,
reconnect P101, P102 A/B or P103A/B.

MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016 Page 19
Installing Universal D-Box
10 Connect data cable(s) to 9-pin D-Sub connectors. In case of T17651 Board, plug MTA Pigtails
to the circuit board(s). In case of M14301 Board, connect cables directly to box connectors
present on board.
11 Verify that the jump jack settings are correct for your configuration. For correct jump jack
configuration, refer to “Jump Jack Configuration”.
Note: When installing the universal D-Box for a RS-422 application (Passport), jump jack
JP9 must be installed for the correct hardware configuration. Configure jump jack JP9
for 45 mA current loop for CRINDs/dispensers and 20 mA for use with G-CAT2 and
G-CAT 3.
Jump Jack Configuration
Configuration 1 Input/8 Loops 1 Input/16 Loops 2 Inputs/8 Loops Each
TWI: Dispensers Figure 9 on page 20
and Figure 10 on
page 21
Figure 11 on page 22
and Figure 12 on
page 23
Figure 13 on page 24
and Figure 14 on
page 25
RS-422: Dispensers or CRINDs Figure 15 on page 26
and Figure 16 on
page 27
Figure 17 on page 28
and Figure 18 on
page 29
Figure 19 on page 30
and Figure 20 on
page 31
RS-422: 8 Dispensers, 8 CRINDs Figure 19 on page 30
and Figure 20 on
page 31
RS-422: 8 Dispensers or CRINDs,
4 G-CATs Figure 21 on page 32
and Figure 22 on
page 33
RS-422: 4 G-CATs Figure 23 on page 34
and Figure 24 on
page 35
12 Plug in AC power cord.
13 Change jump jacks (JP1-JP8) one at a time to the NORMAL position. Verify operation of card
readers and/or dispensing units.

Installing Universal D-Box
Page 20 MDE-2713C Universal Distribution Box (D-Box) Installation Manual · August 2016
14 Replace D-Box cover and secure with screws.
Figure 8: Field Wiring to MTA Pigtails for T17651 Board
Cutandstrip suppliedloopsfor desired
number of field connections.
Wire Nuts
14 AWG Field Wiring
Pigtail Cable Assembly (R19263)
Note: If unused pigtail loops are cut, the exposed ends must be capped with wire nuts.
Figure 9: Jumper Settings - TWI Interface, Single T17651 Board, Single Input, 8 Loops
P107
P101
P106
Note: This configuration interfaces with all TWI consoles/controllers.
To Transformer To Dispensers
Wire Nut to Field Wiring
To Dispensers
To Controller
9-pin D-Sub
Other manuals for PA0261
1
Table of contents
Other GILBARCO VEEDER-ROOT Home Automation manuals