Guardian Controls International RCC-50 User guide

Guardian Controls International Ltd 1
GUARDIAN RCC-50
Reciprocating Compressor Controller
•Single-stage or Dual-stage Reciprocating compressor controller
•Pressure, temperature, capacity% and load% displays
•Suction pressure setpoint control of up to 4 capacity loading valves
•Alarm and trip monitoring
•Multiple pack/compressor system control
•Local panel operation and set-up of pack configuration & control modes
•Communications for remote monitoring and set-up
Operation and Setup Manual
The GUARDIAN RCC-50 Compressor Pack Controller provides suction pressure setpoint
control and alarm monitoring for either a single-stage or a dual-stage large industrial
reciprocating compressor with up to 4 loading valves.
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 2
Contents
GUARDIAN RCC-50................................................................................1
GETTING STARTED................................................................................4
BUTTON OPERATION SHORTHAND.................................................................................5
HARDWARE CONFIGURATION CHECKS.........................................................................5
CONFIGURE UNIT MODEL, SYSTEM No & ADDRESS ....................................................6
Enter Passcode.................................................................................................................6
Select Unit Model..............................................................................................................6
Select System No and Address ........................................................................................7
RS485 Communications ...................................................................................................7
UNIT MODELS.........................................................................................8
OVERVIEW ..........................................................................................................................8
Functions...........................................................................................................................8
Displays.............................................................................................................................9
Pushbuttons......................................................................................................................9
GENERAL SPECIFICATION..............................................................................................10
AVAILABLE UNIT MODELS (RCC-50).............................................................................10
RCC-50 Input/Output Signals........................................................................................11
RCC50 Fuse Ratings......................................................................................................12
RCC50 FUSES and LED LAYOUT.................................................................................13
RCC-50 Termination Wiring - SSrL model selection.......................................................14
RCC-50 Termination Wiring - dSrL model selection.......................................................15
OPERATION..........................................................................................16
RCC-50 PANEL LAYOUT..................................................................................................16
CONTROL STATUS LED LAMPS ..................................................................................16
LED LAMPS. ...............................................................................................................17
ALARM INPUTS..............................................................................................................17
SYSTEM STATUS DISPLAYS........................................................................................17
Enter System Setup Mode...........................................................................................17
Control status displays. ...............................................................................................18
Relay ouput status.......................................................................................................18
Inputs...........................................................................................................................18
Trip inputs....................................................................................................................19
SAFETY TRIP INDICATIONS.........................................................................................19
DISPLAY PUSHBUTTON OPERATION............................................................................20
‘view’ ...............................................................................................................................20
‘type’................................................................................................................................20
CONTROL PUSHBUTTON OPERATION..........................................................................22
“mode”.............................................................................................................................22
“Mode-MANUAL”.............................................................................................................22
“Mode-AUTOMATIC” ......................................................................................................22
“RESET”..........................................................................................................................23
“stop”...............................................................................................................................23
“start”...............................................................................................................................23
“Lower”............................................................................................................................23
“Raise”.............................................................................................................................23
SETTINGS CHANGE PUSHBUTTON OPERATION.........................................................24
“next”...............................................................................................................................24
“Accept”...........................................................................................................................24
“raise”..............................................................................................................................24
“Lower”............................................................................................................................24
ALARM ACCEPT AND RESET PUSHBUTTON OPERATION.........................................25
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 3
SETPOINTS .......................................................................................................................26
CONTROL MODES............................................................................................................27
CONTROL..............................................................................................28
COMPRESSOR CONTROL OPERATION.........................................................................28
POWER UP.....................................................................................................................28
RUNNING .......................................................................................................................28
STOPPING......................................................................................................................30
MODES CHANGES ........................................................................................................30
TIMER SETPOINTS ...........................................................................................................30
SETUP ...................................................................................................31
Compressor Settings .......................................................................................................31
Unit Settings:...................................................................................................................31
Clock Settings.................................................................................................................31
System Settings..............................................................................................................32
Port Settings....................................................................................................................33
Hours run ........................................................................................................................33
Analog.............................................................................................................................33
PT....................................................................................................................................33
Test.................................................................................................................................34
Done................................................................................................................................34
TRANSDUCER SETUP & CALIBRATION.....................................................................35
TRANSDUCER SETUP...............................................................................................35
PRESSURE TRANSDUCER SETUP..........................................................................36
CAPACITY % SETUP .................................................................................................37
MOTOR LOAD % SETUP ...........................................................................................37
COMMUNICATIONS..............................................................................38
MONITOR HIGHWAY MODBUS COMMUNICATIONS (COM1).......................................38
CONTROL HIGHWAY COMMUNICATIONS (COM2) .......................................................39
Suction Group Control Communications........................................................................40
Setup / Commissioning Parameters ...............................................................................41
Settings display and change facilities............................................................................43
RCC-50 Enclosure wiring: for trips negative .................................................................45
RCC-50 Enclosure wiring: for trips positive. .................................................................46
FITTING NEW EPROM..........................................................................47
CORRECT POSITIONING OF EPROM ALIGN INDICATED INDENTS.............................47
Index ..................................................................................................................................48
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 4
GETTING STARTED
Guardian Controllers provide refrigeration engineers with
•ULTIMATE FLEXIBILITY
•ASSURED MONITORING
•RELIABLE ALARMS
This manual provides refrigeration designers, installers, service mechanics and supermarket
personnel with the necessary information to achieve the above objectives.
