GMI D5091S Instruction Manual

D5091 - 5 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition G.M. International ISM0110-12
5 A SIL 3 Relay Output Module for ND Load
with ND or NE Relay condition
DIN-Rail and Termination Board, Model D5091S
D5091S
INSTRUCTION & SAFETY MANUAL

2 D5091 - 5 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition G.M. International ISM0110-12
General Description: The single channel Relay Output, D5091S is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed.2
for high risk industries. It provides isolation between input and output contacts.
Two mutually exclusive (by DIP-Switch programming) monitoring circuits are provided:
1) line input monitoring, to allow DCS/PLC line monitoring function: when enabled, the module permits a wide compatibility towards different DCS/PLC. Driving line pulse testing,
executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and LED flickering.
2) low voltage input monitoring: when enabled, the module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold.
D5091S provides 1 SPDT contact for two different safety functions:
1) SIL 3 Safety Function for Normally De-Energized load (energized in fail safe state) is available at Terminal Blocks 7-8. The driving signal is normally low (0 Vdc),
the relay is normally de-energized, contact is open and load is de-energized. The safety function is met when the driving signal is high (24 Vdc), the relay is energized,
contact is closed and load is energized. At Terminal Blocks 9-10 is also available a service contact (for service load) with opposite (not SIL) function.
2) SIL 3 Safety Function for Normally De-Energized load (energized in fail safe state) is available at Terminal Blocks 9-10. The driving signal is normally high (24 Vdc),
the relay is normally energized, contact is open and load is de-energized. The safety function is met when the driving signal is low (0 Vdc), the relay is de-energized,
contact is closed and load is energized. At Terminal Blocks 7-8 is also available a service contact (for service load) with opposite (not SIL) function.
Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2 or Class I, Zone 2.
Functional Safety Management Certification:
G.M. International is certified by TUV to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3.
Technical Data
Characteristics
Input: 24 Vdc nom (21.6 to 27.6 Vdc) reverse polarity protected, ripple within voltage limits ≤5 Vpp.
The following monitoring circuits are mutually exclusive:
1) Line input monitoring (DIP-Switch selectable): to allow DCS/PLC line monitoring function (pulse test).
2) Voltage monitoring (DIP-Switch selectable): ≥21.6 Vdc for normal operation, ≤17 Vdc reflects a high impedance (≤10 mA consumption) to the control device.
Current consumption @ 24 V: 35 mA with relay energized and line input monitoring disabled, 45 mA with relay energized and line input monitoring enabled, typical.
Power dissipation: 0.85 W with 24 V input voltage, relay energized and line input monitoring disabled, 1.1 W with 24 V input voltage, relay energized and line input monitoring
enabled, typical.
Isolation (Test Voltage): Input/Output 2.5 KV.
Output: voltage free SPDT relay contact.
Terminals 7-8, open when relay de-energized, close in energized condition. Terminals 9-10, close when relay de-energized, open in energized condition.
Contact material: Ag Alloy (Cd free), gold plated.
Contact rating: 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load), 1 A 24 Vdc, 220 mA 125 Vdc, 110 mA 250 Vdc for UL. Min.Switching current 1 mA.
Contact inrush current: 6 A at 24 Vdc, 250 Vac.
AC / DC Load breaking capacity:
Mechanical / Electrical life: 5 * 106/ 3 * 104operation, typical.
Operate / Release time: 8 / 4 ms typical.
Bounce time NO / NC contact: 3 / 8 ms, typical.
Frequency response: 10 Hz maximum.
Compatibility:
CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions:
Operating temperature: temperature limits -40 to +70 °C. Operating relative humidity: relative humidity 95 %, up to 55 °C.
Max altitude: 2000 m a.s.l. Storage temperature: temperature limits -45 to +80 °C.
