GMI D6037S User manual

D6037 - SIL 2 Switch/Proximity Detector Repeater Transistor Out G.M. International ISM0409-0
SIL 2 Switch/Proximity Detector Repeater
Transistor Out, DIN-Rail and
Termination Board, Models D6037S, D6037D
D6037S - D6037D
INSTRUCTION MANUAL

2 D6037 - SIL 2 Switch/Proximity Detector Repeater Transistor Out G.M. International ISM0409-0
General Description: The single and dual channel Switch/Proximity Detector Repeater, D6037S and D6037D module is a unit suitable for applications requiring SIL 2 level (according to
IEC 61508:2010 Ed. 2) in safety related systems for high risk industries.
The unit can be configured for switch or proximity detector (EN60947-5-6, NAMUR), NO or NC and for NO or NC optocoupled open collector transistor output.
Each channel enables a load to be controlled by a switch, or a proximity detector.
A fault detection circuit (DIP switch enabled) is available for both proximity sensor and switch equipped with end of line resistors. In case of fault, when enabled, it de-energizes the
corresponding output transistor and turns the fault LED on; when disabled the corresponding output transistor repeats the input line open or closed status as configured.
Mounting on standard DIN-Rail, with or without Power Bus, or on customized Termination Boards.
Functional Safety Management Certification:
G.M. International is certified by TÜV to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3.
Technical Data
Characteristics
Supply: 24 Vdc nom (18 to 30 Vdc) reverse polarity protected, ripple within voltage limits 5 Vpp, 2 A time lag fuse internally protected.
Current consumption @ 24 V: 22 mA for 2 channels D6037D, 12 mA for 1 channel D6037S with short circuit input and transistor closed, typical.
Power dissipation: 0.53 W for 2 channels D6037D, 0.30 W for 1 channel D6037S with 24 V supply voltage, short circuit input and transistor closed, typical.
Isolation (Test Voltage): In/Out 1.5 kV; In/Supply 1.5 kV; In/In 500 V; Out/Supply 500 V; Out/Out 500 V.
Input switching current levels: ON 2.1 mA (1.9 to 6.2 mA range), OFF 1.2 mA (0.4 to 1.3 mA range), switch current 1.65 mA ± 0.2 mA hysteresis.
Fault current levels: open fault 0.2 mA, short fault 6.8 mA.
Input equivalent source: 8 V 1 ktypical (8 V no load, 8 mA short circuit).
Output: voltage free SPST optocoupled open-collector transistor.
Open-collector rating: 100 mA at 35 Vdc (1.5 V voltage drop).
Leakage current: 50 µA at 35 Vdc.
Response time: 100 µs.
Frequency response: 5 kHz maximum.
Compatibility:
CE mark compliant, conforms to Directive: 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS.
Environmental conditions:
Operating: temperature limits – 40 to + 70 °C, relative humidity 95 %, up to 55 °C.
Storage: temperature limits – 45 to + 80 °C.
Approvals:
TÜV Certificate No. C-IS-722134640-01, SIL 2 conforms to IEC61508:2010 Ed.2.
TÜV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety.
Mounting:
T35 DIN-Rail according to EN50022, with or without Power Bus or on customized Termination Board.
Weight: about 125 g D6037D, 110 g D6037S.
Connection: by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm2.
Protection class: IP 20.
Dimensions: Width 12.5 mm, Depth 123 mm, Height 120 mm.
FSM
SIL 3

3
D6037 - SIL 2 Switch/Proximity Detector Repeater Transistor OutG.M. International ISM0409-0
Ordering Information
Front Panel and Features
SIL 2 according to IEC 61508:2010 Ed. 2
for Tproof = 8 / 20 years (10% / >10 % of total SIF) for D6037S and D6037D.
PFDavg (1 year) 1.21 E-04, SFF 77.15 % for D6037S.
PFDavg (1 year) 1.21 E-04, SFF 78.15 % for D6037D.
Systematic capability SIL 3
NO/NC switch/proximity Detector Input, NO/NC transistor driving mode.
Field open and short circuit detection.
Three port isolation, Input/Output/Supply.
EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
In-field programmability by DIP Switch.
TÜV Certification.
TÜV Functional Safety Certification.
High Density, two channels per unit.
Simplified installation using standard DIN-Rail and plug-in terminal blocks, with or without
Power Bus, or customized Termination Boards.
+ Input Ch 1 for Proximity or Voltage free Contact
Terminal block connections
- Input Ch 1 for Proximity or Voltage free Contact
+ Input Ch 2 for Proximity or Voltage free Contact
- Input Ch 2 for Proximity or Voltage free Contact
7
8
9
10
+ Output Ch 1
1
- Output Ch 1
2
+ Output Ch 2
3
- Output Ch 2
4
+ Power Supply 24 Vdc
5
- Power Supply 24 Vdc
6
Model: D6037
1 channel S
2 channels D
Power Bus and DIN-Rail accessories:
Connector JDFT049 Cover and fix MCHP196
Terminal block male MOR017 Terminal block female MOR022
2 1
4 3
6 5
7 8
9 10