All users require to know a few basic facts about this controller before successfully starting to
perform their design, commissioning, maintenance or operating functions.
a) All GUARDIAN controllers need to be set up with a unit model selection and other basic
b) settings for setpoints, timers and addresses.
c) The shorthand used in the following chapters for concisely expressing button pressing
and selection sequences to do all this set-up needs to be understood.
d) Mains power input voltage and hardware switch and link option selections
(if any are required) must correspond to the selected unit model configuration.
e) Since each controller can be configured in a number of different ways to perform flexible
refrigeration control then an understanding of how to find out what unit model is currently
selected, what it does and how it is connected, is also necessary.
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 5
BUTTON OPERATION SHORTHAND
To assist in easy set-up of control setpoints, delays, timers and other configuration settings,
the sequence of button presses and subsequent displays will be shown in this handbook as
below:
ii) A button symbol, followed by text means press that button. “@accept”
iii) A double button, followed by text means press that button repeatedly. “@:@raise”
iv) A display box with the window above it shows the result of the last button press on
the display.
DISCHARGE OIL2
==== 2.0b
“@:@raise”
DISCHARGE OIL2
==== 2.5b
v) DISCHARGE OIL2 DISCHARGE OIL2
H.P. ==== trip ====
Means the display alternately flashes between identifier and trip message
HARDWARE CONFIGURATION CHECKS
Prior to switching on the GUARDIAN controller check that the hardware unit is the correct
type for the incoming mains voltage.
When satisfied that the correct type of controller is available then the following checks should
be made prior to controller installation or replacement
a) Ensure mains supply is wired correctly to the appropriate TERMINAL WIRING drawing for
the model selected.
b) Ensure that any transducer selector switches specified on the TERMINAL WIRING
diagram are in the correct state.
c) Ensure any shorting link selector pins specified on the TERMINAL WIRING diagram are
correctly fitted.
d) Ensure that probes are wired to the terminal WIRING DIAGRAM and the correct type of
thermistor or pressure transducer probes are fitted.
e) The RS485 highway connections (if required) are wired to the correct terminals and the
screen drain wire is continuous to earth.
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 6
CONFIGURE UNIT MODEL, SYSTEM No & ADDRESS
Enter Passcode
Before any permanent change of controller settings are made then the correct entry of the
appropriate passcode is necessary.
The settings available for change on each passcode are as follows; Passcode
Passcode level 1 setpoints, low & high alarm settings 07
Passcode level 2 low & high trip settings and all level 1 09
Passcode level 3 system settings and levels 1 & 2 15
Enter passcode 15
DISCHARGE
OIL2 “@view”= “SETPOINT” “@next” “@next”
pASS codE
DISCHARGE OIL2 DISCHARGE OIL2
==-= ==12
“@:@raise” ==-= ==15
“@accept”
Press “view” to select “SETPOINT”, then press the “next” button twice to enter
the passcode settings.
Press “raise” repeatedly until passcode 15 is selected and then press “accept”
Select Unit Model
Enter Passcode as button sequence above.
“@:@view”= “SYSTEM”
SUCTION
OIL1 “@:@type”= “SAFETY TRIPS”
==sE tUP=
DISCHARGE OIL2
==== =yEs
“@accept”
DISCHARGE OIL2 DISCHARGE OIL2
==== Unit
“@accept” ==== SSrL
“@:@raise”
DISCHARGE OIL2
==== dSrL
“@accept”
Press ‘view’ repeatedly until ‘SYSTEM’ is selected.