Safety Description:
ATEX: II 3G Ex nA nC IIC T4 Gc; IECEx / INMETRO / NEPSI: Ex nA nC IIC T4 Gc
UL: NI / I / 2 / ABCD / T4; C-UL: NI / I / 2 / ABCD / T4
FM: NI / I / 2 / ABCD /T4, I / 2 / AEx nA nC / IIC /T4; FMC: NI / I / 2 / ABCD /T4, I / 2 / Ex nA nC / IIC /T4
EAC-EX: 2ExnAnCIICT4 X.
UKR TR n. 898: 2ExnAnCIICT4 X.
non-sparking electrical equipment.
-40 °C ≤Ta ≤70 °C.
Approvals:
BVS 10 ATEX E 114 conforms to EN60079-0, EN60079-15.
IECEx BVS 10.0072 X conforms to IEC60079-0, IEC60079-15.
INMETRO DNV 13.0109 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-15.
UL & C-UL E477485 conforms to ANSI/UL508
FM 3046304 and FMC 3046304C conforms to Class 3600, 3611, 3810, ANSI/ISA-60079-0, ANSI/ISA-60079-15, C22.2 No.142, C22.2 No.213, C22.2 No. 60079-0, C22.2 No. 60079-15.
C-IT.ME92.B.00206 conforms to GOST 30852.0, 30852.14.
CЦ16.0036 X conforms to ДСТУ 7113, ДСТУ IЕС 60079-15.
GYJ14.1406X conforms to GB3836.1, GB3836.8.
TÜV Certificate No. C-IS-236198-04, SIL 3 conforms to IEC61508:2010 Ed.2.
TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety.
DNV Type Approval Certificate No.A-13625 and KR No.MIL20769-EL002 Certificates for maritime applications.
Mounting: EN/IEC60715 TH 35 DIN-Rail or on customized Termination Board.
Weight: about 125 g.
Connection: by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm2.
Location: installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4 or Class I, Zone 2, Group IIC, T4.
Protection class: IP 20.
Dimensions: Width 12.5 mm, Depth 123 mm, Height 120 mm.
FSM
SIL 3
0.20.0
V (V)
I (A)
10
20
30
40
50
100
0.3 0.4 0.5 1 2 3
Resistive
Load
200
4
300
250
0.1 56
DC
resistive
AC
Resistive

3
D5091 - 5 A SIL 3 Relay Output Module for ND Load with ND or NE Relay conditionG.M. International ISM0110-12
Ordering Information
Front Panel and Features
SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 6 / 20 yrs (≤10% / >10 % of total SIF) for ND load with ND relay
(terminals 7-8).
SIL 3 according to IEC 61508:2010 Ed. 2 for Tproof = 14 / 20 yrs (≤10% / >10 % of total SIF) for ND load with NE relay
(terminals 9-10).
PFDavg (1 year) 1.59 E-05, SFF 96.35 % for ND load with ND relay.
PFDavg (1 year) 7.01 E-06, SFF 99.17 % for ND load with NE relay.
Systematic capability SIL 3.
Installation in Zone 2 / Division 2.
1 SPDT contact for 2 different Safety Functions:
1) SIL 3 for ND load (energized in fail safe state) with ND relay condition (energized in fail safe state)
2) SIL 3 for ND load (energized in fail safe state) with NE relay condition (de-energized in fail safe state)
6 A inrush current at 24 Vdc / 250 Vac.
Line input monitoring in-field DIP Switch selectable.
Driving input voltage monitoring.
Input/Output isolation.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, UKR TR n. 898, NEPSI, TÜV Certifications.
TÜV Functional Safety Certification.
Type Approval Certificate DNV and KR for maritime applications.
Simplified installation using standard DIN-Rail and plug-in terminal blocks or customized Termination Boards.
Model: D5091S DIN-Rail accessories: Cover and fix MCHP196
SPDT Output Common
Terminal block connections
SAFE AREA
SPDT Output Normally Open Contact
SPDT Output Common
SPDT Output Normally Close Contact
7
8
9
10
+ Input
1
- Input
2
7 8
9 10
12
D5091
7 8
1 2
SIL 3
9 10
STS

4 D5091 - 5 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition G.M. International ISM0110-12
Function Diagram
SAFE AREA, ZONE 2 GROUP IIC T4,
NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2,
GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4
MODEL D5091S
In
+
7
8
9
10
1
2
Termination
board
connector
(SIL3) SPDT Out ND Load
7-8 or 9-10
Relay contact shown
in de-energized position.
