0,6m, 1,5m or 2,8m - 1.6m extension tube available
The Uniguard should be installed according to the
drawing below. The Uniguard can be installed on any side
of the duct. N.B. Rectangular ducts: In order to gain
maximum air sampling coverage, install the Uniguard on
the shortest side of a rectangular duct. We recommend
that the Uniguard is mounted at an equal distance from
heating, cooling, or humidity devices, and similar to the
siting for flow monitors.
A distance of 3 times the duct diameter should be left
before a damper, filter or change of the duct direction,
and 5 times the diameter after these devices.