4 D6037 - SIL 2 Switch/Proximity Detector Repeater Transistor Out G.M. International ISM0409-0
Function Diagram
MODEL D5037D
5 +
6 -
1 +
2 - Out 1 (SIL 2)
10
7
8
Termination
board
connector
Power and
Fault Bus
Supply 24 Vdc
+
-
F
3 +
4 - Out 2 (SIL 2)
9
+
-
In 1
Proximity
voltage free
Contact
+
-
In 2
Proximity
voltage free
Contact
voltage free
Contact
voltage free
Contact
R1
R2
R1
R2
Resistors R1 - R2 used with
voltage free contact required
for line fault detection.
Resistors R1 - R2 used with
voltage free contact required
for line fault detection.
MODEL D5037S
6 -
1 +
2 - Out (SIL 2)
7
8
Termination
board
connector
Power and
Fault Bus
Supply 24 Vdc
+
-
F
5 +
+
-
In
Proximity
voltage free
Contact
voltage free
Contact
R1
R2
MODEL D6037D
MODEL D6037S

5
D6037 - SIL 2 Switch/Proximity Detector Repeater Transistor OutG.M. International ISM0409-0
D6037 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards.
Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury.
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided.
Warning
Operation
D6037 module is a unit suitable for applications requiring SIL 2 level (according to IEC 61508) in safety related systems for high risk industries.
The unit can be configured for switch or proximity detector (EN60947-5-6, NAMUR), NO or NC and for NO or NC optocoupled open collector transistor output.
Each channel enables a load to be controlled by a switch, or a proximity detector.
Fault detection circuit (DIP switch configurable) is available for both proximity sensor and switch equipped with end of line resistors. In case of fault, when enabled it de-energizes
the corresponding output transistor and turns the fault LED on; when disabled the corresponding output transistor repeats the input line open or closed status as configured.
In case of fault output, transistor driving can be programmed as normally close or normally open.
Presence of supply power and status of output (energized or de-energized), as well as integrity or fault condition of sensor and connecting line are displayed by signaling LEDs
(green for power, yellow for status and red for fault condition).
Note: use of voltage free electrical contacts with fault detection enabled (control equipment) requires, near the switch at the end of the line a R1=1 ktypical (470 to 2 krange)
resistor in series and a R2=10 ktypical (5 kto 15 krange) resistor in parallel to the contacts in order to allow the fault detection circuit to distinguish between a condition of
contact close/open and a line open/short circuit fault.
Installation
D6037 series are Switch/Proximity Detector Interface housed in a plastic enclosure suitable for installation on T35 DIN-Rail according to EN50022, with or without Power Bus or
on customized Termination Board.
D6037 unit can be mounted with any orientation over the entire ambient temperature range.
Electrical connection of conductors up to 2.5 mm² are accommodated by polarized plug-in removable screw terminal blocks which can be plugged in/out into a powered unit without
suffering or causing any damage.
The wiring cables have to be proportionate in base to the current and the length of the cable.
On the section “Function Diagram” and enclosure side a block diagram identifies all connections.
Identify the number of channels of the specific card (e.g. D6037S is a single channel model and D6037D is a dual channel model), the function and location of each connection terminal
using the wiring diagram on the corresponding section, as an example:
Connect 24 Vdc power supply positive at terminal “5” and negative at terminal “6”.
For Model D6037S connect positive output of channel 1 at terminal “1” and negative output at “2”.
For Model D6037D in addition to channel 1 connections above, connect positive output of channel 2 at terminal “3” and negative output at “4”.
For Model D6037S, in case of Proximity or Voltage free Contact, connect the wires at terminal “7” for positive and “8” for negative.
For Model D6037D in addition to channel 1 connections above, connect terminal “9” for positive and “10” for negative on channel 2.
Connect SPST output transistors checking the load rating to be within the maximum rating (100 mA at 35 Vdc (1.5 V voltage drop)).
Units must be protected against dirt, dust, extreme mechanical (e.g. vibration, impact and shock) and thermal stress, and casual contacts.
If enclosure needs to be cleaned use only a cloth lightly moistened by a mixture of detergent in water.
Any penetration of cleaning liquid must be avoided to prevent damage to the unit. Any unauthorized card modification must be avoided.
According to EN61010, D6037 series must be connected to SELV or SELV-E supplies.
Start-up
Before powering the unit check that all wires are properly connected, particularly supply conductors and their polarity, input and output wires. Check conductors for exposed wires that
could touch each other causing dangerous unwanted shorts. Turn on power, the “power on” green led must be lit, status and fault led on each channel must be in accordance with
condition of the corresponding input line. If possible close and open input lines one at time checking the corresponding status and fault leds condition as well as output to be correct.