Terminals 7-8 open,
terminals 9-10 close.
SIL3 Safety Function for ND load (energized in fail safe state) is available at terminal blocks 9-10;
In this case, the Safety Function is met when the relay is de-energized (closed contact).
SIL3 Safety Function for ND load (energized in fail safe state) is available at terminal blocks 7-8;
In this case, the Safety Function is met when the relay is energized (closed contact).

5
D5091 - 5 A SIL 3 Relay Output Module for ND Load with ND or NE Relay conditionG.M. International ISM0110-12
Functional Safety Manual and Applications
Application for D5091S - SIL Load Normally De-Energized Condition (ND) and Normally De-Energized Relay
Normal state operation Energized to trip operation
8
Load
SIL3
7 - 9
- / AC
+ / AC
PLC
Output OFF
0 Vdc 10
Service Load
- / AC
+ / AC
Load
SIL3
PLC
Output ON
24 Vdc 8
7 - 9
10
Service Load
Description:
Input Signal from PLC/DCS is normally Low (0 Vdc) and is applied to pins 1-2 in order to Normally De-Energize (ND) the internal relays.
Input Signal from PLC/DCS is High (24 Vdc) during “energized to trip” operation, in order to energize the internal relays.
The Load is Normally De-Energized (ND), therefore its safe state is to be energized; the Service Load is normally energized, therefore it de-energizes during
“energized to trip” operation.
Disconnection of the ND Load is done on only one load supply line.
The following table describes the status (open or closed) of each output contact when the input signal is High or Low.
Safety Function and Failure behavior:
D5091S is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0.
In the 1st Functional Safety application, the normal state operation of relay module is de-energized, with ND (Normally De-Energized) loads.
In case of alarm or request from process, the relay module is energized (safe state), energizing loads.
The failure behaviour of the relay module is described by the following definitions:
□fail-Safe State: it is defined as the output load being energized;
□fail Safe: this failure causes the system to go to the defined fail-safe state without a process demand;
□fail Dangerous: failure mode that does not respond to a demand from the process (i.e. being unable to go to the defined fail-safe state)
so that the output load remains de-energized;
□fail “No effect”: failure mode of a component that plays a part in implementing the safety function but is neither a safe failure nor a dangerous failure.
When calculating the SFF this failure mode is not taken into account.
□fail “Not part”: failure mode of a component which is not part of the safety function but part of the circuit diagram and is listed for completeness.
When calculating the SFF this failure mode is not taken into account.
Failure rate date: taken from Siemens Standard SN29500.
Failure rate table:
Failure rates table according to IEC 61508:2010 Ed.2 :
PFDavg vs T[Proof] table (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes ≤10% of total SIF dangerous failures:
PFDavg vs T[Proof] table (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes >10% of total SIF dangerous failures:
Systematic capability SIL 3.
