GM International PSD1210 User manual

PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 Vdc ISM0076-7
PSD1206 - PSD1210
INSTRUCTION MANUAL
INSTRUCTION MANUAL
SIL 3 - SIL 2 Switching Power Supply
24Vdc, 10A, 250W Output, Zone 2/Div. 2
DIN-Rail Mounting Model PSD1210
SIL 3 - SIL 2 Switching Power Supply
24Vdc, 6A, 150W Output, Zone 2/Div. 2
DIN-Rail Mounting Model PSD1206

2 PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 Vdc G.M. International ISM0076-7
General Description: The PSD1206 or PSD1210 is a DIN-Rail Power Supply to supply process control equipment and can be located in Safe Area/ Non Hazardous Location or
Zone 2 / Division 2 Hazardous Area / Hazardous Location. PSD1206 provides 24 Vdc nominal with 6 A output current and isolation between input - output - ground (2000 V).
PSD1210 provides 24 Vdc nominal with 10 A output current and isolation between input - output - ground (2000V). These supply units can be paralleled for redundancy operation to
increase availability upgrading the system from SIL 2 to SIL 3 or to increase the output power. Internal power diode for parallel operation prevents fault propagation in parallel
connected supply systems and load sarin distributes current load equally to each power supply to increase reliability and reduce internal power dissipation.
Signalling LED: Power supply status indication (green).
Alarm: Output voltage deviation ≥± 5 % from nominal 24 Vdc. Power ON led is off when output voltage is in overvoltage condition or is blinking in undervoltage or overload condition.
Overvoltage protection: Three independent overvoltage protections: 1 voltage limiting loop at 27 Vdc and 1 + 1 crowbars at 29 Vdc.
Periodical testing: builtin provisions for on-site T-proof test without having to remove the enclosure.
EMC: Fully compliant with CE marking applicable requirements.
High load fuse breaking capacity: In case of short circuit of one of the loads, the output current has a peak of 430 A for a duration of 0.5 ms (40 times the max. value) and then
reaches 12 A (max. value) after 1.5 ms. For two units in parallel this current reaches 860 A (80 times the max. value). This characteristic ensures the instant breakage of the protective
fuse or circuit breaker. Because of the very short peak duration, other equipments connected are not affected by the failure event and continue to operate without interruption.
Refer to instruction manual ISM0076 for a detailed diagram of the output current.
PSD1206 Switching Power Supply 24 Vdc 6A Output
PSD1210 Switching Power Supply 24 Vdc 10A Output
Characteristics........................................................................................................................................................................... 2
Technical Data .......................................................................................................................................................................... 2
Ordering Information ................................................................................................................................................................. 3
Features .................................................................................................................................................................................... 3
Function Diagram...................................................................................................................................................................... 3
Warning..................................................................................................................................................................................... 4
Storage...................................................................................................................................................................................... 4
Disposal..................................................................................................................................................................................... 4
Operation................................................................................................................................................................................... 5
Installation ................................................................................................................................................................................. 5
Start-up...................................................................................................................................................................................... 6
High load fuse breaking capacity .............................................................................................................................................. 6
Functional Safety Manual for Safety Related Systems and SIL2, SIL3 Applications................................................................ 6
Functional Safety Specifications from EXIDA analysis and report according IEC 61508 – IEC 61511 .................................... 7
Definitions.................................................................................................................................................................................. 7
General Terms .......................................................................................................................................................................... 8
Assumptions.............................................................................................................................................................................. 8
Summary of Data from EXIDA .................................................................................................................................................. 9
Notes....................................................................................................................................................................................... 12
Possible Proof Tests to reveal Dangerous Undetected Faults................................................................................................ 13
Impact of lifetime of critical components on Failure Rate........................................................................................................ 17
Influence of PFDavg calculation on efficiency of Proof Test for a 1oo1 architecture. ............................................................. 17
48 Vdc Output with connection in series of power supply....................................................................................................... 17
48 Vdc Output with 100 % redundance................................................................................................................................... 18
Side A Configuration ............................................................................................................................................................... 19
Side B configuration ................................................................................................................................................................ 20
Characteristics
Index
Supply: Input voltage: 95 to 264 Vac (48 to 62 Hz) or 115 to 350 Vdc. Limit supply voltage to 250 Vrms for Instrinsic Safety applications.
Power Factor Correction (AC input): 0.95.
Efficiency: higher than 80 %.
Max. internal power dissipation PSD1206: 30 W.
Max. internal power dissipation PSD1210: 50 W
AC input current (sinusoidal at full load) PSD1206: 0.8 A @ 230 Vac supply voltage, 1.7 A @ 115 Vac supply voltage
AC input current (sinusoidal at full load) PSD1210: 1.4 A @ 230 Vac supply voltage, 2.8 A @ 115 Vac supply voltage
Protection: 6.5 A fuse (dual). Connection: plug-in terminal block for 4 mm2wire.
Isolation: Input to output isolation: 2000 Vrms (routine test).
Input to ground isolation: 2000 Vrms (routine test).
Output: Output voltage: 24 Vdc (adjustable from 22.8 to 25.2 Vdc).
Regulation: 0.2 % for a 100 % load change.
Stability: 0.1 % for a 20 % line voltage change.
Ripple: ≤50 mVpp.
Output current PSD1206: 6 A nominal. Parallel connection for redundancy with load sharing.
Output current PSD1210: 10 A nominal, 12 A maximum. Parallel connection for redundancy with load sharing.
Technical Data

3
PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 VdcG.M. International ISM0076-7
Connection: plug-in terminal block for 4 mm2wire.
Hold-up time at full load: 100 ms (AC input).
Over voltage protection: output limited to 27 Vdc plus redundant crowbars for over voltage protection at 29 Vdc.
Power good signalling: Output good: 0.95 ≤Vout ≤1.05 nominal value.
Indication: power good green LED, OFF in overvoltage condition or blinking in undervoltage or overload condition.
Signalling: voltage free SPST normally energized optocoupled open-collector transistor, de-energize in overvoltage/undervoltage/overload conditions.
Open-collector rating: 100 mA at 35 V (≤2.0 V voltage drop)
Leakage current: ≤50 µA at 35 V.
Connection: plug-in terminal block for 2.5 mm2wire.
Compatibility:
CE mark compliant, conforms to EN61000-6-2, EN61000-6-4, EN60950 for electrical safety and 89/336/CEE EMC Directive.
Environmental conditions:
Operating temperature limits: -20 to + 60 °C.
Relative humidity limits (up to 40 °C): 10 to 90 %, non condensing.
Transport, storage temperature limits: - 45 to + 80 °C.
Safety Description:
ATEX Category 3 for Zone 2. II 3 G EEx nA IIC T4, -20 °C ≤Ta ≤60 °C. AEx nA T3 for FM certification, -20 °C ≤Ta ≤60 °C.
Approvals: DNV-2006-OSL-ATEX-0099X conforms to EN60079-15, FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3611, 3810 and C22.2 No.142, C22.2 No.213,
E60079-0, E60079-15, EXIDA Report No. GMI 06/11-20 R004, SIL 1 / SIL 2 / SIL 3 according to IEC 61508. Please refer to Functional Safety Manual for SIL applications.
Mechanical: Mounting: T35 DIN Rail according to EN50022.
Weight PSD1206: about 1.8 Kg. Weight PSD1210: about 2.5 Kg.
Location: Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T3 and Class I, Zone 2, Group IIC, IIB, IIA
T3 installation.
Protection class: IP 20.
Dimensions PSD1206: width 200 mm, height 95 mm, depth 110 mm.
Features
• SIL 3 according to IEC 61508 for Tproof = 3 / 6 years (10 / 20 % of total SIF,
two units in parallel with NE Load).
• SIL 2 according to IEC 61508 for Tproof = 9 / 10 years (10 / 20 % of total SIF,
two units in parallel with ND Load).
• SIL 2 according to IEC 61508 for Tproof = 1 / 3 years (10 / 20 % of total SIF,
single unit with NE Load).
• SIL 1 according to IEC 61508 for Tproof = 5 / 10 years (10 / 20 % of total SIF,
single unit with ND Load).
• PFDavg (1 year) 3.03 E-05, SFF 99 % (2 units, NE Load).
• PFDavg (1 year) 8.09 E-05, SFF 97 % (2 units, ND Load).
• PFDavg (1 year) 5.90 E-04, SFF 80 % (1 unit, NE Load).
• PFDavg (1 year) 1.53 E-03, SFF 48 % (1 unit, ND Load).
• Universal AC / DC Input, 95 to 264 Vac (48 to 62 Hz) or 115 to 350 Vdc.
• Installation in Zone 2, Division 2.
• ATEX, FM & FM-C Certifications.
Ordering information
Model: PSD1206 Model: PSD1210
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, GROUPS A, B, C, D T-Code T3, CLASS I, ZONE 2, GROUP IIC T3
Function Diagram
++- - -+ L/+N/-
=
_
CS
Current
Sharing
Fault
Output
Supply
Input
24 Vdc
Output
SIL 2
MODELS PSD1206 - PSD1210
• Power Factor Correction eliminates power-line harmonics loading.
• High load fuse breaking capacity without interrupting operation.
• PSD1206 Highly regulated, trimmable output of 24 Vdc up to 6 A.
• PSD1210 Highly regulated, trimmable output of 24 Vdc up to 10 A.
• 3 over-voltage redundant protections prevent risks to the load.
• Supports redundant parallel connection with load sharing.
• Under-Over voltage alarm monitoring with signalling output (± 5 %).
• Under-Over voltage LED indication.
• 100 ms hold-up time at full load, mitigates power-line glitches.
• Durable metal enclosure, improves shielding and heat sinking.
• High (better than 80 %) efficiency.
• Simplified installation using standard DIN-Rail and plug in input and output
terminal blocks.
• Externally accessible connections for Tproof periodic test.

