5
The boiler needs to be connected to a conventional flue
system. There is no provision for connection to a balanced
flue system as there is draft regulator fitted to the appliance.
The boiler is not designed specifically for operation on a
system with a buffer tank/ thermal store, however when used
on a system with a buffer tank/ thermal store there is no effect
on the boiler performance.
The only flue system suitable for the Grant SPIRA
condensing wood pellet boiler is the Grant „Black‟
insulated conventional flue system.
This 125mm (5”) „Black‟ flue system is suitable for both
models 6-26 & 9-36.
1.3 Boiler components
1.3.1 Burner. The burner is supplied separately and will need
to be mounted to the boiler on site. All burners are supplied at
a factory default setting. During commissioning each burner
parameter will need to be checked and adjusted if necessary
as pellet feed auger angle, pellet size and flue sizes/length
can have significant effect on the boiler performance. Refer to
commissioning in section 9. The Burner is equipped with a
self cleaning device to prevent a build up ash and clinker in
the burner brazier. The burner output is determined by the
feed / pause times of the pellet feed auger supplying the
burner. See section 8 for full burner operation.
1.3.2 Boiler. The SPIRA condensing boiler is supplied with a
combined primary and secondary heat-exchanger. The boiler
is also equipped with a self cleaning system, of which the
primary cleaning system comes fitted in the boiler and the
secondary cleaning system needs to be fitted. See section 4.
Boiler Installation.
1.3.3 Boiler controls. The temperature of the water leaving
the boiler to heat the radiators and hot water cylinder is user
adjustable by adjusting the set point on the burner menu see
section 8. The boiler is fitted with an overheat thermostat
(which allows it to be used on a sealed central heating
system) which will automatically switch off the boiler if the
temperature exceeds a pre-set temperature of 110°C. The
control panel is fitted with a Burner ON/STAND-BY switch.
This switch interrupts the switched live supply to the burner, it
does not isolate the electrical supply to the burner. The
control panel is also fitted with a cleaning switch, in the
default position it allows the boiler cleaning system to perform
automatically, when pressed it allows the cleaning system to
be manually tested. Only operate the cleaning switch when
the boiler is in „WAIT BOILER THERMOSTAT‟. See figure 1.1
Fig. 1.1
After the burner has been switched off (either manually
by the switch on the control panel, the boiler stat‟, or the
switched live input) the burner needs to burn-down the
remaining pellets in the brazier. Do not AT ANY TIME
open the front combustion chamber access door until
the burner display reads “WAIT BOILER THERMOSTAT”
1.3.4 Pellet Feed Auger. The pellet feed auger is a hollow
spiral type. Its function is to deliver the pellets from the
hopper to the burner. The output of the boiler is determined
by varying the on/off periods of the pellet feed auger motor.
All Grant hoppers are fitted with a fixed angle feed pellet feed
auger at 45° to maintain consistent feed. Once the pellet feed
auger angle is altered the input to the boiler is also altered.
1.3.5 Hopper. The system comes complete with an
intermediate hopper. This hopper stores 120 kg (169 lt) of
wood pellets with a refill capacity of 80 kg The hopper is for
indoor use only and should be positioned in a dry
environment. Position the hopper to the left side of the boiler
only and on the same floor level as the boiler. The hopper is
supplied with castors, allow sufficient area in front of the
hopper for removal during servicing. The hopper comes
with „knock-out‟ to allow entry of pellets from a bulk
hopper system, this knockout is positioned to ensure the
pellets drop into the hopper and will de-activate the low
level indicator. Making an alternate opening in the
intermediate hopper could effect the operation of the low level
indicator.
Always ensure that the door and top panel of the intermediate
hopper are fitted to ensure no foreign debris enters the
hopper. If a bulk system is fitted ensure the bulk auger does
not stop the opening of the intermediate hopper access door.