Operation Input Signal
Pins 1-2
Pins
7/9- 8
Pins
7/9 - 10
ND Load (SIL3)
Pins 8 — - / AC Supply
Service Load (Not SIL)
Pins 10 — - / AC Supply
Normal Low (0 Vdc) Open Closed De-Energized Energized
Trip High (24 Vdc) Closed Open Energized De-Energized
Failure category Failure rates (FIT)
λdd = Total Dangerous Detected failures 0.00
λdu = Total Dangerous Undetected failures 3.64
λsd = Total Safe Detected failures 0.00
λsu = Total Safe Undetected failures 96.00
λtot safe = Total Failure Rate (Safety Function) = λdd + λdu + λsd + λsu 99.64
MTBF (safety function, single channel) = (1 / λtot safe) + MTTR (8 hours) 1145 years
λno effect = “No effect” failures 302.96
λnot part = “Not Part” failures 0.00
λtot device = Total Failure Rate (Device) = λtot safe + λno effect + λnot part 402.60
MTBF (device, single channel) = (1 / λtot device) + MTTR (8 hours) 283 years
MTTFS(Total Safe) = 1 / (λsd + λsu) 1189 years
MTTFD(Dangerous) = 1 / λdu 31387 years
λsd λsu λdd λdu SFF
0.00 FIT 96.00 FIT 0.00 FIT 3.64 FIT 96.35%
T[Proof] = 1 year T[Proof] = 6 years
PFDavg = 1.59 E-05 - Valid for SIL 3 PFDavg = 9.57 E-05 - Valid for SIL 3
T[Proof] = 20 years
PFDavg = 3.19 E-04 - Valid for SIL 3
1)

6 D5091 - 5 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition G.M. International ISM0110-12
Functional Safety Manual and Applications
Application for D5091S - SIL Load Normally De-Energized Condition (ND) and Normally Energized Relay
Normal state operation De-energized to trip operation
8
Service
Load
7 - 9
- / AC
+ / AC
PLC
Output ON
24 Vdc 10
Load
SIL3
- / AC
+ / AC
Service
Load
PLC
Output OFF
0 Vdc 8
7 - 9
10
Load
SIL3
Description:
Input Signal from PLC/DCS is normally High (24 Vdc) and is applied to pins 1-2 in order to Normally Energize (NE) the internal relays.
Input Signal from PLC/DCS is Low (0 Vdc) during “de-energized to trip” operation, in order to de-energize the internal relays.
The Load is Normally De-Energized (ND), therefore its safe state is to be energized; the Service Load is normally energized, therefore it de-energizes during
“de-energized to trip” operation.
Disconnection of the ND Load is done on only one load line supply.
The following table describes the status (open or closed) of each output contact when the input signal is High or Low.
Safety Function and Failure behavior:
D5091S is considered to be operating in Low Demand mode, as a Type A module, having Hardware Fault Tolerance (HFT) = 0.
In the 2nd Functional Safety application, the normal state operation of relay module is energized, with ND (Normally De-Energized) load.
In case of alarm or request from process, the relay module is de-energized (safe state), energizing the load.
The failure behaviour of the relay module is described by the following definitions:
□fail-Safe State: it is defined as the output load being energized;
□fail Safe: this failure causes the system to go to the defined fail-safe state without a process demand;
□fail Dangerous: failure mode that does not respond to a demand from the process (i.e. being unable to go to the defined fail-safe state),
so that the output load remains de-energized.
□fail “No effect”: failure mode of a component that plays a part in implementing the safety function but is neither a safe failure nor a dangerous failure;
When calculating the SFF this failure mode is not taken into account.
□fail “Not part”: failure mode of a component which is not part of the safety function but part of the circuit diagram and is listed for completeness.
When calculating the SFF this failure mode is not taken into account.
Failure rate date: taken from Siemens Standard SN29500.
Failure rate table:
Failure rates table according to IEC 61508:2010 Ed.2 :
PFDavg vs T[Proof] table (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes ≤10% of total SIF dangerous failures:
PFDavg vs T[Proof] table (assuming Proof Test coverage of 99%), with determination of SIL supposing module contributes >10% of total SIF dangerous failures:
Systematic capability SIL 3.