4 PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 Vdc G.M. International ISM0076-7
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, GROUPS A, B, C, D T-Code T3, CLASS I, ZONE 2, GROUP IIC T3
Function Diagram
Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only.
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the PSD1206, PSD1210 shall be accomplished via conduit
connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC.
For Intrinsic Safety application limits the line supply voltage to a maximum of 250 Vrms, not to be connected to control equipment that uses or generates more than
250 Vrms or Vdc with respect to earth ground.
PSD1206, PSD1210 must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, ANSI/ISA
RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, and the Canadian Electrical
Code CEC) following the established installation rules.
The power supply must be placed in an enclosure with IP4X protection degree when used in locations providing adequate protection against the entry of solid foreign
objects or water capable of impairing safety, or be placed in an enclosure with IP54 protection degree for other locations.
De-energize main power source (turn off power supply voltage), wait at least 3 minutes to discharge internal capacitors before plug or unplug the terminal blocks when installed in
Hazardous Area/Hazardous Locations or unless area is known to be nonhazardous. Hazardous voltage are present at the input terminal block and inside the unit when connected to the
main supply voltage, do not touch electrical connection and do not put conductive object inside the unit.
Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2.
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury.
The unit has no serviceable parts inside, do not open the enclosure. The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized
representative, any unauthorized modification must be avoided.
Warning
PSD1206, PSD1210
Power Supply
FM Approved under
non-incendive field wiring
Unclassified Locations or
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C, D, T-Code T3
Class I, Zone 2, Group IIC, IIB, IIA, T-Code T3
Hazardous (Classified) Locations
Class I, Division 2, Groups A, B, C, D
Class II, Division 2, Groups E, F, G
Class III, Division 2
Class I, Zone 2, Group IIC, IIB, IIA
FM Approved under non-incendive field
wiring (permitted only for US installations),
UL Listed or third party approval
Non-incendive
Equipment
Unclassified Locations
-24Vdc
+24Vdc+
-
FLT+
L/+
N/-
FLT- -
+
Supply Line
Control
Equipment
Must not use or generate
more than 250 Vrms or Vdc
Storage
If after an incoming inspection the unit is not installed directly on a system (parts for spare or expansion with long storage periods) it must be conveniently stocked. Stocking area
characteristics must comply with the following parameters: Temperature: –20 to +60 °C, the –45 to +80 °C in the data sheet is meant for limited periods, mainly to arrange for air
transport, -10 to +30 °C are preferred. Humidity: 0 to 90 %, long period high humidity affects the package integrity, 0 to 60 % humidity is preferred.
Vibration: no prolonged vibration should be perceivable in the stocking area to avoid loosening of parts or fatigue ruptures of components terminals.
Pollution: presence of pollutant or corrosive gases or vapors must be avoided to prevent corrosion of conductors and degradation of insulating surfaces.
Disposal
The product should not be disposed with other wastes at the end of its working life. It may content hazardous substances for the health and the environment, to prevent possible harm
from uncontrolled waste disposal, please separate this equipment from other types of wastes and recycle it responsibly to promote the sustainable reuse of material resources.
This product should not be mixed with other commercial wastes for disposal.
MODELS PSD1206 - PSD1210
++-- -+ L/+N/-
=
_
CS
Current
Sharing
Fault
Output 1
Supply
Input 1
24 Vdc
Output Bus
MODELS PSD1206 - PSD1210
++-- -+ L/+N/-
=
_
CS
Current
Sharing
Fault
Output 2
Supply
Input 2
Connection for current sharing
SIL 3
PSD1206 or PSD1210 is an isolated Switching Power Supply unit installed on a standard EN50022 T35 DIN Rail located in Safe Area/Non Hazardous Locations or Zone 2, Group IIC,
Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T3 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T3 Hazardous Area/Hazardous
Locations (according to EN/IEC60079-15, FM Class No.3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C and
mounting conditions.

