GTE ADICOS HOTSPOT-X0 Interface-X1 User manual

EN
HOTSPOT-X0 Interface-X1
Operating manual
IR-Temperatur Detector

ADICOS HOTSPOT-X0 Interface-X1 - Operating manual
Article number: 410-2410-011
Index: EN12
Release date: 03.05.2021
– Translation –
Manufacturer:
GTE Industrieelektronik GmbH
Helmholtzstr. 21, 38-40
41747 Viersen
GERMANY
Support hotline: +49 2162 3703-0
E-Mail: [email protected]
© 2021 GTE Industrieelektronik GmbH – This document and all figures contained may not be copied,
changed, or distributed without explicit approval by the manufacturer!
Subject to technical changes!
ADICOS®and GSME®are registered trademarks of GTE Industrieelektronik GmbH.

I
HOTSPOT-X0 Interface-X1 410-2410-011 EN11
KURZBESCHREIBUNG
Kurzbeschreibung
The Advanced Discovery System (ADICOS) is used for early detection of fires in industrial
environments. It is comprised of various separate detector units. With aid of suitable
arrangement and parameterization the system meets a specified detection goal, without being
suspectable to interference.
The detector units are connected using the ADICOS M-Bus to a central unit, which enables
voltage supply and parameterization of every individual detector, and which stores all sensor
data for statistical analyses.
The ADICOS HOTSPOT-X0 Interface-X1 is an interface between the ADICOS HOTSPOT-X0
Sensor Unit and the fire control panel within potentially explosive atmospheres of zones 0, 1,
and 2. Additionally it can be used as a connection and branching box (AAB) within these
zones.

CONTENTS
II HOTSPOT-X0 Interface-X1410-2410-011 EN12
Contents
1 About this manual .......................................... 3
1.1 Objective ........................................... 3
1.2 Explanation of symbols .................................. 3
1.3 Abbreviations......................................... 4
1.4 Storing the manual ..................................... 4
2 Safety instructions........................................... 5
2.1 Intended use ......................................... 5
2.2 Standards and regulations ................................ 5
2.3 Personnel qualification ................................... 6
2.4 Handling electrical voltage ................................ 6
2.5 Modification ......................................... 6
2.6 Accessories and spare parts ............................... 6
3 Accessories............................................... 7
4 Structure ................................................. 8
4.1 Overview ........................................... 8
4.2 Connection terminals .................................... 9
5 Installation ...............................................11
5.1 Selecting the mounting location .............................11
5.2 Wall mounting ........................................11
6 Wiring..................................................12
6.1 Wiring of ADICOS HOTSPOT-X0 Sensor Unit ...................12
6.2 Wiring of the fire detection system ...........................13
7 Commissioning ............................................13
8 Maintenance..............................................14
9 Disposal.................................................14
10 Specifications .............................................15

3
HOTSPOT-X0 Interface-X1
ABOUT THIS MANUAL
410-2410-011 EN12
1 About this manual
1.1 Objective
These instructions describe the requirements on installation, wiring, commissioning, and oper-
ation of the ADICOS HOTSPOT-X0 Interface-X1. After commissioning it is used as reference
work in the case of faults.
It is exclusively addressed to knowledgeable specialist personnel (–› Chap. 2, Safety instructions).
1.2 Explanation of symbols
This manual features a continuous structure for best possible comprehension. Here, the follow-
ing labels are used.
Action objectives
Action objectives describe the result to be achieved by the subsequent instructions. Action
objectives are presented in bold font.
Action instructions
Action instructions describe the activities to be performed in order to achieve the action objec-
tive previously mentioned. Action instructions are presented as follows.
►Individual action instruction
1 First of several sequential action instructions
2 Second of several sequential action instructions
3 etc.
Intermediate states
In the case of describable intermediate states or results, which are the result of action steps
(e.g. displays, internal function steps, etc.), are presented as follows.
ZIntermediate state
Warning signs
This manual uses the following information types.
NOTE!
This information type provides information directly important for further
system operation.