Operation Input Signal
Pins 1-2
Pins
7/9- 8
Pins
7/9 - 10
ND Load (SIL3)
Pins 10 — - / ACSupply
Service Load (Not SIL)
Pins 8 — - / ACSupply
Normal High (24 Vdc) Closed Open De-Energized Energized
Trip Low (0 Vdc) Open Closed Energized De-Energized
Failure category Failure rates (FIT)
λdd = Total Dangerous Detected failures 0.00
λdu = Total Dangerous Undetected failures 1.60
λsd = Total Safe Detected failures 0.00
λsu = Total Safe Undetected failures 191.40
λtot safe = Total Failure Rate (Safety Function) = λdd + λdu + λsd + λsu 193.00
MTBF (safety function, single channel) = (1 / λtot safe) + MTTR (8 hours) 591 years
λno effect = “No effect” failures 209.60
λnot part = “Not Part” failures 0.00
λtot device = Total Failure Rate (Device) = λtot safe + λno effect + λnot part 402.60
MTBF (device, single channel) = (1 / λtot device) + MTTR (8 hours) 283 years
MTTFS(Total Safe) = 1 / (λsd + λsu) 596 years
MTTFD(Dangerous) = 1 / λdu 71347 years
λsd λsu λdd λdu SFF
0.00 FIT 191.40 FIT 0.00 FIT 1.60 FIT 99.17%
T[Proof] = 1 year T[Proof] = 14 years
PFDavg = 7.01 E-06 - Valid for SIL 3 PFDavg = 9.81 E-05 - Valid for SIL 3
2)
T[Proof] = 20 years
PFDavg = 1.40 E-04 - Valid for SIL 3

7
D5091 - 5 A SIL 3 Relay Output Module for ND Load with ND or NE Relay conditionG.M. International ISM0110-12
The proof test shall be performed to reveal dangerous faults which are undetected by diagnostic. This means that it is necessary to specify how dangerous undetected faults, which
have been noted during the FMEDA, can be revealed during proof test. The Proof test consists of the following steps:
Testing procedure at T-proof
Steps Action
1Bypass the safety-related PLC or take other appropriate action to avoid a false trip when removing the unit for test.
2For the single channel, verify the input-to-output functionality:
1. For De-energized relays and open contacts, terminals “7”-“8”, the output load is normally de-energized when the input channel is off, while the activation of the input
channel energizes the load (safe state).
2. For Energized relays and open contacts, terminals “9”-“10”, the output load is normally de-energized when the input is supplied, while the shutdown of the input
channel energizes the load (safe state).
The channel functionality must be verified for a min to max input voltage change (21.6 to 27.6 Vdc).
In addition, the use of three relays for the single output channel, where the contacts are connected in parallel, requires to control the single coils by means of DIP-switch
(n°1, 3, 5) and to check the ohmic continuity of the contacts, as described in the following procedures.
1. Do not supply the input channel (terminals “1”-“2”) of the unit under test and verify that the ohmic continuity at the output contact terminals “7”-“8” is absent (i.e. the
parallel connection of the 3 NO contacts is open: 1st requisite is verified). But this condition could also be true if all contacts are normally open except one, which is
blocked (for welding) into open position: this will be verified testing the channel when input is supplied (see 3rd requisite). Instead, the presence of ohmic continuity
implies that at least one relay contact is blocked (for welding) into closed position: this could only be verified disassembling and individually testing each relay.
2. Do not supply the input channel (terminals “1”-“2”) of the unit under test and verify that the ohmic continuity at the output contact terminals “9”-“10” is present (i.e. the
parallel connection of the 3 NC contacts is closed: 2nd requisite is verified). But this condition could also be true if only one contact is closed and others are blocked
(for welding) into closed or open position: this will be verified testing the channel when input is supplied (see 4th requisite). Instead, the absence of ohmic continuity
implies that all relay contacts are blocked (for welding) into open position.
3. Supply the input channel (terminals “1”-“2”) of the unit under test and verify that the ohmic continuity at the output contacts (terminals “7”-“8”) is present (i.e. the
parallel connection of the 3 NO contacts is closed: 3rd requisite is verified). The absence of ohmic continuity implies that all relay contacts are blocked (for welding)
into
open position. Instead, to verify if a single contact is blocked (for welding) into open position, use the DIP-switches (n°1, 3, 5) to short circuit each possible couple
among the 3 relay coils (starting with 1st & 2nd coils by DIP-switches n°1 & 3, then going with 1st & 3rd ones by DIP-switches n°1 & 5, and finally proceeding with 2nd &
3rd ones by DIP-switches n°3 & 5), verifying that ohmic continuity is always present between terminals “7”-“8”. In this situation, the absence of ohmic continuity implies
that a relay contact (the only one with energized coil because the others are de-energized) is blocked (for welding) into open position.
