Growatt AXE 5.0L-C1 User manual

Shenzhen Growatt New Energy Co., Ltd
4-13/F,Building A,Sino-German(Europe) Industrial Park,Hangcheng Ave,
Guxing Community,Xixiang Subdistrict, Bao’an District, Shenzhen, China
+86 755 2747 1942
www.ginverter.com
T
E
W
service@ginverter.com
Download
Manual
Growatt New Energy Residential Energy Storage User Manual
AXE 5.0L Battery System
GR-UM-275-A-01

Contents
1 Product Overview
2 Safety
3 Storage and Transportation
2.1 Basic security
2.2 Safety Precautions
2.3 Warning Labels
2.4 Emergency Responses
4 Installation
5 Power on and off the Battery
5 1 Power On.
5.2 Power off
6.1 Preparation
6.2 PACK Replacement
6.3 System Failure Information List
and Troubleshooting Suggestions
1.1 Intended Use
1.2 Appearance
1.3 Working Principle and Function
3.1 Storage Requirements
3.2 Transportation Requirement
About this Document
This document describes the installation, electrical connection, operation, commission,
maintenance and troubleshooting of AXE 5.0L-C1and AXE 5.0L-X1 Battery System
(hereafter simply put AXE 5.0L). Before installing and operating AXE 5.0L, ensure that
you are familiar with product features, functions, and safety precautions provided in this
document.
Symbol
Description
Indicates a potentially hazardous situation, if not avoided, could result
in serious injury or death.
WARNING
4 1. Installation environment
4.2 Basic Installation Requirements
4.3 Installation Required Tools
4.4 Check
4.5 Installation
4.6 About mixing old and new
batteries in parallel
6 Maintenance Guide
7 Technical Specifications
Appendix I
Appendix I I

4
5
6
7
8
9
10
11
Each AXE 5.0L consists of 100Ah cells which form 51.2V voltage battery module and
sixteen serial connection (1P16S). A single cluster can connect up to 10 batteries in
parallel, and up to 8 clusters in parallel to expand the capacity and power of the energy
storage system. The same type of cell and the same software version of the PACK can be
used in parallel. Specifically, the AXE battery system powers the loads through PCS at
nighttime without solar; when solar becomes available during daytime, solar energy
powers the loads as a priority and store residual solar power into the AXE batter system.
1.2 Appearance
1 Product Overview
1.1 Intended Use
AXE 5.0L consists of battery module (including cell and mechanical parts), battery
management system (BMS) as well as power and communication terminals. Product
appearance is shown as below.
Fig 1.1: Battery size diagram
12
1.3 Working Principle and Function
AXE 5.0L is an energy storage unit composed of electrochemical cells, switch button,
battery management unit, power and signal terminals, and mechanical parts.
It features better charge and discharge performance, more precise status monitor, longer
cycle life, and less self-discharge loss than other batteries.
The scalability is very strong, a single cluster can connect up to 10 batteries in parallel,
and up to 8 clusters in parallel to expand the capacity and power of the energy storage
system.
The whole battery system communicates to Power Conversion System (PCS) via CAN.
ØMonitoring: voltage, current and temperature detection of both single cells and PACK.
ØProtection and Alarm: protection and alarm when overvoltage, under voltage, over
current, over-temperature or under temperature occurs. See Appendix I for details.
ØReport: report all alarm and status data to PCS.
ØPower off triggered by fault: PACK and PCS communication drop for 25 minutes or
under voltage protection for 2 minutes.
650mm
140mm
350mm
1.2.1 Dimension
1.2.2 Introduction to the battery operation panel
1
2
3
5
Communication interface
Communication between battery
packs of single cluster
6
USB interface
USB interface for system upgrade
7
Communication interface
Link-out for multi-cluster in parallel
communication
8
Link-in for multi-cluster in parallel
communication
9
PCS CAN communication
10
GND terminal
Terminal connect to ground
11
Negative terminal
Stands for PACK cathode output
b
3
3
3
c
3
d
3
e
3
3
f
a
Location
Port
Function
1
Fault light
Display battery alarm and fault status
2
SOC light
Display battery SOC status
3
Power button
Turn the battery on and off
4
Positive terminal
Stands for PACK anode output
No.
Name
Color
Description
A
RUN
Green
Normal operation
B
ALM
Red
Failure or protection status
C
LED 4
Blue
76%-100%
D
LED 3
Blue
51%-75%
E
LED 2
Blue
26%-50%
F
LED 1
Blue
0%-25%
Fig 1.2: Introduction to the battery operation panel
Fig 1.3: LED lights