5
PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 VdcG.M. International ISM0076-7
Operation
PSD1206, PSD1210 provides fully floating 24 Vdc supply to drive process control equipment like instrumentation, control systems, PLC or loads requiring a stabilized voltage, located in
Safe Area/Non Hazardous Locations or Zone 2, Group IIC, Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T3 and Class I, Zone 2, Group IIC,
IIB, IIA Temperature Code T3 Hazardous Area/Hazardous Locations ensuring that the relevant safety installation conditions are respected. PSD1206 provides a 6 A, 150 W output
capability while the PSD1210 provides a 10 A, 250 W output capability. The power supply has a switching input and a power factor correction circuit resulting in a high efficiency module.
Output is provided with a decoupling diode that permits the parallel operation to increase the current capability or redundancy operation (note that for parallel operation the output voltage
must be separately calibrated at the same value through the “Vout Adjust” trimmer to improve the current sharing operation). Output voltage can be regulated within ± 5 % of the nominal
value. Use an isolated screwdriver for trimmer adjustments. Output circuit is protected by three independent overvoltage circuit: 1 voltage limiting loop at 27 Vdc and 1 + 1 crowbars
at 29 Vdc. Output circuit has under and over voltage detection with separate signaling by an optocoupled transistor; alarm output is normally closed (energized transistor), it de-energizes
when output voltage goes out of the ± 5 % range of the nominal value. It de-energizes also with an input voltage lack. Presence of supply power and normal working condition is
displayed by a green signaling LED: this is normally ON in normal operation, is OFF in overvoltage output or input voltage lack condition and is blinking in undervoltage or overload
condition. Units is equipped with trimmers for output voltage setting and for alarm threshold setting. Example of setting output voltage and alarm threshold: suppose to have a power
supply standard with 24 Vdc output and thresholds set at 22.8-25.2 V. Suppose you want to set the output at 25 V with 23.7-26.3 V threshold value. The procedure to be used is the
following: rotate the “Vout Adjust” trimmer until the voltage has reached the new upper threshold value of 26.3 V. Rotate the “Alarm Adjust” trimmer until the “Power ON” LED turn on,
then slowly rotate until the LED turn off; in this way you set the threshold value at 26.3 V. Finally rotate the “Vout Adjust” trimmer until the output voltage has reached the new requested
value of 25 V.
Installation
The terminal block are not usable as breaking device according to EN60950. The wiring cables have to be proportionate in base to the current and the length of the cable.
For PSD1206 typical cable section is AWG15 for input connection and AWG13 for output connection. For PSD1210 typical cable section is AWG12 for input connection and AWG10 for
output connection. Identify the function and location of each connection terminal using the wiring diagram on the corresponding data sheet, as an example:
Connect AC input mains power at terminal “L/+” and “N/-” to the “Supply Line” terminal block. Connect the terminal “ “ to the protective earth of the system.
Connect positive output at terminal “+” and negative output at terminal “-” to the “24 Vdc Output” terminal block (two connections provided).
Connect if required the alarm indication at terminal “+” and “-“ to the “Fault Output” terminal block, the alarm is provided by an optocoupled transistor normally closed (energized),
it de-energizes in fault condition of the power supply. In case of parallel or redundancy operation of the power supply, connect the terminal “CS” of the “Current Sharing Bus” terminal
block at each power supply in the system.
1.5*
Vin_min
1.2*Pout
Itar =
PSD1206, PSD1210 is a switching power supply housed in a light metal enclosure suitable for installation on T35 DIN Rail according to EN50022.
PSD1206, PSD1210 unit must be mounted with horizontal (standard) orientation for –20 to +60 °C ambient temperature operation range, ensuring a proper free space of 5 cm
around the enclosure to let the necessary air flow for convection cooling.
Standard Orientation (OK)
Non Standard Orientation (Not permitted)
where Itar = circuit breaker current, Pout = requested output power, Vin_min = minimum supply voltage.
Electrical connection of conductors up to 4.0 mm² are accommodated by plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or
causing any damage (for Zone 2 or Division 2 installations check the area to be nonhazardous before servicing). On the data sheet and enclosure side a block diagram identifies
all connections. The input line is internally protected by fuses (1 for each line); connect an automatic bipolar “C” intervention characteristics switch, upstream the power supply line or
other equipment to ensure compliance with local regulations. For the choice of the input automatic circuit breaker protection, it is opportune to use the following formula:

6 PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 Vdc G.M. International ISM0076-7
Installation and wiring must be in accordance to the relevant national or international installation standards (e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres
- Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified)
Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, and the Canadian Electrical Code CEC), make sure that conductors are well isolated from each other and
do not produce any unintentional connection. The enclosure provides, according to EN60529, an IP20 minimum degree of mechanical protection (or similar to NEMA Standard
250 type 1) for indoor installation, outdoor installation requires an additional enclosure with higher degree of protection (i.e. IP54 to IP65 or NEMA type 12-13) consistent with the
effective operating environment of the specific installation.
The power supply must be placed in an enclosure with IP4X protection degree when used in locations providing adequate protection against the entry of solid foreign
objects or water capable of impairing safety, or be placed in an enclosure with IP54 protection degree for other locations when used for Intrinsic Safety installations.
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts.
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
Start-up
Before powering the unit check that all wires are properly connected, particularly their polarity. Check conductors for exposed wires that could touch each other causing dangerous
unwanted shorts. Turn on power, the “power on” green led must be lit, check the supply voltage generated by PSD1206, PSD1210 is 24 Vdc.
High load fuse breaking capacity
Figure below shows the current waveform through the short circuit connection:
1) The peak short circuit current is about 430 A.
2) This peak current decays to 37 %
(time constant) within 0.5 msec.
3) The current decays to about 12 A within 1.5 msec.
4) The I2t of the short circuit current pulse is about
50 A2sec.
This Safety Manual summarizes the results of hardware assessment carried out on the PSD1206, PSD1210 Power Supply. The failure rates used in this analysis are the basic failure
rates from the Siemens standard SN 29500. According the table 2 of IEC 61508-1, the average PFD for systems operating in low demand mode has to be ≥1.00 E-03 to < 1.00 E-02
for SIL 2 safety functions. However, as the modules under consideration are only one part of an entire safety function, they have been certified claiming no more than 10% of this range.
For SIL 2 application the total PFDavg value of the SIF must be smaller than 1.00 E-02, hence the maximum allowable PFDavg value for the assed modules would then be 1.00 E-03.
The listed modules are considered to be Type A (“Non-complex” component with all failure modes well defined, for details see 7.4.3.1.2 of IEC 61508-2) components, with a hardware
fault tolerance of 0. According to table 2 of IEC61508-2, for Type A components the SFF has to be:
• less than 60% for SIL 1 (sub-) systems with a hardware fault tolerance of 0;
• between 60% and 90% for SIL 2 (sub-) systems with a hardware fault tolerance of 0;
• less than 60% for SIL 2 (sub-) systems with a hardware fault tolerance of 1;
• between 90% and 99% for SIL 3 (sub-) systems with a hardware fault tolerance of 0;
• between 60% and 90% for SIL 3 (sub-) systems with a hardware fault tolerance of 1.
Functional Safety Manual for Safety Related Systems and SIL2, SIL3 Applications

7
PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 VdcG.M. International ISM0076-7
Functional Safety Specifications from EXIDA analysis and report according IEC 61508 – IEC 61511
Model
PSD1206
Single Unit
NE Loads
PSD1206
Single Unit
ND Loads
PSD1210
Single Unit
NE Loads
PSD1210
Single Unit
ND Loads
PSD1206
2 Units
In parallel
NE Loads
PSD1206
2 Units
In parallel
ND Loads
PSD1210
2 Units
In parallel
NE Loads
PSD1210
2 Units
In parallel
ND Loads
Safety
Function
Isolated
Switching
Power
Supply
Isolated
Switching
Power
Supply
Isolated
Switching
Power
Supply
Isolated
Switching
Power
Supply
Isolated
Switching
Power
Supplies
Isolated
Switching
Power
Supplies
Isolated
Switching
Power
Supplies
Isolated
Switching
Power
Supplies
SFF
80.1 %
48.3 %
80.1 %
48.3 %
99.4 %
97.2 %
99.4 %
97.2 %
PFDavg
Per year
5.90 E-04
1.53 E-03
5.90 E-04
1.53 E-03
3.03 E-05
8.09 E-05
3.03 E-05
8.09 E-05
T Proof Test
(years)
for defined
SIL value
(10% of total
safety func.)
TI = 1 SIL 2
TI = 5 SIL 1
TI = 1 SIL 2
TI = 5 SIL 1
TI = 3 SIL 3
TI = 10 SIL 2
TI = 9 SIL 2
TI = 3 SIL 3
TI = 10 SIL 2
TI = 9 SIL 2
T Proof Test
(years)
for defined
SIL value
(20% of total
safety func.)
TI = 3 SIL 2
TI = 10 SIL 1
TI = 3 SIL 2
TI = 10 SIL 1
TI = 6 SIL 3
TI = 10 SIL 2
TI = 10 SIL 2
TI = 6 SIL 3
TI = 10 SIL 2
TI = 10 SIL 2
Hardware
Fault
Tolerance
EXIDA
or TÜV
analysis
Fail-Safe
Output
State
λSU
(FIT)
λDD
(FIT)
λDU
(FIT)
MTBF
(years)
0
0
0
0
1
1
1
1
Exida
Exida
Exida
Exida
Exida
Exida
Exida
Exida
<2V
20V<…<30V
20V<…<30V
<2V
20V<…<30V
20V<…<30V
<2V
20V<…<30V
20V<…<30V
<2V
20V<…<30V
20V<…<30V
542
327
542
327
1084
654
1084
654
0
0
0
0
0
0
0
0
135
350
135
350
6.9
18.5
6.9
18.5
134
(with
diagnostic)
134
(with
diagnostic)
134
(with
diagnostic)
134
(with
diagnostic)
79
(with
diagnostic)
112
(with
diagnostic)
79
(with
diagnostic)
112
(with
diagnostic)
In order to judge the failure behavior of the considered modules, the following definitions for the failure of the product must be considered:
• Fail-Safe State: The fail-safe state is defined as the output reaching the user defined threshold.
In normally energized (NE) loads, is defined as the output being between 20 V and 30 V (load current up to 80% of rated) or lower than 2V.
In normally de-energized (ND) loads, is defined as the output being between 20 V and 30 V (load current up to 80% of rated).
• Fail Safe: Fail that causes the output to go to the defined fail-safe state without a demand from the process.
• Fail Dangerous: with normally energized (NE) loads, failure that leads to an output higher than 30 V or between 2 V and 20 V.
With normally de-energized (ND) loads, failure that leads to an output higher than 30 V or lower than 20 V.
• Fail High: Failure mode that leads to an over voltage condition (> 30 V).
• Fail Low: Failure mode that leads to an under voltage condition (< 2 V).
• Fail “No Effect”: Failure mode of a component that is part of the safety function but has no effect on the safety function.
For the calculation of SFF it is treated like a safe undetected failure.
• Fail “Annunciation Undetected”: Failure mode that does not directly impact safety but does impact the ability to detect a future fault (such as a fault in a diagnostic circuit) and
that is not detected by internal diagnostics. For the calculation of SFF it is treated to 1 % as a dangerous failure and to 99 % as a no effect failure as in this system there are
3 different over voltage protection mechanism.
• Fail “Not part”: Failures of a component which is not part of the safety function but part of the circuit diagram and is listed for completeness.
When calculating the SFF this failure mode is not taken into account. It is also not considered for the total failure rate evaluation.
Definitions