4. Supply the input channel (terminals “1”-“2”) of the unit under test and verify that the ohmic continuity at the output contacts (terminals “9”-“10”) is absent (i.e. the
parallel connection of the 3 NC contacts is closed: 4th requisite is verified). The presence of ohmic continuity implies that at least one relay contact is blocked (for
welding) into closed position: this could only be verified after disassembling and individually testing each relay. Instead, to verify if a contact is blocked (for welding)
into open position, use internal DIP-switches (n°1, 3, 5) to put in short circuit one relay coil at a time (starting with the 1st coil by DIP-switch n°1, then going on with the
2nd one by DIP-switch n°3, and finally proceeding with the 3rd one by DIP-switch n°5), verifying that the ohmic continuity is always present between terminals “9” &
“10”. In this situation, the absence of ohmic continuity implies that a relay contact (the only one with de-energized coil) is blocked (for welding) into open position.
3Remove the bypass from the safety-related PLC or restore normal operation inserting the unit.
This test reveals almost 99 % of all possible Dangerous Undetected failures in the relay module.
Warning
Operation
D5091S relay module is suitable for the switching of safety related circuits, providing isolation between the input and output contacts.
D5091S provides 1 SPDT contact for two different safety functions:
1) SIL 3 Safety Function for Normally De-Energized load (energized in fail safe state) is available at Terminal Blocks 7-8. The driving signal is normally low (0 Vdc),
the relay is normally de-energized, contact is open and load is de-energized. The safety function is met when the driving signal is high (24 Vdc), the relay is energized,
contact is closed and load is energized. At Terminal Blocks 9-10 is also available a service contact (for service load) with opposite (not SIL) function.
2) SIL 3 Safety Function for Normally De-Energized load (energized in fail safe state) is available at Terminal Blocks 9-10. The driving signal is normally high (24 Vdc),
the relay is normally energized, contact is open and load is de-energized. The safety function is met when the driving signal is low (0 Vdc), the relay is de-energized,
contact is closed and load is energized. At Terminal Blocks 7-8 is also available a service contact (for service load) with opposite (not SIL) function.
A “RELAY STATUS” yellow led lights when input is powered, showing that relay is energized.
Installation
D5091 series are relay output module housed in a plastic enclosure suitable for installation on EN/IEC60715 TH 35 DIN-Rail or on customized Termination Board.
D5091 series can be mounted with any orientation over the entire ambient temperature range.
Electrical connections are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without suffering or causing any damage
(for Zone 2 installations check the area to be nonhazardous before servicing). Connect only one individual conductor per each clamping point, use conductors up to 2.5 mm²
(13 AWG) and a torque value of 0.5-0.6 Nm. Use only cables that are suitable for a temperature of at least 85°C.The wiring cables have to be proportionate in base to the current and the
length of the cable.
On the section “Function Diagram” and enclosure side a block diagram identifies all connections.
Identify the function and location of each connection terminal using the wiring diagram on the corresponding section, as an example:
Connect positive input at terminal “1” and negative input at “2”.
Connect positive or AC load supply line to SPDT Output Common pole (terminal “7” or “9”).
Connect SIL 3 Normally De-Energized load between negative or AC load supply line and the terminal “8” (when relays are normally de-energized) or the terminal “10” (when relays are
normally energized), as previously shown in the Functional Safety applications.
Installation and wiring must be in accordance to the relevant national/international installation standards (e.g. EN/IEC60079-14 Electrical apparatus for explosive gas atmospheres -Part
14: Electrical installations in hazardous areas (other than mines)), make sure that conductors are well isolated from each other and do not produce any unintentional connection.
Connect load relay contacts checking the load rating to be within the contact maximum rating (5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W resistive load).