34
Safety information contains in this section must be observed at all times when working
on or with batteries. For safety, installers are responsibility to familiarize themselves with
this manual and all warnings before installation.
2.1 Basic security
The PACK has been designed and tested in strict rules with international safety
certification requirements. Read all safety instructions carefully before any work and
obey the rules at all times when working on or with the PACK. Growatt shall not be liable
for any consequence caused by the violation of the following:
ŸDamage occurred during transportation .
ŸIncorrect transportation, storage, installation and use, or customer fails to convey the
Ÿcorrect information about transportation, storage, installation and use to terminal
Ÿcustomers.
ŸNon-professional installation.
ŸFailure to obey the rules of this operation instructions and safety precautions in this
document.
ŸUnauthorized modifications or removal of the software package.
ŸPACK tamper label is damaged or product with any part missing (except the authorized
dissemble parts).
ŸOperate and use in extreme environments not allowed in this document.
ŸRepair, disassemble, or change PACKs without authorization and cause failure.
ŸDamage to shell labels or modifies date of production.
ŸPACK fail to be charge for more than six months.
ŸDamages due to force majeure (such as lightning, earthquakes, fire, and storms).
ŸWarranty expiration.
2.2 Safety Precautions
2.2.1 Environment requirements
ŸDo not expose the battery to temperature above 50℃or heat sources.
ŸDo not install or use the battery in wet locations, moisture , corrosive gases or liquids,
such as bathroom.
ŸDo not expose the battery to direct sunlight for extended periods of time.
ŸPlace battery in safe place away from children and animals.
ŸBattery power terminals shall not touch conductive objects such as wires.
ŸDo not dispose the batteries in fire, which may cause an explosion.
ŸThe PACK shall not come in contact with liquids.
ŸThe PACK can only be installed indoors. Regarding indoor installation, please do not
install it in the bedroom, living room, kitchen, etc.
2 Safety 2.2.2 Operation Precautions
ŸDo not touch the PACK with wet hands.
ŸDo not disassemble the PACK without permission
ŸDo not crush, drop or puncture the PACK and battery
ŸDispose the batteries according to local safety regulations.
ŸStore and recharge battery in accordance with this manual.
ŸEnsure the connection of ground wire reliable.
ŸRemove all metal objects such as watches and rings that could cause a short-circuit
before installation, replacement and maintenance.
ŸThe Pack shall be repaired, replaced or maintained by skilled personal that has been
recognized.
ŸWhen storing or handling batteries ,do not stack batteries without package.
ŸDo not broke the battery, the released electrolyte may be toxic and is harmful to skin
and eyes.
ŸPackaged batteries should not be stacked more than specified number stipulated on
the packing case.
ŸDo not use damaged, failed or deformed batteries, which may lead to high
temperature or even dangerous accidents. Continued operation of damaged battery may
result in electrical shock, fire or even worse.
2.3 Warning Labels/Étiquettes d'avertissement
Symbols/ Symboles
Description
Do not dispose in trash/Ne pas jeter à la poubelle
Lithium ion battery can be recycled/La batterie lithium-ion
peut être recyclée
Certification in European union area/Certification dans la zone
de l'Union européenne
UK certification/Certification britannique
Electric shock hazard/Risque de choc électrique
Explosive gas/Gaz explosif
May leak corrosive electrolyte/Peut fuir un électrolyte corrosif
Heavy enough to cause severe injury/Assez lourd pour causer
des blessures graves
Keep the Pack away from children/Gardez le pack hors de
portée des enfants
Make sure the battery polarity well connected/Assurez-vous
que la polarité de la batterie est bien connectée