ABOUT THIS MANUAL
4HOTSPOT-X0 Interface-X1410-2410-011 EN12
WARNING!
This information type signals a danger that can lead to fatal or severe
injuries.
DANGER!
This information type signals a danger that directly leads to fatal or severe
injuries.
DANGER!
This information type signals measures that must be implemented for maintaining
the explosion protection.
1.3 Abbreviations
This manual uses the following abbreviations.
Abbr. Meaning
ADICOS Advanced Discovery System
X0 Ex zone 0
X1 Ex zone 1
1.4 Storing the manual
Store this manual easily reachable and in direct vicinity of the detector to enable use as
needed.

5
HOTSPOT-X0 Interface-X1 410-2410-011 EN12
SAFETY INSTRUCTIONS
2 Safety instructions
The ADICOS HOTSPOT-X0 Interface-X1 ensures operational safety assuming proper installation,
commissioning, operation and maintenance. For this purpose, it is absolutely required to com-
pletely read, understand, and follow these instructions and the safety information contained.
WARNING!
Installation and operating errors can lead to fatal and severe injuries and
damage to the industrial system.
−Read and follow this manual carefully!
2.1 Intended use
The ADICOS HOTSPOT-X0 Interface-X1 is intended for use with the ADICOS HOTSPOT-X0
Sensor Unit and is designated for the detection of fire scenarios in potentially explosive atmo-
spheres of zones 0, 1, and 2. It may be exclusively operated within ADICOS systems. In this
context, the operating parameters described in Chap. 8, »Maintenance« must be met. Any
deviating use requires prior consultation with the manufacturer.
Compliance with this manual as well as all applicable country-specific provisions is also part
of the intended use.
2.2 Standards and regulations
The safety and accident prevention regulations applicable for the specific application must
be observed during ADICOS HOTSPOT-X0 Interface-X1 installation, commissioning, mainte-
nance, and test.
The ADICOS HOTSPOT-X0 Interface-X1 also meets the following standards and directives:
Regulation Description
2014/34/EU ATEX Product Directive
1999/92/EG ATEX Operational Directive
DIN EN 60079-0:2012
IEC 60079-0:2011
Explosive atmospheres
Equipment - General requirements
DIN EN 60079-1:2014
IEC 60079-1:2014
Explosive atmospheres
Equipment protection by flameproof enclosures „d“
DIN EN 60079-11:2012
IEC 60079-11:2011
Explosive atmospheres
Equipment protection by intrinsic safety “I”

SAFETY INSTRUCTIONS
6HOTSPOT-X0 Interface-X1410-2410-011 EN12
2.3 Personnel qualication
Any work on ADICOS systems may only be performed by qualified personnel. Persons, who
can perform work on electrical systems in potentially explosive atmospheres and recognize
possible dangers based on their professional education, knowledge, and experience as well
as knowledge of the applicable provisions, are considered qualified persons.
WARNING!
Installation, commissioning, parameterization, and maintenance may only be
performed by authorized and respectively trained personnel.
2.4 Handling electrical voltage
DANGER!
The electronics of the ADICOS HOTSPOT-X0 Interface-X1 works with a voltage
that can trigger an explosion in potentially explosive atmospheres.
−De-energize the entire detector system and secure
against unintentional reactivation for all wiring work!
2.5 Modication
WARNING!
Any form of unauthorized modifications or extensions are expressively
prohibited!
−In case of doubt, contact the manufacturer!
2.6 Accessories and spare parts
WARNING!
Only original spare parts and original accessories of the manufacturer
may be used!