8 PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 Vdc G.M. International ISM0076-7
• DC: Diagnostic coverage (safe or dangerous) of the safety logic solver for the considered module.
• DCs: Diagnostic coverage for safe failures = λsd / (λsd + λsu).
• DCd: Diagnostic coverage for dangerous failures = λdd / (λdd + λdu).
• FIT: Failure In Time (1x10 E-9 failures per hour).
• Failure Rates: The failure rate data used in the FMEDA analysis are the basic failure rates from the Siemens SN 29500 failure rate database. The rates where chosen in a way
that is appropriate for safety integrity level verification calculations, and to mach operating stress conditions typical of an industrial field environment similar to IEC 60654-1,
class C. It is expected that the actual number of field failures will be less than the number predicted by these failure rates.
• FMEA: Failure Modes and Effects Analysis is a systematic way to identify and evaluate the effects of different component failure modes, to determine what could eliminate or
reduce the chance of failure, and to document the system in consideration.
• FMEDA: Failure Modes Effects and Diagnostic Analysis is an FMEA extension. It combines standard FMEA techniques with extension to identify online diagnostics techniques
and the failure mode relevant to safety instrumented system design. It is a technique recommended to generate failure rates for each important category (safe detected, safe
undetected, dangerous detected, dangerous undetected, fail high, fail low) in the safety modules. The format for the FMEDA is an extension of the FMEA format MIL STD 1629A.
• Low demand mode: Mode where the frequency of demands for operation made on Safety-related system is no greater than one per year and no greater than twice the proof test
frequency.
• MTBF: Mean Time Between Failure.
• MTTF: Mean Time To Failure.
• MTTFS: Mean Time To safe Failure.
• MTTFD: Mean Time To dangerous Failure.
• MTTR: Mean Time To Repair.
• PFDavg: Average Probability of Failure on Demand.
• SFF: Safe Failure Fraction, according IEC 61508 summarizes the fraction of failures, which lead to a safe state and the fraction of failures which will be detected by diagnostic
measures and lead to a defined safety action.
General Terms
SUSD
D
U
D
D
DU
SUSD
D
U
D
D
SUSDDD
SFF
λ
λ
λ
λ
λ
λ
λ
λ
λ
λ
λ
λ
+++
−=
+++
++
=1
with: λDD: Dangerous Detected failure rate; λDU: Dangerous Undetected failure rate
λSD: Safe Detected failure rate; λSU: Safe Undetected failure rate
• SIF: Safety Instrumented Function.
• SIS: Safety Instrumented System.
• SIL: Safety Integrity Level.
• T Proof Test & Maintenance (TI): Proof Test Interval (for example 1 - 5 - 10 years, with 1 year = 8760 hours). Maintenance time is considered 8 hours.
The following assumptions have been made during the Failure Modes, Effects, and Diagnostic Analysis of the Switching Power Supply Types PSD1206 and PSD1210.
• Failure rates are constant, wear out mechanisms are not included.
• Propagation of failures is not relevant.
• Failures during parameterization are not considered.
• Sufficient test are performed prior to shipment to verify the absence of component supplier and/or manufacturing defects that prevent proper operation of specified functionality to
product specifications or cause operation different from design analyzed.
• The device is operated in the low demand mode of operation.
• The time to restoration or repair time after a safe failure is 8 hours, as MTTR.
• Only the described versions are used for safety applications.
• Practical fault insertion tests can demonstrate the correctness of the failure effects assumed during the FMEDAs.
• The fault output is not part of the safety function.
• The common cause factor βbetween the two crowbars is estimated at be 5 %.
• The stress levels are average for an industrial environment and the assumed environment is similar to IEC 60654-1, Class C (Sheltered location) with temperature limits within the
manufacturer’s rating and an average temperature over a long period of time of 40 °C. Humidity levels are assumed within manufacturer’s rating.
• The listed failure rates are valid for operating stress conditions typical of an industrial field environment similar to IEC 60654-1 class C with an average temperature over a long
period of time of 40 °C. For a higher average temperature of 60 °C, the failure rates should be multiplied with an experience based factor of 2.5. A similar multiplier should be
used if frequent temperature fluctuation must be assumed.
• Over voltage protection has a diagnostic coverage of 99 %.
• Safety Integrity Levels as defined in IEC 61508 and IEC 61511:
Assumptions
SIL
Safety Integrity Level
SIL 4
SIL 3
SIL 2
SIL 1
PFDavg
Average probability of failure
on demand per year
(low demand)
≥10-5 to < 10-4
≥10-4 to < 10-3
≥10-3 to < 10-2
≥10-2 to < 10-1
RRF
Risk Reduction Factor
From 100000 to 10000
From 10000 to 1000
From 1000 to 100
From 100 to 10
PFDavg
Average probability of dangerous
failure on demand per hour
(high demand)
≥10-9 to < 10-8
≥10-8 to < 10-7
≥10-7 to < 10-6
≥10-6 to < 10-5