Do not expose to fire/Ne pas exposer au feu
Operate as the Manual/Fonctionne comme le manuel
2.4 Emergency Responses
Manufacturer takes foreseeable risk scenarios into consideration and is designed to
reduce hazards and dangers. However, if the following situation occurs, do as below:
Situation Occurs
Description and action need
Leakage
Avoid touch of leaking liquid or gas. If you touch the leaking
electrolyte, do as below immediately.
Inhalation: Evacuate the contaminated area, and seek medical help.
Eye contact: Rinse eyes with flowing water for 15 minutes, and seek
medical help.
Skin contact: Rinse contacted area thoroughly with soap and water,
and seek medical help.
Ingestion: Vomiting, and seek medical help.
Fire
It's hard for PACK systems ignite spontaneously. If the PACK has
caught a fire, do not try to extinguish the fire but evacuate people
immediately.
Wet Packs
If PACK is flooded or submerged, do not access it. Contact Growatt
or distributor for technical assistance immediately.
Damaged PACKS
Damaged PACKS are dangerous and must be handled with special
attention. They are no longer suitable for use and may cause danger
to people. If the PACK damaged, stop use it and contact the Growatt
or distributor.
56
Do not disassemble or a lter th e PACK to a void heat ,explosion or f ire.
Do not use the PACK be yond sp ecifide conditions. It migh t cause h eat
generation,d amage ,or deterioration of it s perfo rmanc e.
Do not throw,dro p,hit ,driv e a nail in,stamp on t he PACK .It may c ause
heat generatio n,exp losion,or fire.
In case of electro lyte le akage,keep leaked ele ctrol yte awa y from
contact with eye s or skin .imme diately clean wi th wate r and see k help
from a doctor.
Do not put the PACK in to a fire .Do not u se it or leave it on a pla ce
near fire,heat ers,o r high temperature sour ces.I t may cau se over
temperature, explo sion or fire.
Do not submerge th e PACK in w ater,or wet the product .It may c ause
heat generatio n,exp losion ,or fire.
Do not reversely c onnec t the PACK positi ve(+) and neg ative(-)terminal.
Do not short circu it by let ting th e PACK ter minal s(+an d -)contact a wire
or any metal.
The unit is heavy en ough to c ause severe injury.
Keep out of reach of c hildr en or animals.
WARNING
X
Ne pas démonte r ou modi fier le PACK po ur évit er tout e chaleur, explosion
ou incendie.
Ne pas utilise r le PACK en dehors des co nditi ons spé cifiées. Cela pourrait
provoquer un c haleu r impor tante , des dommages ou une détéri orati on des
performanc es de l’a ppare il.
Ne pas jeter, lai sser to mber, fr apper, p lanter un clou ou piétiner l e PACK.
Cela peut prov oquer u n dégag ement d e chaleur, une explosion ou u n incen die.
En cas de fuite d' élect rolyt e, ne pas m ettre l'électro lyte en c ontac t avec le s
yeux ou la peau. N ettoy er immé diate ment à l'eau et demander l'a ide d'u n
médecin.
Ne pas mettre le PACK dans un feu . Ne pas l' utili ser prè s d'une source de
chaleur impo rtant e. Cela p eut pro voquer une surchauffe, une explosi on ou
un incendie.
Ne pas immerge r le PACK dans l' eau, ou m ouill er le pro duit.Cela pourrait
provoquer un d égage ment de c haleu r, une explosion ou un incend ie.
Ne pas inverse r la pola rité de s câble s du pack.
Ne pas court-c ircui ter en la issan t les bornes du PACK (+ et -) en contact avec
un fil ou un métal .
L'appareil e st suffisa mment l ourd po ur prov oquer d es blessures grav es.
Gardez votre a ppare il hors d e porté e des enfants ou des animaux .
X
Avertissement
English French
Battery Module
AXE 5.0L-C1
51.2V
500A,50us
I
Maximum Short Current
and Duration
Protective Class
Nominal/Rated Capacity
Nominal/Rated Energy
Rated Current
Operating Ambient
Temperature 0°C ~ +50°C
IP20
60A
100Ah 90Ah
/
5000Wh 4600Wh
/
C US
51.2V
Operating Ambient
Temperature 0°C ~ +50°C
Protective Class
I
AXE 10.0L-C1/120A/200Ah/
180Ah/10.0kWh/9.2kWh
AXE 15.0L-C1/150A/300Ah/
270Ah/15.0kWh/13.8kWh
AXE 20.0L-C1/150A/400Ah/
360Ah/20.0kWh/18.4kWh
AXE 25.0L-C1/150A/500Ah/
450Ah/25.0kWh/23.0kWh
AXE 30.0L-C1/150A/600Ah/
540Ah/30.0kWh/27.6kWh
AXE 35.0L-C1/150A/700Ah/
630Ah/35.0kWh/32.2kWh
AXE 40.0L-C1/150A/800Ah/
720Ah/40.0kWh/36.8kWh
AXE 45.0L-C1/150A/900Ah/
810Ah/45.0kWh/41.4kWh
AXE 50.0L-C1/150A/1000Ah/
900Ah/50.0kWh/45.0kWh
AXE 5.0L-C1/60A/100Ah/
90Ah/5.0kWh/4.6kWh
Nominal Capacity/
Rated Current/
System Model/
Rated Energy
Nominal Energy/
Rated Capacity/
Ingress
Protection
Nominal Voltage
IP 20
C US
AXE 5.0L-X1
51.2V
500A,50us
I
Maximum Short Current
and Duration
Protective Class
Nominal/Rated Capacity
Nominal/Rated Energy
Rated Current
Operating Ambient
Temperature 0°C ~ +50°C
IP20
60A
100Ah 90Ah
/
5000Wh 4600Wh
/
C US
51.2V
Operating Ambient
Temperature 0°C ~ +50°C
Protective Class
I
AXE 10.0L-X1/120A/200Ah/
180Ah/10.0kWh/9.2kWh
AXE 15.0L-X1/150A/300Ah/
270Ah/15.0kWh/13.8kWh
AXE 20.0L-X1/150A/400Ah/
360Ah/20.0kWh/18.4kWh
AXE 25.0L-X1/150A/500Ah/
450Ah/25.0kWh/23.0kWh
AXE 30.0L-X1/150A/600Ah/
540Ah/30.0kWh/27.6kWh
AXE 35.0L-X1/150A/700Ah/
630Ah/35.0kWh/32.2kWh
AXE 40.0L-X1/150A/800Ah/
720Ah/40.0kWh/36.8kWh
AXE 45.0L-X1/150A/900Ah/
810Ah/45.0kWh/41.4kWh
AXE 50.0L-X1/150A/1000Ah/
900Ah/50.0kWh/45.0kWh
AXE 5.0L-X1/60A/100Ah/
90Ah/5.0kWh/4.6kWh
Nominal Capacity/
Rated Current/
System Model/
Rated Energy
Nominal Energy/
Rated Capacity/
Ingress
Protection
Nominal Voltage
IP 20
C US
Fig 2.2: Label