7
HOTSPOT-X0 Interface-X1 410-2410-011 EN12
ACCESSORIES
3 Accessories
WARNING!
Only original accessories of the manufacturer may be used!
The following accessories are available for the ADICOS HOTSPOT-X0 Interface-X1:
Art no. Description
410-2401-310 HOTSPOT-X0 Sensor Unit
83-09-06052 Cable gland for non-reinforced and non-sealed cables
83-09-06053 Cable gland for reinforced and non-sealed cables
83-09-06050 Cable gland for non-reinforced and sealed cables
83-09-06051 Cable gland for reinforced and sealed cables

STRUCTURE
8HOTSPOT-X0 Interface-X1410-2410-011 EN12
4 Structure
4.1 Overview
No. Description
①Flameproof enclosure
②Top-hat rail with Ex barriers, connection terminals and interface circuit board
③Thread for enclosure lid
④Enclosure lid
⑤Mounting place for additional cable glands
⑥Cable gland (2x)
⑦Mounting bracket (4x)
1
2
3
4
6
5
7

9
HOTSPOT-X0 Interface-X1 410-2410-011 EN12
STRUCTURE
4.2 Connection terminals
The connection terminals are located inside the enclosure on the top-hat rail.
Nr. Beschreibung
①Ex barrier 1: sensor communication (intrinsically safe circuit 1)
②Ex barrier 2: sensor power supply (intrinsically safe circuit 2)
③System connection
4.2.1 Sensor communication (intrinsically safe circuit 1)
No. Occupation
9Cabinet shielding
10 Shield for intrinsically safe cable
11 -/-
12 -/-
13 Sensor communication B
14 Sensor communication A
15 -/-
16 -/-
4.2.2 Sensor power supply (intrinsically safe circuit 2)
No. Occupation
1Sensor power supply +
2Sensor power supply –
3-/-
1
2
3

STRUCTURE
10 HOTSPOT-X0 Interface-X1410-2410-011 EN12
4.2.3 System connection terminal
No. Occupation
10 V
20 V
3M-Bus A
4M-Bus A
5Alarm A
6Fault A
7LOOP A in
8LOOP A out
9Shield
10 Shield
11 +24 V
12 +24 V
13 M-Bus B
14 M-Bus B
15 Alarm B
16 Fault B
17 LOOP B in
18 LOOP B out
19 Shield
20 Shield

11
HOTSPOT-X0 Interface-X1 410-2410-011 EN12
INSTALLATION
5 Installation
WARNING!
Installation work may only be performed, if the potentially explosive
area is released for work via a risk assessment.
−De-energize the entire detector system and secure against
unintentional reactivation for all wiring work!
5.1 Selecting the mounting location
WARNING!
In contrast to the ADICOS HOTSPOT-X0 Sensor Unit, the ADICOS HOTSPOT-X0
Interface-X1 is not approved for installation within Ex zone 0.
−The device may only be installed outside of Ex zone 0!
The following aspects have to be considered when choosing the mounting location.
– Install device easily accessible and in direct vicinity to the connected sensor – but outside
of Ex zone 0.
– The mounting location must satisfy all environmental requirements specified in Chap. 10,
»Specifications«.
– The mounting spot must be solid and free of vibrations.
5.2 Wall mounting
WARNING!
Improper installation of the ADICOS AABs can lead to faults and failures
of the detector system.
−Mounting may only be performed by specialist personnel!
(–› Chap. 2.3, Personnel qualification)
1 At the mounting location drill four holes (Ø8) in a pattern
of 240 x 160 mm
2 Press in suitable dowels
3 Using the mounting brackets firmly bolt the enclosure to the
wall using four suitable screws and washers
240
160