9
PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 VdcG.M. International ISM0076-7
Note: green color indicates that PFDavg of the unit is less than 10 % of the PFDavg required by its SIL level, yellow color indicates that PFDavg of the unit is more than 10 % of the
PFDavg required by its SIL level.
PSD1206, PSD1210 Isolated Power Supply, single unit, NE loads
Failure rates:
Failure rates according to IEC 61508:
Summary of Data from EXIDA
Failure category Failure rates (FIT)
Total Fail Dangerous Undetected = λdu
Fail Dangerous Undetected
Fail High (1% of Total Fail High)
Fail “Annunciation Undetected” (1% of Total Fail “Ann. Undet.”)
Total Fail Safe Undetected = λsu
Fail High (99% of Total Fail High)
Fail Low
Fail “Annunciation Undetected” (99% of Total Fail “Ann. Undet.”)
Fail “Not Part” = λnotpart
MTBF = MTTF + MTTR = 1 / (λsd + λsu + λdd + λdu + λnotpart) + MTTR
MTTFS= 1 / (λsd + λsu)
134.80
134.00
0.21
0.59
542.20
20.79
215.00
58.41
174.00
134 years
210 years
Fail “No Effect” 214.00
Λsd
0.00 FIT
λsu
542.20 FIT
λdd
0.00 FIT
λdu
134.80 FIT
SFF
80.09%
PFDavg vs T[Proof], with determination of SIL supposing module contributes 10% of entire safety function:
T[Proof] = 1 year
PFDavg = 5.90 E-04
Valid for SIL 2
See Note 2 in the section Notes
T[Proof] = 3 years
PFDavg = 1.77 E-03
See Note 3 and Note 4
In the section Notes
T[Proof] = 6 years
PFDavg = 3.54 E-03
See Note 3 and Note 4
In the section Notes
Total Fail Dangerous Detected = λdd 0.00
Total Fail Safe Detected = λsd 0.00
Fail Safe Undetected 34.00
Total Failure Rate (Safety Function) = λsd + λsu + λdd + λdu 677.00
Total Failure Rate (Device) = λsd + λsu + λdd + λdu + λnotpart 851.00
MTTFD= 1 / λdu 847 years
T[Proof] = 10 years
PFDavg = 5.90 E-03
See Note 3 and Note 4
In the section Notes
PFDavg vs T[Proof], with determination of SIL supposing module contributes 20% of entire safety function:
T[Proof] = 1 year
PFDavg = 5.90 E-04
Valid for SIL 2
See Note 7 in the section Notes
T[Proof] = 3 years
PFDavg = 1.77 E-03
Valid for SIL2
See Note 7 in the section Notes
T[Proof] = 6 years
PFDavg = 3.54 E-03
See Note 8 and Note 9
In the section Notes
T[Proof] = 10 years
PFDavg = 5.90 E-03
See Note 8 and Note 9
In the section Notes

10 PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 Vdc G.M. International ISM0076-7
PSD1206, PSD1210 Isolated Power Supply, 2 units in parallel
One way to calculate the PFDavg of a system with 2 power supply units in parallel architecture is by using the fault tree as presented in following figure:
System of two PSD12xx connected in
parallel architecture fails undetected
OR
Both PSD12xx fail because of
common cause (ß = 5 %)
First PSD12xx
fails undetected
&
Second PSD12xx
fails undetected
PSD1206, PSD1210 Isolated Power Supply, single unit, ND loads
Failure rates:
Failure rates according to IEC 61508:
Λsd
0.00 FIT
λsu
327.20 FIT
λdd
0.00 FIT
λdu
349.80 FIT
SFF
48.33%
PFDavg vs T[Proof], with determination of SIL supposing module contributes 10% of entire safety function:
Failure category Failure rates (FIT)
Total Fail Dangerous Undetected = λdu
Fail Dangerous Undetected
Fail High (1% of Total Fail High)
Fail “Annunciation Undetected” (1% of Total Fail “Ann. Undet.”)
Total Fail Safe Undetected = λsu
Fail High (99% of Total Fail High)
Fail Low
Fail “Annunciation Undetected” (99% of Total Fail “Ann. Undet.”)
Fail “Not Part” = λnotpart
MTBF = MTTF + MTTR = 1 / (λsd + λsu + λdd + λdu + λnotpart) + MTTR
MTTFS= 1 / (λsd + λsu)
349.80
134.00
0.21
0.59
327.20
20.79
215.00
58.41
174.00
134 years
349 years
Fail “No Effect” 214.00
Total Fail Dangerous Detected = λdd 0.00
Total Fail Safe Detected = λsd 0.00
Fail Safe Undetected 34.00
Total Failure Rate (Safety Function) = λsd + λsu + λdd + λdu 677.00
Total Failure Rate (Device) = λsd + λsu + λdd + λdu + λnotpart 851.00
MTTFD= 1 / λdu 326 years
PFDavg vs T[Proof], with determination of SIL supposing module contributes 20% of entire safety function:
T[Proof] = 1 year
PFDavg = 1.53 E-03
Valid for SIL 1
See Note 9 in the section Notes
T[Proof] = 10 years
PFDavg = 1.53 E-02
Valid for SIL1
See Note 9 in the section Notes
T[Proof] = 1 year
PFDavg = 1.53 E-03
Valid for SIL 1
See Note 4 in the section Notes
T[Proof] = 5 years
PFDavg = 7.66 E-03
Valid for SIL 1
See Note 4 in the section Notes
T[Proof] = 9 years
PFDavg = 1.38 E-02
See Note 5 in the section Notes
T[Proof] = 10 years
PFDavg = 1.53 E-02
See Note 5 in the section Notes

11
PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 VdcG.M. International ISM0076-7
The probability of this system to fail is calculated as follows, considering 5 % βcommon cause factor, between the two power supply units PSD12xx:
()
()
()
2
_ System _ PSD12xx _ PSD12xx
2
() () ()1
1
22
AVG AVG AVG
DU DU
TI x years TI x years TI x yearsPFD PFD PFD
TI TI
ββ
βλ β λ
== ==⋅ + − ⋅ =
⎛⎞
=⋅ ⋅ + − ⋅ ⋅
⎜⎟
⎝⎠
where = Dangerous Undetected failure rate of PSD12xx; = Proof Test Interval.
D
U
λ
TI
NE loads
For 2 power supply units in parallel architecture driving NE loads, it’s possible to calculate the system probability to fail for different values by using previous
TI
_System ()
AVG TI x yearsPFD =equation and replacing _ PSD12xx ()
AVG TI x yearsPFD =or
D
U
λ
with values in NE loads tables (pag.11)
In following table, it’s reported the _System()
AVG TI x yearsPFD =with determination of SIL supposing module contibutes 10% of total SIF
ND loads
For 2 power supply units in parallel architecture driving ND loads, it’s possible to calculate the system probability to fail for different values by using previous
TI
_System ()
AVG TI x yearsPFD =equation and replacing _ PSD12xx ()
AVG TI x yearsPFD =or
D
U
λ
with values in ND loads tables (pag.12)
In following table, it’s reported the _System ()
AVG TI x yearsPFD =with determination of SIL supposing module contributes 10% of total SIF
T[Proof] = 1 year
PFDavg = 3.03 E-05
Valid for SIL 3
See Note 1 in the section Notes
T[Proof] = 3 years
PFDavg = 9.34 E-05
Valid for SIL 3
See Note 1 in the section Notes
T[Proof] = 6 years
PFDavg = 1.90 E-04
Valid for SIL 2
See Note 2 in the section Notes
T[Proof] = 10 years
PFDavg = 3.41 E-04
Valid for SIL 2
See Note 2 in the section Notes
T[Proof] = 1 year
PFDavg = 8.09 E-05
Valid for SIL 2
See Note 2 in the section Notes
T[Proof] = 5 years
PFDavg = 4.65 E-04
Valid for SIL 2
See Note 2 in the section Notes
T[Proof] = 9 years
PFDavg = 9.40 E-04
Valid for SIL 2
See Note 2 in the section Notes
T[Proof] = 10 years
PFDavg = 1.10 E-03
See Note 3 and Note 4
in the section Notes
In following table, it’s reported the _System ()
AVG TI x yearsPFD =with determination of SIL supposing module contibutes 20% of total SIF
T[Proof] = 1 year
PFDavg = 3.03 E-05
Valid for SIL 3
See Note 6 in the section Notes
T[Proof] = 3 years
PFDavg = 9.34 E-05
Valid for SIL 3
See Note 6 in the section Notes
T[Proof] = 6 years
PFDavg = 1.90 E-04
Valid for SIL 3
See Note 6 in the section Notes
T[Proof] = 10 years
PFDavg = 3.41 E-04
Valid for SIL 2
See Note 7 in the section Notes
In following table, it’s reported the _System ()
AVG TI x yearsPFD =with determination of SIL supposing module contibutes 20% of total SIF
T[Proof] = 1 years
PFDavg = 8.09 E-05
Valid for SIL 2
See Note 6 in the section Notes
T[Proof] = 10 years
PFDavg = 1.10 E-03
Valid for SIL 2
See Note 6 in the section Notes
PSD1206, PSD1210 Isolated Power Supply, 3 units in parallel
For 3 power supply units in parallel architecture, it’s possible to calculate the system probability to fail for different values by using the following equation:
TI
()
()
3
_System ()
1
24
DU
AVG DU
TI x years
TI
TI
PFD
βλ
βλ
=−⋅ ⋅
≅⋅ ⋅ +
NE Loads
T[Proof] = 1 year
PFDavg = 2.99 E-05
Valid for SIL 3
See Note 1 in the section Notes
T[Proof] = 3 years
PFDavg = 8.96 E-05
Valid for SIL 3
See Note 1 in the section Notes
T[Proof] = 10 years
PFDavg = 2.99 E-04
Valid for SIL 2
See Note 2 in the section Notes
Where β= 5 %; = Dangerous Undetected failure rate of PSD12xx; = Proof Test Interval
D
U
λ
TI
In following table, it’s reported the _System()
AVG TI x yearsPFD =, with determination of SIL supposing module contributes 10% of total SIF
Use previous _System ()
AVG TI x yearsPFD =equation and replace
D
U
λ
with value 134.80 FIT