3 Storage and Transportation Installation 4
WARNING
ØEnsure to read the Guidance before installation in order to
understand product information and safety cautions/ Assurez-vous de
lire le guide avant l'installation afin de comprendre les informations
sur le produit et les précautions de sécurité;
ØOperators should be well trained technicians and fully understand
the whole photovoltaic system, grid network, working principle and
national regional standards/ Les opérateurs doivent être des
techniciens bien formés et bien comprendre l'ensemble du système
photovoltaïque, le réseau électrique, le principe de fonctionnement et
les normes régionales nationales;
ØInstallers must use insulating tools and wear safety equipment/ Les
installateurs doivent utiliser des outils isolants et porter des
équipements de sécurité;
ØDevice damages caused by failure to comply with storage,
transportation, installation and use requirements specified in
Guidance are not coved by Warranty/ Les dommages à l'appareil
causés par le non-respect des exigences de stockage, de transport,
d'installation et d'utilisation spécifiées dans le guide ne sont pas
couverts par la garantie.
ØThe PACK can only be installed indoors. Regarding indoor
installation, please do not install it in the bedroom, living room,
kitchen, etc/ Le PACK ne peut être installé qu'en intérieur. En ce qui
concerne l'installation à l'intérieur, veuillez ne pas l'installer dans la
chambre, le salon, la cuisine, etc.
ØDifferent types of batteries are not recommended to be mixed and
used in parallel/ Il est déconseillé de mélanger et d'utiliser différents
types de batteries en parallèle.
ØThe battery system cannot be installed, dismantled, and maintained
when it has been powered on/ Le système de batterie ne peut pas être
installé, démonté et entretenu lorsqu'il a été mis sous tension.
4.1 Installation environment
The ambient temperature for the installation of the battery system shall be above 0℃,
below 50℃, and the humidity shall between 5% and 85%.
Fig 4.1: Installation environment requirements
Max.+50℃Min.0℃ Indoor installation
78
Avertissement
3.1 Storage Requirements
ØPlace the PACK follow the identification on the packing case during storage.
ØDo not put the PACK upside down or sidelong.
ØThe defective PACK needs to be separated from other PACKs.
ØThe storage environment requirements are as follows:
1) Install the PACK in a dry and clean place with proper ventilation.
2) The storage temperature for a short week is between -20℃ to 50℃.
3) If you store the PACK over a long period of six months, the storage temperature is
between-20°C to 40°C, relative humidity: 5%~85%RH.
4) Place the PACK away from corrosive and organic substances (including gas exposure).
5) Free from direct exposure to sunlight and rain .
6) At least two meters away from heat sources (such as a radiator).
7) Free from exposure to intensive infrared radiation.
ØIf the PACK has not been used for more than six months, it needs to be charged, The
charging procedure is as follows:
1) Identify the PACK that needs charging;
2) Refer to quick installation guidance, complete the installation and wire connection.
Ensure PACK in off status during all the steps.
3) Set the power system as “CC≤25A, CV=55.8V” , activate the PACK and start
recharging.
4) Recharge until LED2 flicks.
5) Having completed recharge, leave circuit open for five minutes before check voltage. If
voltage is not less than 52V, the recharge succe.
3.2 Transportation Requirement
PACK has been certified in UN38.3 (Section 38.3 of the sixth Revised Edition of the
Recommendations on the Transport of Dangerous Goods: Manual of Tests and Criteria)
and SN/T 0370.2-2009 (Part 2: Performance Test of the Rules for the Inspection of
Packaging for Exporting Dangerous Goods). PACK is classified as category 9 dangerous
goods.
ØThe PACK shall not be transported with other inflammable, explosive or toxic
substances.
ØEnsure the original Package and label complete and recognizable.
ØProhibit direct exposure to sunlight, rain, condensing water caused by temperature
difference and mechanical damages.
ØThere will be a drop in capacity during transportation and storage.
ØTransportation temperature is between-20°C to 45°C, relative humidity: 5%~85%RH.
RH.+5%~+85%

ARK 5.0 L Cable
C
(2000±25)mm
RJ 45 dust cover
USB dust cover
910
Do not turn the PACK upside down, and keep the ground
level/ Ne retournez pas le PACK et maintenez le niveau du
sol.
WARNING/Avertissemen
4.3 Installation Required Tools
The following tools are required to install the PACK:
5mm Allen key Screw Driver Wrench
Tap Measure Multimeter
Ground(2~8 clusters installation)
150mm ≤d≤500mm
. . .
Cluster 1 Cluster 2
Cluster 8
150mm ≤d≤500mm
Cluster 3
Fig 4.2: Acceptable floor standing installation
It is recommended to wear the following safety gear when dealing with the PACK.
Insulated Glove Safety Goggle Safety Shoes
4.4 Check
Check the package
Check the PACK package before open it. If any abnormity is
detected, do not open the Package and contact your distributor.
Check the power
Check and confirm the PACK is powered off before installation.
Check deliverable
Check the quantity of all parts inside according to the package list.
If there is any part missing or damaged, please contact your
distributor.
Fig 4.3: AXE 5.0L packing list
4.4.1 Pre-installation Check
4.4.2 Check Packing List
4.4.3 Check accessories
A
ARK 5.0 L
Ground Ground
≥150mm ≥150mm
90°
Wall
90°
4.2 Basic installation requirements
Fig 4.4: Parts list
AXE 5.0L *1 Quick installation Manual *1
User Manual *1
Quick
installation
Manual
Warranty card *1
Certificate of conformity *1
Warranty
card
Certificate of
conformity
User Manual
ARK 5.0 L Base(Any of them)
B

12
11
Step 1: Check the ground, make sure that the ground is level, then place the base at the
position where it needs to be installed, and keep the base level.
Step 2: Place the first battery on the base.
Step 3: Stack the second battery on the first battery, stack the third battery on the second
battery, and so on, until all the batteries are installed.
Step 4: Make sure that all the batteries are aligned, then use a screwdriver to open the
connectors on the left end of the batteries, rotate the connector position, and connect
the upper and lower battery modules together.
4.5 Installation
4.5.1 Floor Standing Installation
1) The battery base is required while installing the battery system/ La
base de la batterie est requise lors de l'installation du système de
batterie.
2) The maximum quantity of stacking battery pack is 10, if it exceeds
10, please install them by.
3) the way of multiple clusters in parallel/ La quantité maximale de
batterie d'empilage est de 10, si elle dépasse 10, veuillez les installer
par le biais de plusieurs clusters en parallèle.
4) Please install indoors and ensure the level of the ground/ Veuillez
installer à l'intérieur et assurer le niveau du sol.
Fig 4.5: Multiple AXE 5.0L with base installation process
4.5.2 Electrical Connection
ØDo not forget wear ESD wrist strap and gloves, safety gloves and
goggles/ N'oubliez pas de porter un bracelet antistatique et des gants,
des gants de sécurité et des lunettes de protection.
ØIt is recommended that the power line and communication line
between the battery and the PCS should not exceed 2 meters/ Il est
recommandé que la ligne électrique et la ligne de communication entre
la batterie et le PCS ne dépassent pas 2 mètres.
WARNING
4.5.2.1 Communication interface definition:
Item
Crystal head picture
Serial no.
Definition
PCS
1
/
2
/
3
GND_COM
4
CAN_H
5
CAN_L
6
GND_COM
7
WAKE-
8
WAKE+
4.5.2.2 Single cluster wiring
PCS Link-in Link-out
To PCS CAN
Fig 4.6: Block diagram of a single
cluster system
Fig 4.7: Single cluster communication wiring
Installation Method
Compound Mode
Single cluster installation
A*M+B+C
Floor installation into N columns
A*M+B*N+C*N
Note: "M" means the number of batteries, "N" means the number of clusters.
WARNING
Avertissemen
Battery+
Battery-
PE
CAN communication
AXE 5.0L Cable
To PCS
Avertissemen