WIRING
12 HOTSPOT-X0 Interface-X1410-2410-011 EN12
6 Wiring
WARNING!
Installation work may only be performed, if the potentially explosive
area is released for work via a risk assessment.
−De-energize the entire detector system and secure against
unintentional reactivation for all wiring work!
−Wiring may only be performed by specialist personnel!
(–› Chap. 2.3)
WARNING!
The ADICOS HOTSPOT-X0 Interface-X1is subject to the protection principle
and/or the ignition protection type equipment protection by ameproof
enclosures „d“.
−Only use approved cable glands!
−Firmly close enclosure lid after wiring!
6.1 Wiring of ADICOS HOTSPOT-X0 Sensor Unit
WARNING!
The connection cable must be routed according to DIN EN 60079-14!
−Only use approved, intrinsically safe connection cables provided
by GTE!
−Observe minimum bending radius!
1 Remove enclosure lid by rotating counter clockwise
2 Open cable gland
3 Insert sensor connection cable through cable gland
4 Connect green wire (communication A) to terminal 14 of
Ex barrier 1 (intrinsically safe circuit 1)
5 Connect yellow wire (communication B) to terminal 13 of
Ex barrier 1 (intrinsically safe circuit 1)
6 Connect brown wire (power supply +) to terminal 1 of Ex
barrier 2 (intrinsically safe circuit 2)
7 Connect white wire (power supply –) to terminal 2 of Ex
barrier 2 (intrinsically safe circuit 2)
8 Connect shield of sensor connection cable to terminal 3 of
Ex barrier 2 (intrinsically safe circuit 2)
9 Close cable gland
10 Mount enclosure lid by rotating clockwise and pulling tight
green yellow
white brown

13
HOTSPOT-X0 Interface-X1 410-2410-011 EN12
COMMISSIONING
6.2 Wiring of the re detection system
Depending on the system configuration connect the fire detection system to terminals 1 ... 20
of the system connection terminal (–› Chap. 4.2.3).
Also consult GTE-manual No. 430-2410-001 (ADICOS AAB Operating manual) and
GTE-manual No. 430-2410-004 (ADICOS AAB-L Operating manual).
7 Commissioning
DANGER!
ADICOS systems work with electricity that may lead to system damage
and fire in the case of improper installation.
−Prior to switching on, check that all detectors are properly
mounted and wired!
−Commissioning may only be performed by qualied
specialist personnel!
DANGER!
The ADICOS HOTSPOT-X0 Interface-X1is subject to the protection principle
and/or the ignition protection type equipment protection by ameproof
enclosures „d“.
−Firmly close enclosure lid before commissioning!
NOTE!
The ADICOS HOTSPOT-X0 Interface-X1 is a passive component. A separate
commissioning is not required.
−Initialize the ADICOS re detection system according to the
operating manual of the installed central unit (ADICOS BMZ-30 /
M-Busmaster)!

MAINTENANCE
14 HOTSPOT-X0 Interface-X1410-2410-011 EN12
8 Maintenance
The ADICOS HOTSPOT-X0 Interface-X1 does not require maintenance.
9 Disposal
Return device to the manufacturer after the end of the useful
life. The manufacturer ensures environmental-friendly dispos-
al of all components.

15
HOTSPOT-X0 Interface-X1 410-2410-011 EN12
SPECIFICATIONS
10 Specications
General information
Enclosure dimensions: mm 220 x 220 x 180 (L x W x H)
Overall dimensions: mm 270 x 264 x 180 (L x W x H)
Enclosure material: Aluminium
Weight: kg 8
Cable bending radius: mm > 38
Protection class: IP 66
Information regarding explosion protection
Explosion protection class: II 2(1)G Ex db [ia Ga] IIC T4 Gb
Temperature class: T4
Device group: II, category 2G
Type approval: Certificate per 2014/34/EU
IECEx certificate: IECEx KIWA 17.0007X
ATEX certificate: KIWA 17ATEX0018 X
Electrical properties
Uo[1,2] V≥17
Io[1,2] mA ≥271
Po[1,2] W≥1,152
Uo[13,14] V≥3,7
Io[13,14] mA ≥225
Po[13,14] mW ≥206
Ui[13,14] V≤30
Ii[13,14] mA ≤282
CO[1,2] µF 0,375
LO[1,2] mH 0,48
LO/RO[1,2] µH/Ω30
CO[13,14] µF 100
LO[13,14] mH 0,7
LO/RO[13,14] µH/Ω173

Table of contents