12 PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 Vdc G.M. International ISM0076-7
PSD1206, PSD1210 Isolated Power Supply, fail with over voltage condition
One way to calculate the probability that the Power Supply types PSD1206 and PSD1210 fail with an over voltage condition is by using the fault tree as presented in following figure:
Over voltage condition
&
Power Supply fails
with over voltage
Both crowbars fail
because of common caus
e
Over voltage protection
fails undetected
Crowbars
fail undetected
≥1
&
Crowbar 2
fails undetected
Crowbar 1
fails undetected
When using fault trees, the PFD should be calculated for multiple time steps (e.g. each hour) and then averaged over the time period of interest. The probability of the system to fail with
an over voltage condition is calculated as follows for each time step:
PFDAVG_OC_Sys = PFD_OC_PS * PFD_OP * PFD_CB
PFD_CB = PFD_CB1 * PFD_CB2 + β* PFD_CB12
PFD_OC_PS (Tproof = 1 year) = 1.84 E-04
PFD_OP (Tproof = 1 year) = 9.64 E-05
PFD_CB1 (Tproof = 1 year) = PFD_CB2 (Tproof = 1 year) = 2.10 E-04
PFD_CB12 (Tproof = 1 year) = 2.11 E-04
β* PFD_CB12 (Tproof = 1 year) = 0.05 * 2.11 E-04 = 1.05 E-05
PFD_CB (Tproof = 1 year) = 1.06 E-05
PFDAVG_OC_Sys (Tproof = 1 year) = 9.36 E-14
Notes
• Note 1: Considering a SIL 3 application, the total PFDavg value of the SIF must be < 1.00 E-03 according to table 2 of IEC 61508-1 and table 3.1 of ANSI/ISA-84.01-1996.
However, as the module under consideration contributes for only 10% of the entire SIF, the PFDavg value of the module must be ≤1.00 E-04. This limit is satisfied from the
calculated PFDavg value, therefore the module is valid for SIL 3 application.
• Note 2: Considering a SIL 2 application, the total PFDavg value of the SIF must be < 1.00 E-02 according to table 2 of IEC 61508-1 and table 3.1 of ANSI/ISA-84.01-1996.
However, as the module under consideration contributes for only 10% of the entire SIF, the PFDavg value of the module must be ≤1.00 E-03. This limit is satisfied from the
calculated PFDavg value, therefore the module is valid for SIL 2 application.
• Note 3: Considering a SIL 2 application, the total PFDavg value of the SIF must be < 1.00 E-02 according to table 2 of IEC 61508-1 and table 3.1 of ANSI/ISA-84.01-1996.
However, as the module under consideration contributes for only 10% of the entire SIF, the PFDavg value of the module must be ≤1.00 E-03. This limit is NOT satisfied from the
calculated PFDavg value, therefore the module is NOT valid for SIL 2 application, but it’s ok for SIL 1.
• Note 4: Considering a SIL 1 application, the total PFDavg value of the SIF must be < 1.00 E-01 according to table 2 of IEC 61508-1 and table 3.1 of ANSI/ISA-84.01-1996.
However, as the module under consideration contributes for only 10% of the entire SIF, the PFDavg value of the module must be ≤1.00 E-02. This limit is satisfied from the
calculated PFDavg value, therefore the module is valid for SIL 1 application.
• Note 5: Considering a SIL 1 application, the total PFDavg value of the SIF must be < 1.00 E-01 according to table 2 of IEC 61508-1 and table 3.1 of ANSI/ISA-84.01-1996.
However, as the module under consideration contributes for only 10% of the entire SIF, the PFDavg value of the module must be ≤1.00 E-02. This limit is NOT satisfied from the
calculated PFDavg value, therefore the module is NOT valid for SIL 1 application.
• Note 6: Considering a SIL 3 application, the total PFDavg value of the SIF must be < 1.00 E-03 according to table 2 of IEC 61508-1 and table 3.1 of ANSI/ISA-84.01-1996.
However, as the module under consideration contributes for only 20% of the entire SIF, the PFDavg value of the module must be ≤2.00 E-04. This limit is satisfied from the
calculated PFDavg value, therefore the module is valid for SIL 3 application.
• Note 7: Considering a SIL 2 application, the total PFDavg value of the SIF must be < 1.00 E-02 according to table 2 of IEC 61508-1 and table 3.1 of ANSI/ISA-84.01-1996.
However, as the module under consideration contributes for only 20% of the entire SIF, the PFDavg value of the module must be ≤2.00 E-03. This limit is satisfied from the
calculated PFDavg value, therefore the module is valid for SIL 2 application.
• Note 8: Considering a SIL 2 application, the total PFDavg value of the SIF must be < 1.00 E-02 according to table 2 of IEC 61508-1 and table 3.1 of ANSI/ISA-84.01-1996.
However, as the module under consideration contributes for only 20% of the entire SIF, the PFDavg value of the module must be ≤2.00 E-03. This limit is NOT satisfied from the
calculated PFDavg value, therefore the module is NOT valid for SIL 2 application, but it’s ok for SIL 1.
• Note 9: Considering a SIL 1 application, the total PFDavg value of the SIF must be < 1.00 E-01 according to table 2 of IEC 61508-1 and table 3.1 of ANSI/ISA-84.01-1996.
However, as the module under consideration contributes for only 20% of the entire SIF, the PFDavg value of the module must be ≤2.00 E-02. This limit is satisfied from the
calculated PFDavg value, therefore the module is valid for SIL 1 application.
• Note 10: It is important to realize that the “No Effect” failures and the “Annunciation Undetected” failures are included in the Safe Undetected failure category according to
IEC 61508. Note that these failures themselves will not affect system reliability or safety, and should not be included in spurious trip calculations.
ND Loads
T[Proof] = 1 year
PFDavg = 7.80 E-05
Valid for SIL 2
See Note 2 in the section Notes
T[Proof] = 10 years
PFDavg = 7.87 E-04
Valid for SIL 2
See Note 2 in the section Notes
In following table, it’s reported the _System()
AVG TI x yearsPFD =, with determination of SIL supposing module contributes 10% of total SIF
Use previous _System ()
AVG TI x yearsPFD =equation and replace
D
U
λ
with value 349.80 FIT