13 14
Fig 4.8: Power connection
Note:
1) The battery is not allowed to be wired in the running state, and the RUN lights of the
battery module should all be off before installation.
2) Please install the communication line first, then plug the unused RJ45 port and USB
port with a dust cover, and finally install the power line.
3) To ensure the safety of the system, do not forget to ground the ground wire.
4) We recommend installing a circuit breaker between the PCS and the battery. For the
specifications of the circuit breaker, we recommend using a molded case circuit breaker
with a rated operating voltage greater than 80Vdc and a rated operating current greater
than 200A.
5) No cable connection required between battery packs in a single battery cluster.
4.5.2.3 Multi-cluster wiring
. . .
CAN communication
Power+
Power-
PE
To PCS
Cluster 1 Cluster 2 Cluster 3 Cluster 8
Fig 4.9: Block diagram of multi-cluster system
PCS Link-in Link-out
PCS Link-in Link-out
PCS Link-in Link-out
PCS Link-in Link-out
To PCS CAN
Cluster 1 Cluster 2 Cluster 3 Cluster 8
...
Fig 4.10: Multi-cluster communication wiring
Note:
1) Refer to Figure 13 for power line wiring.
2) The power combiner box needs to be prepared by the user.
3) Please install the communication line first, then plug the unused communication port
and USB port with a dust cover, and finally install the power line.
4) We recommend installing a circuit breaker between the PCS and each cluster.. For the
specifications of the circuit breaker, we recommend using a molded case circuit breaker
with a rated operating voltage greater than 80Vdc and a rated operating current greater
than 200A.
RJ45 dust cover USB dust cover
PCS
PCS
Press down
PCS
Battery HUB

4.5.3 Remove the power cord
PCS
Press
Press
Upwards
Fig 4.11: Remove the power cord
Power on and off the Battery 5
5.1 Power On
WARNING
ØThe installation and use of batteries involve much specialized
knowledge. Therefore, technicians should be given appropriate
technical training and obtain operational certificates in compliance
with local laws and regulations. Please ensure technicians have
obtained training certificate before operation/ L'installation et
l'utilisation des batteries impliquent des connaissances très
spécialisées. Par conséquent, les techniciens doivent recevoir une
formation technique appropriée et obtenir des certificats opérationnels
conformément aux lois et réglementations locales. Veuillez vous assurer
que les techniciens ont obtenu un certificat de formation avant
l'utilisation.
ØPlease stand on dry insulating objects and do not wear conductive
material such as watches and necklace during operation. Insulated
tools should be used/ Veuillez vous tenir sur des objets isolants secs et
ne pas porter de matériaux conducteurs tels que des montres et des
colliers pendant le fonctionnement. Des outils isolés doivent être
utilisés.
ØDo not contact any positions with potential difference/ Ne contactez
aucune position avec une différence de potentiel.
ØProhibition sign should be hung on the battery: " Non -
professionals, do not touch"/ Un panneau d'interdiction doit être
accroché sur la batterie : " Non - professionnels, ne pas toucher ".
ØIf any abnormalities occur during the startup phase, power off the
PACK immediately. After problem confirmed, proceed again/ Si des
anomalies surviennent pendant la phase de démarrage, mettez
immédiatement le PACK hors tension. Une fois le problème confirmé,
recommencez.ACK immediately. After problem confirmed, proceed
again.
Ø Make sure the inverter is turned off before checking the PACK/
Assurez-vous que l'onduleur est éteint avant de vérifier le PACK.
15 16
Step 1: Remove the security screw
Step 2: Press the buttons on both sides of the terminal at the same time, and then pull it
out forcefully
When multiple batteries are connected in parallel or multiple clusters of batteries are
connected in parallel, press one of the battery power buttons and all the batteries
connected in parallel can be turned on.
WARNING
Avertissemen
Power on the PACK by pressing power button(t>2S)
Serial
Procedures
Acceptation criteria
1
Connect the battery and PCS
Make sure the wiring harnesses are well
connected
2
Close the breaker of the PACK
Make sure the breaker is ON
3
Press POWER button for three to
five seconds. Observe the LED
indication on panel.
1. If both RUN/ALM and SOC lights turn on
normally, PACK is powered on successfully.
2. If RUN/ALM light turns red, there is a failure
and should solve it before power on again.
4.6 About mixing old and new batteries in parallel
Please ensure batteries in parallel connection are from the same batch, same model
and same manufacturer. Do not mix an old battery with a new battery. Batteries
undergone less than 300 cycles are defined as new batteries.The installation time of
the newly added battery and the installed battery is less than or equal to 1 year, and
the newly added battery must be within the shelf life of 6 months.