6 D6037 - SIL 2 Switch/Proximity Detector Repeater Transistor Out G.M. International ISM0409-0
Configuration
D6037D
A configuration DIP switch is located on component side of pcb. This switch allows the configuration of input/output relationship, fault detection functions and operating mode.
Input Input
OutputInputOutputInput
CH1
Setting
Line fault
detection
IN / OUT
Operation
NO-NC or
NC-NO
NO-NO or
NC-NC
Disabled
(switch / proximity sensor)
Enabled
(proximity sensor or switch
with end of line resistors, de-energizes
transistor in fault condition)
7
NO
8
OR NC 7
8
7
NO
8
OR NC 7
8
1
OFF
1
ON
NC 1
2
1
NO
2
Output
1
NO
2
Output
NC 1
2
Position in fault condition
1
2
2
ON
2
OFF
Input Input
OutputInputOutputInput
CH2
Setting
Line fault
detection
IN / OUT
Operation
NO-NC or
NC-NO
NO-NO or
NC-NC
Disabled
(switch / proximity sensor)
Enabled
(proximity sensor or switch
with end of line resistors, de-energizes
transistor in fault condition)
9
NO
10
OR NC 9
10
9
NO
10
OR NC 9
10
NC 3
4
3
NO
4
Output
3
NO
4
Output
NC 3
4
3
3
ON
OFF Position in fault condition
3
4
4
4
ON
OFF
ON
Dip switch configuration
1234
ON
Dip switch factory settings. All Switches are OFF
1234
ON
CH1 CH2
For SIL Application
For SIL Application
For SIL Application
For SIL Application

7
D6037 - SIL 2 Switch/Proximity Detector Repeater Transistor OutG.M. International ISM0409-0
D6037S
A configuration DIP switch is located on component side of pcb. This switch allows the configuration of input/output relationship, fault detection functions and operating mode.
Configuration
CH1
Setting
Line fault
detection
IN / OUT
Operation
NO-NC or
NC-NO
NO-NO or
NC-NC
Disabled
(switch / proximity sensor)
Enabled
(proximity sensor or switch
with end of line resistors, de-energizes
transistor in fault condition)
1
OFF
1
ON
Input Input
OutputInputOutputInput
7
NO
8
OR NC 7
8
7
NO
8
OR NC 7
8
NC 1
2
1
NO
2
Output
1
NO
2
Output
NC 1
2
Position in fault condition
1
2
2
ON
2
OFF
ON
Dip switch configuration
1234
ON
Dip switch factory settings. All Switches are OFF
1234
ON
CH1 3-4 not used
For SIL Application
For SIL Application
Line fault detection SW1
Disabled
(switch/proximity sensor) OFF
Enabled, for SIL application
(proximity sensor or switch with end of line resistors,
detects field open circuit and short circuit,
de-energizes transistor in fault condition)
ON
IN/OUT Operation SW2
NO-NC or NC-NO ON
NO-NO or NC-NC
(for SIL application) OFF
D6037S Configuration Summary Table
Channel 1 2
Line fault detection SW1 SW3
Disabled
(switch/proximity sensor) OFF OFF
Enabled, for SIL application
(proximity sensor or switch with end of line resistors,
detects field open circuit and short circuit,
de-energizes transistor in fault condition)
ON ON
IN/OUT Operation SW2
NO-NC or NC-NO ON
NO-NO or NC-NC
(for SIL application) OFF
Channel 1 2
SW4
ON
OFF
D6037D Configuration Summary Table
SW1 SW2 SW3 SW4
OFF OFF OFF OFF
DIP Switch factory settings (valid for D6037S and D6037D)
Configuration
Note: SW3 and SW4 not used.
Note: SW3 and SW4 used only in D6037D.
This manual suits for next models
1
Table of contents
Other GMI Security Sensor manuals
Popular Security Sensor manuals by other brands

HIK VISION
HIK VISION DS-PDP15P-EG2-WE manual

HIK VISION
HIK VISION DS-PDMCK-EG2-WE user manual

Abus
Abus FAS 101 Installation and operation instructions

C.P. Electronics
C.P. Electronics SPIR-PRM Product guide

C.P. Electronics
C.P. Electronics Green-i GESM installation guide

Maxouttech
Maxouttech RF-SHK-319-NN quick start guide

HIK VISION
HIK VISION DS-PDTT15AM-LM-WB user manual

C.P. Electronics
C.P. Electronics EBDSPIR-DNET1 installation guide

C.P. Electronics
C.P. Electronics EBDRC-PRM installation guide

Maxouttech
Maxouttech RF-ROR-135S-319-NN manual

Tinker & Rasor
Tinker & Rasor PD Product instructions

Paradox
Paradox NV780MX installation manual