13
PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 VdcG.M. International ISM0076-7
MODEL PSD1210
++-- -+ L/+N/-
=
_
CS
Current
Sharing
Fault
Output 1
Supply
Input 1
24 Vdc
Output Bus
MODEL PSD1210
++-- -+ L/+N/-
=
_
CS
Current
Sharing
Fault
Output 2
Supply
Input 2
Connection for current sharing
SIL 3
Draft about connection of 2 units PSD1210 in parallel mode.
Maximum load current
required to the power
supply system
(A)
Number of power supply units
at least required to satisfy
maximum load current
N
Number of power supply units,
with redundancy required for
normal operation of system
N+1
Number of power supply units,
with redundancy required for
normal operation and during
T-proof periodic test of system
N+2
10 1 2 3
20 2 3 4
30 3 4 5
40 4 5 6
50 5 6 7
For NE load:
a) SIL 2 with T-proof = 1 year;
b) SIL 2 with T-proof = 3 years.
For ND load:
c) SIL 1 with T-proof = 5 years;
d) SIL 1 with T-proof = 10 years.
During T-proof of each power supply
unit, the power supply system can not
sustain the maximum load current
because redundancy (N+1) is absent.
For NE load:
a) SIL 3 with T-proof = 3 years or
SIL 2 with T-proof = 10 years;
b) SIL 3 with T-proof = 6 years or
SIL 2 with T-proof = 10 years.
For ND load:
c) SIL 2 with T-proof = 9 years or
SIL 1 with T-proof = 10 years;
d) SIL 2 with T-proof = 10 years.
During T-proof of each power supply
unit, the power supply system can
sustain the maximum load current but
SIL value changes from SIL 3 to
SIL 2 (for NE load) or from SIL 2 to
SIL 1 (for ND load), because
redundancy (N+2) is absent.
For NE load:
a) SIL 3 with T-proof = 3 years;
b) SIL 3 with T-proof = 6 years.
For ND load:
c) SIL 2 with T-proof = 9 years;
d) SIL 2 with T-proof = 10 years.
During T-proof of each power supply
unit, the power supply system can
sustain the maximum load current
and maintain SIL 3 value (for NE
load) or SIL 2 value (for ND load),
because redundancy (N+2) is
present.
Number of power supply units connected in parallel for different maximum load currents required to the power supply system.
To maintain the power supply system safety integrity level, SIL 2 (ND loads) or SIL 3 (NE loads), also during the T-proof periodic test, in addition two redundant units for each
system are required.
If N is the number of power supply units connected in parallel, for the maximum load current required to the power supply system without redundancy, the total number of modules
must be N+2.
Maintaining SIL level during T-proof test in redundant architecture

14 PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 Vdc G.M. International ISM0076-7
According to section 7.4.3.2.2 f) of IEC 61508-2 proof test shall be undertaken to reveal dangerous faults which are undetected by diagnostic tests. This means that it is necessary
to specify how dangerous undetected fault which have been noted during the FMEDA can be detected during proof testing.
Proof tests should be carried out by qualified service instrumentation technicians. Any failures or faults should be reported to G.M. International.
This procedure specifies the type of test that must be carried on the supply unit at the end of the T-proof period of operation to verify the correct operation of protection circuits in
the supply unit required to restore the Safety Integrity Level required.
The functions to be tested are:
Proof test 1: Current sharing capability.
Proof test 2: Paralleling diode operation .
Proof test 3: Crowbar A operation.
Proof test 4: Crowbar B operation.
Proof test 5: Over voltage protection.
Possible Proof Tests to reveal Dangerous Undetected Faults
Ammeter range 0 to 10 A (0.1 A resolution or better)
300 W variable resistor load, from 2 to 25 Ω, current up to 10 A to test PSD1210
or 150 W variable resistor load, from 4 to 25 Ω, current up to 6 A to test PSD1206
A1, A2, A3
PR
Voltmeter range 30 V, Resolution 1 mV. V1, V2, V3
Calibrator, to set 100 mA current CAL
IdentificationRequired instrumentation
Overvoltage crowbar test Jig TPF1210 (with cables) TPF1210
SW1 = Vout Control
SW2 = Over Voltage Protection
SW3 = Crowbar A
SW4 = Crowbar B
TPF1210
13
14
1
2
3
4
5
6
7
8
15
16
17
18
19
20
Overvoltage Crowbar
Test Jig
Multi-core cable Jig 5-poles Multi-core cable Jig 6-poles
20
16
15
1918
14
17
13
1 2 3 4
5 6 7 8
Vout Adjust
TPF1210
Diode Test
ON OFF
1
2
3
4
Multi-core cable Jig 5-poles
Multi-core cable Jig 6-poles
P1 = Potentiometer
-+
PSD1210 (PSD1206)
Side view

15
PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 VdcG.M. International ISM0076-7
Procedure
Supply both units under test and set the variable load resistor PR so that maximum load is applied to the connected power supplies,
verifying through A1 that load current is 10 A (6 A for PSD1206).
Note that load current A1 will be shared by the two power supplies, therefore A2 and A3 = 5 A
Step
1
Disconnect “current sharing” connection2
Current sharing:
Connect the two power supplies as shown in the following image:
MODELS
PSD1210
PSD1206
Regulate the second’s power supply voltage (V2) by rotating its “Vout Adjust” trimmer clockwise, until obtaining 24.6 V3
Verify that output current (A3) is at 75% of full load and that output current (A2) is instead at 25%4
Re-connect “current sharing” connection and verify that voltage are approximately the same (V1 ≈V2)5
Verify that output current (A3) is about 60% of full load and that output current (A2) is instead about 40%6
Regulate the second’s power supply voltage (V2) by rotating its “Vout Adjust” trimmer counter-clockwise, until obtaining 24 V7
Turn off both power supplies8
++-- -+
=
_
CS
Sharing
current
++-- -+
=
_
CS
Sharing
current
Current sharing connection
PR
L/+ N/-
V1
+
V2
+
A2
+
A3
+
220 Vac
L/+ N/-
220 Vac
A1
+
D2
D1
S2
COM
S1
C2
C1
B2
B1
A2
A1
D2
D1
S2
COM
S1
C2
C1
B2
B1
A2
A1
PS UNDER TEST SECOND PS
MODELS
PSD1210
PSD1206

16 PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 Vdc G.M. International ISM0076-7
ProcedureStep
Connect the “overvoltage crowbar test jig” (TPF1210) to the PS under test and set TPF1210 with the following configuration:
SW1=OFF, SW2=OFF, SW3=OFF, SW4=OFF and potentiometer P1 completely rotated clockwise
1
Turn on power supply under test and regulate the load current (A1) until obtaining 10 A (6A for PSD1206)2
Connect voltmeter (V2) to “Out diodes” pins of “overvoltage crowbar test jig” and check that voltage drop is between 0.3V and 0.7V3
Turn on the second PS4
Turn off the PS under test5
Check that voltage (V2) between the diodes is between -22 V and -26 V6
Paralleling diode operation:
Connect the two power supplies as shown in the following image:
Turn off also the second PS and disconnect voltmeter V2 from the “Out diodes” pins of the “overvoltage crowbar test jig”7
MODELS
PSD1210
PSD1206
MODELS
PSD1210
PSD1206
++-- -+
=
_
CS
Sharing
current
++-- -+
=
_
CS
Sharing
current
Current sharing connection
PR
D2
D1
S2
COM
S1
C2
C1
B2
B1
A2
A1
L/+ N/-
V1
+
V2
+
A1
+
A2
+
220 Vac
L/+ N/-
220 Vac
V2
+
4321
ON
OFF
+
-
Vout
adjust
Diode test
TPF1210
D2
D1
S2
COM
S1
C2
C1
B2
B1
A2
A1
PS UNDER TEST SECOND PS