D5091 series are electrical apparatus installed on EN/IEC60715 TH 35 standard DIN-Rail located in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2,
Group A, B, C, D, T4 Hazardous Area within the specified operating temperature limits Tamb - 40 to +70 °C.
D5091 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards (e.g. IEC/EN60079-14
Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines)), following the established installation rules. De-energize
power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area or unless area is known to be nonhazardous.
Warning: substitution of components may impair suitability for Zone 2/Division 2. Avertissement: la substitution des composants peut nuire à l’aptitude à la Zone 2/Div. 2.
Explosion Hazard: to prevent ignition of flammable atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. Danger d'Explosion: pour
éviter l’inflammation d’atmosphères inflammables, débrancher l’alimentation avant l’entretien ou à moins que région est connue pour être non dangereuse.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock
when connected to live hazardous potential. Avertissement: débrancher l’alimentation (couper la tension d'alimentation) et les blocs de jonction enfichables avant d’ouvrir
le boîtier pour éviter les chocs électriques lorsqu’ils sont connectés à un potentiel dangereux.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury.
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.

8 D5091 - 5 A SIL 3 Relay Output Module for ND Load with ND or NE Relay condition G.M. International ISM0110-12
Start-up
Before powering the inputs of unit check that all wires are properly connected, also verifying their polarity. Check conductors for exposed wires that could touch each other causing
dangerous unwanted shorts. Enabling input, the corresponding “RELAY STATUS” yellow led must be lit and load circuit must be according to the connection required.
Indeed, disabling each input, the corresponding “RELAY STATUS” yellow led must be turned off and load circuit must change the status.
Configuration
An eight position DIP Switch is located on component side of pcb in order to set four mutually exclusive configurations:
1) line input monitoring, to allow DCS/PLC line input monitoring function (driving line pulse testing);
2) low voltage input monitoring (UVLO—under voltage lock out): module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold;
3) T-proof relay testing.
WARNING: dip-switch 2-4-6
must be set to “OFF” position
for any configuration.
ON
1) line input monitoring:
2) low voltage input monitoring:
3) T-proof relay testing:
DIP switch configurations:
12345678
ON
OFF OFF OFF OFF OFF OFF ON ON
12345678
ON
OFF OFF OFF OFF OFF OFF ON OFF
T-proof relays enable
135
135
Normal Operation
ON ON
OFF
ON
OFFOFF
T-proof relays (dip1 = relay1;
dip3 = relay2; dip5 = relay3)
12345678
ON
ON OFF ON OFF ON OFF ON ON
Please, see next page for testing procedure at T-proof.
WARNING: after T-proof test, dip-switch 1-3-5 must be set to “OFF” position for normal operation.
To prevent relay contacts from damaging, connect an external protection (fuse or similar), chosen according to the relay breaking capacity diagram from installation
instructions.
The enclosure provides, according to EN60529, an IP20 minimum degree of protection (or similar to NEMA Standard 250 type 1). The unit shall be installed in an area of no more than
pollution degree 2 according to EN/IEC60664-1. When installed in EU Zone 2, the unit shall be mounted in a certified Ex enclosure that provides a degree of protection not less than IP54
in accordance with EN/IEC60079-15. When installed in a Class I, Division 2 Hazardous Location, the unit shall be mounted in a supplemental enclosure that provides a degree of
protection not less than IP54. The enclosure must have a door or cover accessible only by the use of a tool. The end user is responsible to ensure that the operating temperature of the
module is not exceeded in the end use application.
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts. If enclosure needs to be cleaned use only a
cloth lightly moistened by a mixture of detergent in water.
Electrostatic Hazard: to avoid electrostatic hazard, the enclosure of D5091 series must be cleaned only with a damp or antistatic cloth.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit.
Any unauthorized card modification must be avoided.
All circuits connected to D5091 series must comply with the overvoltage category II (or better) according to EN/IEC60664-1.
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosure to avoid electrical shock
when connected to live hazardous potential.
This is factory settings
Table of contents
Other GMI Relay manuals