5.2 Power off
Press the power button to turn off the PACK and five LED lights will flicker for three
times. If under the situation of multiple packs in parallel, only turning off one of the
packs then the whole battery system will turn off.
Power on the PACK by PCS
1
Connect the battery and PCS
Make sure the wiring harnesses are well
connected
2
Close the breaker of the PACK
Make sure the breaker is ON
3
Power on the PCS. PCS outputs
a wake up signal of 5V or an
output main circuit voltage
signal of 46-58V
1. If both RUN/ALM and SOC lights turn on
normal, PACK powers on successfully.
2. If RUN/ALM light turns red, there is a failure
and should solve it before power on again.
Maintenance Guide 6
6.1 Preparation
6.2 PACK Replacement
§Wear safety gloves.
§Open the breaker and power off the PACK.
§Remove your safety screw under the power supply, and disconnect the power cord and
CAN communication line of the PACK.
§Remove the safety part at the left end of the battery and lift the PACK upward.
§Put the PACK into the packing box according to the repair procedure and transport the
PACK to the designated repair site.
§Install new PACK based on procedure specified in Section 4.
6.3 System Failure Information List and Troubleshooting
Suggestions
Error
Indication
Error
description
Error cause
Suggested actions
ALM
( ALM
Light
Flickers)
Discharge under
voltage
protection
Single cell voltage
below the threshold
for under-voltage
protection.
There is over discharge risk. User
should stop discharging and
arrange recharge
Charge over
voltage
protection
Single cell voltage
exceeding threshold
for protection
threshold.
1. There is no safety threat;
2. User should stop charging.Idle
PACK and it will turn to normal
status.
External CAN
Communication
failure
Communication loss
between
PCS and PACK.
1. There is no safety threat and
user should stop using battery.
2. Check if PCS and battery
communication terminal is well
connected.
3. If PCS and PACK cannot
communicate when the
communication wire is confirmed
well connected, user should
contact installer to repair battery.
17 18
ØTools like safety gloves, cross head driver and socket wrench should be prepared.
ØTurn off and turn on new PACK.
1. If the PACK is power-off. Press power button for 3-5 seconds to turn on.
2. If the PACK is power-on. Press power button once to turn off.
Before maintaining the battery, turn off the breaker and press power button once to
make sure the PACK is power-off. Follow the installation and wire connection procedures
specified above. Ensure wires are properly connected before turn the breaker on. After
that, turn on the breaker and press power button of any PACK for 3-5 seconds to check if
the system normal works.
3.When installing or maintaining, it is recommended that the battery SOC be at
35%~45% percent.

20
( ALM
Light
Flickers)
Interior CAN
Communication
failure
Communication loss
between
two parallel
1. Check Can connection
between two batteries, CAN
connection between Linkin and
Linkout;
Parallel
connection
failure
protection
Communication
failure
between two
parallel
connected PACK
1. Check Can connection
between two batteries, CAN
connection between Battery and
PCS;
(ALM
Light on)
Discharge short
circuit
External short circuit
of
PACK
There is safety risk and user
should stop using battery
User should contact installer to
Precharger short
circuit
Precharger
overtime circuit
Type
inconsistency of
PACK
The pack type is
different
There is safety risk and user
should stop using battery
User should contact installer to
use the same PACK in Parallel.
Main circuit fault
BMS main power
circuit failure
There is safety risk and user
should stop using battery.
User should contact installer to
repair battery
Technical Specifications 7
19
No.
Items
Specification
1
Parallel number of Battery systems
1
2
2
Battery Model
AXE 5.0L-C1/X1
AXE 10.0L-C1/X1
3
Nominal Capacity/Energy
100Ah/5.0kWh
200Ah/10.0kWh
4
Rated Capacity/Energy
90Ah/4.6kWh
180Ah/9.2kWh
5
Rated Voltage
51.2V
6
Operating Voltage
46.4 - 57.6V
7
Rated Charging/discharging current
60A
120A
8
Max Charging/discharging current
80A
150A
9
Over current protection
90A
160A
10
Rated Charging/discharging power
3kW
6kW
11
Max Charging/discharging power
4kW
7.6kW
12
Battery Type
Cobalt Free Lithium Iron Phosphate (LFP)
13
Operative temperature range
0°C~50°C
14
Recommended operating
15°C~30°C
15
Storage conditions
Temperature: -20°C ~ +50°C/ 7 days
-20°C~40°C/6 months
Humidity:5%~85%RH
Within six months after initial charge
16
Cooling
Natural cooling
17
Dimension (W/D/H)(mm)
650*350*140
650*350*280
18
Weight
40kg
80kg
19
Installation
Floor standing installation
20
Ingress protection
IP 20
21
Cell safety certification
IEC62619/UL1973
22
PACK certification
IEC 62619/IEC 63056/
UL1973/CE/UKCA/FCC/RoHS/UN38.3
23
Charging batteries
See Appendix II
24
Communication port
CAN
25
Battery Designation
IFpP/51/161/119
/[(1P16S)1P]M/0
+50/90
IFpP/51/161/119/
[(1P16S)2P]M/0+
50/90
26
Multiple clusters in parallel
Max.8 Clusters
Functional parameters of AXE 5.0L Energy Storage System are as shown below:

22
21
No.
Items
Specification
1
Parallel number of Battery systems
3
4
2
Battery Model
AXE 15.0L-C1/X1
AXE 20.0L-C1/X1
3
Nominal Capacity/Energy
300Ah/15.0kWh
400Ah/20.0kWh
4
Rated Capacity/Energy
270Ah/13.8kWh
360Ah/18.4kWh
5
Rated Voltage
51.2V
6
Operating Voltage
46.4 - 57.6V
7
Rated Charging/discharging current
120A
120A
8
Max Charging/discharging current
160A
160A
9
Over current protection
160A
160A
10
Rated Charging/discharging power
7.6kW
7.6kW
11
Max Charging/discharging power
8.1kW
8.1kW
12
Battery Type
Cobalt Free Lithium Iron Phosphate (LFP)
13
Operative temperature range
0°C~50°C
14
Recommended operating
temperature
15°C~30°C
15
Storage conditions
Temperature: -20°C ~ +50°C/ 7 days
-20°C~40°C/6 months
Humidity:5%~85%RH
Within six months after initial charge
16
Cooling
Natural cooling
17
Dimension (W/D/H)(mm)
650*350*420
650*350*560
18
Weight
120kg
160kg
19
Installation
Floor standing installation
20
Ingress protection
IP 20
21
Cell safety certification
IEC62619/UL1973
22
PACK certification
IEC 62619/IEC 63056/
UL1973/CE/UKCA/FCC/RoHS/UN38.3
23
Charging batteries
See Appendix II
24
Communication port
CAN
25
Battery Designation
IFpP/51/161/119
/[(1P16S)3P]M/0
+50/90
IFpP/51/161/119/
[(1P16S)4P]M/0+
50/90
26
Multiple clusters in parallel
Max.8 Clusters
No.
Items
Specification
1
Parallel number of Battery systems
5
6
2
Battery Model
AXE 25.0L-C1/X1
AXE 30.0L-C1/X1
3
Nominal Capacity/Energy
500Ah/25.0kWh
600Ah/30.0kWh
4
Rated Capacity/Energy
450Ah/23.0kWh
540Ah/27.6kWh
5
Rated Voltage
51.2V
6
Operating Voltage
46.4 - 57.6V
7
Rated Charging/discharging current
120A
120A
8
Max Charging/discharging current
160A
160A
9
Over current protection
160A
160A
10
Rated Charging/discharging power
7.6kW
7.6kW
11
Max Charging/discharging power
8.1kW
8.1kW
12
Battery Type
Cobalt Free Lithium Iron Phosphate (LFP)
13
Operative temperature range
0°C~50°C
14
Recommended operating
temperature
15°C~30°C
15
Storage conditions
Temperature: -20°C ~ +50°C/ 7 days
-20°C~40°C/6 months
Humidity:5%~85%RH
Within six months after initial charge
16
Cooling
Natural cooling
17
Dimension (W/D/H)(mm)
650*350*700
650*350*840
18
Weight
200kg
240kg
19
Installation
Floor standing installation
20
Ingress protection
IP 20
21
Cell safety certification
IEC62619/UL1973
22
PACK certification
IEC 62619/IEC 63056/
UL1973/CE/UKCA/FCC/RoHS/UN38.3
23
Charging batteries
See Appendix II
24
Communication port
CAN
25
Battery Designation
IFpP/51/161/119
/[(1P16S)5P]M/0
+50/90
IFpP/51/161/119/
[(1P16S)6P]M/0+
50/90
26
Multiple clusters in parallel
Max.8 Clusters

23 24
No.
Items
Specification
1
Parallel number of Battery systems
7
8
2
Battery Model
AXE 35.0L-C1/X1
AXE 40.0L-C1/X1
3
Nominal Capacity/Energy
700Ah/35.0kWh
800Ah/40.0kWh
4
Rated Capacity/Energy
630Ah/32.2kWh
720Ah/36.8kWh
5
Rated Voltage
51.2V
6
Operating Voltage
46.4 - 57.6V
7
Rated Charging/discharging current
120A
120A
8
Max Charging/discharging current
160A
160A
9
Over current protection
160A
160A
10
Rated Charging/discharging power
7.6kW
7.6kW
11
Max Charging/discharging power
8.1kW
8.1kW
12
Battery Type
Cobalt Free Lithium Iron Phosphate (LFP)
13
Operative temperature range
0°C~50°C
14
Recommended operating
temperature
15°C~30°C
15
Storage conditions
Temperature: -20°C ~ +50°C/ 7 days
-20°C~40°C/6 months
Humidity:5%~85%RH
Within six months after initial charge
16
Cooling
Natural cooling
17
Dimension (W/D/H)(mm)
650*350*980
650*350*1120
18
Weight
280kg
320kg
19
Installation
Floor standing installation
20
Ingress protection
IP 20
21
Cell safety certification
IEC62619/UL1973
22
PACK certification
IEC 62619/IEC 63056/
UL1973/CE/UKCA/FCC/RoHS/UN38.3
23
Charging batteries
See Appendix II
24
Communication port
CAN
25
Battery Designation
IFpP/51/161/119
/[(1P16S)7P]M/0
+50/90
IFpP/51/161/119/
[(1P16S)8P]M/0+
50/90
26
Multiple clusters in parallel
Max.8 Clusters
No.
Items
Specification
1
Parallel number of Battery systems
9
10
2
Battery Model
AXE 45.0L-C1/X1
AXE 50.0L-C1/X1
3
Nominal Capacity/Energy
900Ah/45.0kWh
1000Ah/50.0kWh
4
Rated Capacity/Energy
810Ah/41.4kWh
900Ah/46.0kWh
5
Rated Voltage
51.2V
6
Operating Voltage
46.4 - 57.6V
7
Rated Charging/discharging current
120A
120A
8
Max Charging/discharging current
160A
160A
9
Over current protection
160A
160A
10
Rated Charging/discharging power
7.6kW
7.6kW
11
Max Charging/discharging power
8.1kW
8.1kW
12
Battery Type
Cobalt Free Lithium Iron Phosphate (LFP)
13
Operative temperature range
0°C~50°C
14
Recommended operating
temperature
15°C~30°C
15
Storage conditions
Temperature: -20°C ~ +50°C/ 7 days
-20°C~40°C/6 months
Humidity:5%~85%RH
Within six months after initial charge
16
Cooling
Natural cooling
17
Dimension (W/D/H)(mm)
650*350*1260
650*350*1400
18
Weight
360kg
400kg
19
Installation
Floor standing installation
20
Ingress protection
IP 20
21
Cell safety certification
IEC62619/UL1973
22
PACK certification
IEC 62619/IEC 63056/
UL1973/CE/UKCA/FCC/RoHS/UN38.3
23
Charging batteries
See Appendix II
24
Communication port
CAN
25
Battery Designation
IFpP/51/161/119
/[(1P16S)9P]M/0
+50/90
IFpP/51/161/119/
[(1P16S)10P]M/0
+50/90
26
Multiple clusters in parallel
Max.8 Clusters