17
PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 VdcG.M. International ISM0076-7
Procedure
With PS switched OFF, set the “overvoltage crowbar test jig” (TPF1210) as follows: SW1=OFF, SW2=ON, SW3=OFF, SW4=ON
Test
1
Rotate Potentiometer (P1) of the “overvoltage crowbar test jig” clockwise to obtain the maximum resistance (10 KΩ)
2
Output voltage value (V1) should be greater than 24 V nominal at 80% of full load. Now, after checking this condition,
rotate potentiometer (P1) counter-clockwise slowly to decrease its resistance and observe that the corresponding output voltage
(V1) increases simultaneously while rotating.
4
At this point “Crowbar A” will trigger the shortcircuit and output voltage (V1) will be < 2 V. Maximum voltage (V1)
obtained just before the crowbar’s trigger point should be between 27.0 V and 29.0 V
5
Turn off the PS immediately by opening the supply switch (I1) so that the “crowbar” is reset6
Rotate potentiometer (P1) clockwise completely to obtain maximum resistance7
Crowbar A operation:
Connect the power supply as shown in the following image:
MODELS PSD1210 - PSD1206
Turn on the PS by closing switch I13
+
-
CS
Sharing
current
+
+
-
-
I1
=
_
PR
+
A1
V1
+
L/+
N/-
220 Vac
4321
ON
OFF
+
-
Vout
adjust
Diode test
TPF1210
C2
C1
B2
B1
A2
A1
D2
D1
S2
COM
S1

18 PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 Vdc G.M. International ISM0076-7
Procedure
After “Crowbar A test”, continue setting the “overvoltage crowbar test jig” (TPF1210): SW1=OFF, SW2=ON, SW3=ON, SW4=OFF
Step
1
Turn on the PS by closing switch I12
3
At this point “Crowbar B” will trigger the shortcircuit and output voltage (V1) will be < 2 V. Maximum voltage (V1)
obtained just before the crowbar’s trigger point should be between 27.0 V and 29.0 V
4
Turn off the PS immediately by opening the supply switch (I1) so that the “crowbar” is reset5
Crowbar B operation:
Connect the power supply as shown in the following image
Output voltage value (V1) should be greater than 24 V nominal at 80% of full load. Now, after checking this condition,
rotate potentiometer (P1) counter-clockwise slowly to decrease its resistance and observe that the corresponding output voltage
(V1) increases simultaneously while rotating.
MODELS PSD1210 - PSD1206
Rotate potentiometer (P1) clockwise completely to obtain maximum resistance6
+
-
CS
Sharing
current
+
+
-
-
I1
=
_
PR
+
A1
V1
+
L/+
N/-
220 Vac
4321
ON
OFF
+
-
Vout
adjust
Diode test
TPF1210
C2
C1
B2
B1
A2
A1
D2
D1
S2
COM
S1

19
PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 VdcG.M. International ISM0076-7
Procedure
Set the “overvoltage crowbar test jig” (TPF1210): SW1=ON, SW2=OFF, SW3=ON, SW4=ON
Step
1
Turn on the PS by closing switch I12
Verify that the output voltage (V1) is between 25.5V and 28V nominal at 80% of full load and without load3
Overvoltage Protection operation:
Connect the power supply as shown in the following image:
MODELS PSD1210 - PSD1206
Turn off the PS4
+
-
CS
Sharing
current
+
+
-
-
I1
=
_
PR
+
A1
V1
+
L/+
N/-
220 Vac
4321
ON
OFF
+
-
Vout
adjust
Diode test
TPF1210
C2
C1
B2
B1
A2
A1
D2
D1
S2
COM
S1

20 PSD1206 - PSD1210 - SIL 3 - SIL 2 Switching Power Supply 24 Vdc G.M. International ISM0076-7
Although a constant failure rate is assumed by the probabilistic estimation method, this only applies provided that the useful lifetime of components is not exceeded. Beyond this useful
lifetime, the result of the probabilistic calculation method is meaningless as the probability of failure significantly increases with time. The useful lifetime is highly dependent on the
component itself and its operating conditions, temperature in particular (for example, electrolyte capacitors can be very sensitive to temperature). This assumption of a constant failure
rate is based on the bathtub curve, which shows the typical behavior for electronic components. Therefore it is obvious that PFDavg calculation is only valid for components that have this
constant domain and that the validity of the calculation is limited to the useful lifetime of each component. It is assumed that early failures are detected to a huge percentage during the
installation period and therefore the assumption of a constant failure rate during the useful lifetime is valid. However, according to section 7.4.7.4 of IEC 61508-2, a useful lifetime, based
on experience, should be assumed. According to section 7.4.7.4 note 3 of the IEC 61508-2 experience has shown that the useful lifetime often lies within a range of about 10-15 years.
Impact of lifetime of critical components on Failure Rate
The equation of PFDavg, applicable when the component or sub-system is new and when λdu are 99 % known by proof test is:
When these tests do not detect at least 99 % of λdu the same equation changes to:
where: Et is the effectiveness of proof test (0-100 %), SL can be intended as:
1) Time between two proof tests with 99-100 % effectiveness;
2) Time between two replacements;
3) Component Life time if no substitution and no proof test is meant to be done.
For TI = 1 year the equation becomes:
Example 1:
λdu = 0.01 / yr ; TI = 1 yr ; SL = 12 yrs ; Et = 90 % = 0.9 ; PFDavg = 0.0002 / yr
At installation: PFDavg = 0.01 / 2 = 0.005 / yr ; RRF = 1 / PFDavg = 1 / 0.005 = 200 (Suitable for SIL 2)
After 1 yr: PFDavg = (0.9 x 0.01/2) + (0.1 x 0.01 x 6) = 0.0105 ; RRF = 95 (Suitable for SIL 1)
Example 2:
λdu = 0.01 / yr ; TI = 1 yr ; SL = 12 yrs ; Et = 99 % = 0.99 ; PFDavg = 0.0002 / yr
At installation: PFDavg = 0.01 / 2 = 0.005 / yr ; RRF = 1 / PFDavg = 1 / 0.005 = 200 (Suitable for SIL 2)
After 1 yr: PFDavg = (0.99 x 0.01/2) + (0.01 x 0.01 x 6) = 0.0056 ; RRF = 178 (Suitable for SIL 2)
2
TI
duPFDavg ×=
λ
2
)1()
2
(SL
duEt
TI
duEtPFDavg ××−+××=
λλ
()
1
22
du SL
PFDavg Et Et du
λλ
⎛⎞
⎜⎟
⎜⎟
⎝⎠
=× +−× ×
Influence of PFDavg calculation on efficiency of Proof Test for a 1oo1 architecture.
MODELS PSD1206 - PSD1210
++- - -+ L/+N/-
=
_
CS
Current
Sharing
Fault
Output 1
Supply
Input 1
48 Vdc
Output Bus
MODELS PSD1206 - PSD1210
++- - -+ L/+N/-
=
_
CS
Current
Sharing
Fault
Output 2
Supply
Input 2
SIL 3
48 Vdc Output with connection in series of power supplies
To obtain higher output voltage of 48 V, it is possible to connect two modules in series as shown below. Output voltage can be furtherly increased by connecting more units in series.
NOTE: In this configuration, Current Sharing feature is not available, therefore current sharing connection (CS) must not be used.
This manual suits for next models
1
Table of contents
Other GM International Power Supply manuals
Popular Power Supply manuals by other brands

Techroutes
Techroutes TSR 2800-10C Hardware installation manual

Matsusada Precision
Matsusada Precision eK-FG2 instruction manual

Delta Electronics
Delta Electronics DPS-300AB-5 Specifications

patura
patura p30 user manual

Black & Decker
Black & Decker POWER TO GO P2G7B instruction manual

Bpt
Bpt VAS/101 installation instructions