Dimensions
RAIL MOUNT 35mm
(DIN 50022)
Installation Types
.
the maximum allowable peak current "Ip" must be less than
100 times the rms current of the switched capacitor.
WARNING: DANGEROUS VOLTAGE VALUES MAY CAUSE SHOCK
AND BURNING. In THESE CIRCUMSTANCES, ALWAYS DISABLE
POWER BEFORE INTERVENTION.
DO NOT INTERFERE WITH CONTRACTORS AND DO NOT PRESS THE
POSITION INDICATOR WHEN ENERGY IS IN THE SYSTEM AND THE LOAD IS
LOCKED FUNCTION TEST WITHOUT CONDENSATOR DESARGATION NO
FUNCTION TEST WITHOUT DESARGING.
VERY IMPORTANT NOTE:
For single compensation air coils or 3-phase reactors (coils with magnetic core
and air gap) are not necessary.
When the contactor is used for group (central) compensation we recommend to
use appropriate 3-phase filter circuit reactors (coils with magnetic core and air
gap).
At single compensation the power of selected contactor is according to
capacitors rated power.
At group and central compensation the power of selected contactor has to be
one step higher than-capacftor's rated power (if you don't use reactors).
During exploitation, current value must not exceed the declared values. Use
only HRC fuses gG type for each step for short circuit protection.
Use only halogen free connection wires.
CHANGING THE COIL
C
ABLE SELE
C
TION
S
G
GRUPARGE
Dimensions
RAIL MOUNT 35mm
(DIN 50022)
CHANGING THE COIL
.
the maximum allowable peak current "Ip" must be less than
100 times the rms current of the switched capacitor.
WARNING: DANGEROUS VOLTAGE VALUES MAY CAUSE SHOCK
AND BURNING. In THESE CIRCUMSTANCES, ALWAYS DISABLE
POWER BEFORE INTERVENTION.
DO NOT INTERFERE WITH CONTRACTORS AND DO NOT PRESS THE
POSITION INDICATOR WHEN ENERGY IS IN THE SYSTEM AND THE LOAD IS
LOCKED FUNCTION TEST WITHOUT CONDENSATOR DESARGATION NO
FUNCTION TEST WITHOUT DESARGING.
VERY IMPORTANT NOTE:
For single compensation air coils or 3-phase reactors (coils with magnetic core
and air gap) are not necessary.
When the contactor is used for group (central) compensation we recommend to
use appropriate 3-phase filter circuit reactors (coils with magnetic core and air
gap).
At single compensation the power of selected contactor is according to
capacitors rated power.
At group and central compensation the power of selected contactor has to be
one step higher than-capacftor's rated power (if you don't use reactors).
During exploitation, current value must not exceed the declared values. Use
only HRC fuses gG type for each step for short circuit protection.
Use only halogen free connection wires.
Contactor installation, step: A and B
Contactor removal, step: 1, 2 and 3
Contactor installation, step: A and B
Contactor removal, step: 1, 2 and 3
C
ABLE SELE
C
TION
Installation Types