Appendix I
LED indication Control Mechanism
LED light definition
Status
Items
SOC indication
RUN/ALM
Remark
LED1
LED2
LED3
LED4
LED5
Charge
SOC
0%-25%
(t=1S)
RUN/ALM light
on and one SOC
lights flicker
26%-50%
(t=1S)
51%-75%
(t=1S)
76%-99%
(t=1S)
100%
Discharge
SOC
100%-76%
75%-51%
50%-26%
25%-0%
Idle
100%-76%
75%-51%
50%-26%
25%-0%
Parallel
connectio
n
Parallel
connection
succeeds
SOC indicates current remaining
capacity
RUN/ALM light
flicker green
Protection
Cell charge
overvoltage
alarm
(t=1S)
RUN/ALM light
flicker green
Cell charge
overvoltage
protection
(t=1S)
RUN/ALM light
flicker green
PACK
charge
overvoltage
alarm
(t=1S)
RUN/ALM light
flicker green
PACK
charge
overvoltage
protection
(t=1S)
RUN/ALM light
flicker green
Over
charge and
over
discharge
alarm
(t=1S)
RUN/ALM light
flicker green
Over charge
and over
discharge
protection
(t=1S)
RUN/ALM light
flicker green
Charging
current limit
does not
respond
(t=1S)
RUN/ALM light
flicker green
Charge and
discharge
high
temperature
alarm
(t=1S)
RUN/ALM light
flicker green
Charge and
discharge
high
temperature
protection
(t=1S)
RUN/ALM light
flicker green
Charge and
discharge
low
temperature
alarm
(t=1S)
RUN/ALM light
flicker green
Charge and
discharge
low
temperature
protection
(t=1S)
RUN/ALM light
flicker green
Cell
discharge
undervoltag
e alarm
(t=1S)
RUN/ALM light
flicker green
Cell
discharge
undervoltag
e protection
(t=1S)
RUN/ALM light
flicker green
PACK
discharge
undervoltag
e alarm
(t=1S)
RUN/ALM light
flicker green
PACK
discharge
undervoltag
e protection
(t=1S)
RUN/ALM light
flicker green
Charge and
discharge
Overcurrent
hardware
protection
(t=1S)
RUN/ALM light
flicker green
25 26

28
27
Mos high
temperature
alarm
(t=1S)
RUN/ALM light
flicker green
Mos high
temperature
protection
(t=1S)
RUN/ALM light
flicker green
High
temperature
environment
alarm
(t=1S)
RUN/ALM light
flicker green
High
temperature
environment
protection
(t=1S)
RUN/ALM light
flicker green
Cell Large
voltage
difference
alarm
(t=1S)
RUN/ALM light
flicker green
Cell Large
voltage
difference
protection
(t=1S)
RUN/ALM light
flicker green
difference
protection
between
PACK
voltage and
module
voltage
(t=1S)
RUN/ALM light
flicker green
Parallel
connection
over charge
and over
discharge
alarm
(t=1S)
RUN/ALM light
flicker green
Fault,perso
nnel
handling
required
Discharge
short circuit
SOC indicates current remaining
capacity
(t=1S)
RUN/ALM light
flicker red
Precharged
short circuit
(t=1S)
RUN/ALM light
flicker red
Precharged
overtime
circuit
(t=1S)
RUN/ALM light
flicker red
External
CAN
communicat
ion failure
(t=1S)
RUN/ALM light
flicker red
Interior CAN
communicat
ion failure
(t=1S)
RUN/ALM light
flicker red
Parallel
connection
failure
(t=1S)
RUN/ALM light
flicker red
Type
inconsistenc
y of PACK
(t=1S)
RUN/ALM light
flicker red
Batteries
failure
protection
RUN/ALM light
stays red
Voltage
sampling
anomaly
protection
RUN/ALM light
stays red
Current
sampling
fault
RUN/ALM light
stays red
Main circuit
fault
RUN/ALM light
stays red
Shenzhen Growatt New Energy Co., Ltd
4-13/F,Building A,Sino-German(Europe) Industrial Park,Hangcheng Ave,
Guxing Community,Xixiang Subdistrict, Bao’an District, Shenzhen, China
+86 755 2747 1942
www.ginverter.com
T
E
W
service@ginverter.com
Appendix II
Charging batteries
1) Charge with 60A constant current to the highest cell voltage of 3.53V;
2) Charge with25A constant current charging to the highest cell voltage 3.54V;
3) Charge with10A constant current charging to the highest cell voltage 3.55V;
4) Charge with5A constant current charging to the highest cell voltage 3.55V
(SOC is 100%)
This manual suits for next models
1
Table of contents
Other Growatt Storage manuals
Popular Storage manuals by other brands

SanDisk
SanDisk ImageMate CompactFlash quick start guide

Supermicro
Supermicro Supero SC847DE16-R1K28LPB user manual

Seagate
Seagate Barracuda 7200.7 ST360019A product manual

Seagate
Seagate MOMENTUS 5400.2 SATA product manual

LaCie
LaCie Little Big Disk Quadra user manual

Maxtor
Maxtor STM31000528AS datasheet

OilSafe
OilSafe Advanced Bulk System owner's manual

Livarno Living
Livarno Living 306270 Instructions for use

Fujitsu
Fujitsu ETERNUS DX60 user guide

Brocade Communications Systems
Brocade Communications Systems 1606 Reference

Western Digital
Western Digital WD1000FYPS - RE2-GP Quick install guide

Logicube
Logicube SuperSonix-NG user manual