Press ‘type’ repeatedly until ‘SAFETY TRIPS’ is selected. Press ‘accept’
‘Unit’ is displayed press ‘accept’
Display shows unit model currently selected which may be wrong.
Press ‘raise’ repeatedly until correct model is displayed (e.g.SSrL) and then press ‘accept’
which causes the display to wink briefly and display the new unit model selection (e.g dSrL)
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 7
Select System No and Address
e.g. setup unit for system 65 compressor number 1 at address 195
Enter setup as button sequence as above
SUCTION OIL1
==sE tUP=
DISCHARGE OIL2
==== =yEs
“@accept”
DISCHARGE OIL2
DISCHARGE OIL2
==== Unit
“@accept” ==== dSrL “@next”
DISCHARGE OIL2
DISCHARGE OIL2
==== Sn01
“@:@raise” ==== Sn65 “@accept”
DISCHARGE
OIL2 “@next”
==== Cn01
“@accept”
DISCHARGE OIL2
“@next”
==== A=01
“@:@raise”
DISCHARGE OIL2
==== A195
“@accept”“@:@next”
DISCHARGE OIL2
==== donE
“@accept”
RS485 Communications
When the correct system number, case/compressor number and highway address have
been entered as above then the controller can communicate with the GUARDIAN Consultant
Terminal PC for central alarm monitoring and temperature display. Control setpoints, timers
and alarm limits may then be sent to the controller from the PC.
For further details see page 38
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 8
UNIT MODELS
Guardian controllers may be configured in a number of different ways dependent on unit
model selection. Each unit model fulfils a different refrigeration temperature monitoring and
control requirement. In order to perform the required refrigeration control then each model
has different uses for the controller’s input output signals. This section gives details of all the
model variations available for the controller and the way to connect the wiring to the plant
devices and measuring transducers.
OVERVIEW
Functions
The GUARDIAN RCC-50 controller provides facilities for:-
MONITORING
Measurement of 5 pressures and 5 temperatures and pack load for control, alarm and trip
display.
Calculation of differential pressures and superheat temperatures for control, alarm and trip
display.
Detection of digital input states on up to 8 safety trip inputs.
ALARMS
Detection after a preset guardtime of pressure and temperature High/Low alarms when the
compressor is in operation. Alarms are indicated by alternating a =Hi= or =Lo=
message on the appropriate temperature or pressure display.
TRIPS
Detection of pressure and temperature High/Low trips which stop the compressor. Trips are
indicated by the flashing red TRIPPED lamp and an alternating 'TRIP' message on the
appropriate temperature/pressure display.
Automatic trips include:-
high discharge temperature
low suction pressure
high discharge pressure
MCB overload
high/low suction superheat
low oil flow
Low oil level
Detection of safety trips which stop the compressor.
Trips are indicated by the flashing red TRIPPED lamp and an appropriate message.
Trips vary dependent on pack model configuration.
ie :- nncb ,H.P. ,diff,syst alternating with a trIP message on the
appropriate display.
CONTROLS
Control of compressor motors, and different combinations of loading valves dependent on
suction pressure setpoint.
Startup and run sequences use preset timers and limits plus compressor runhours to
determine control sequence actions.
Compressor stage is indicated by LED lamps on the control panel.
Suction pressure initiation of other compressors in the system via a RS485 link when in
REMOTE mode.
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 9
Displays
i). SUCTION, DISCHARGE, OIL1 & OIL 2 .
SUCTION OIL1
2.1b 11.7b
4-digit 7-segment LED displays for display of
measurements setpoints/limits for temperatures and
pressures
DISCHARGE OIL2
The contents change dependent on ‘view’ and
10.2b 11.5b ‘type’ selections
ii). CAPACITY%.
CAPACITY%
100
3-digit 7-segment LED displays for display of loading timers
and capacity.
iii). MOTOR LOADING%.
MOTOR LOAD%
105
3-digit 7-segment LED displays for display of timers and
motor load.
iv). COMPRESSOR No.
No
1
1-digit 7-segment LED display
Pushbuttons.
All pushbuttons are embossed, tactile membrane switches.
start, stop, raise & lower used to control compressors when in manual mode.
RESET used after a trip to reset the compressor.
Mode, view & type used in conjunction with appropriate LED displays to select
control, display or settings change facilities.
accept, next used in conjunction with raise, lower and appropriate LED
displays during setpoint and limit settings changes.
Unaccepted alarms and trips are acknowledged by pressing accept.
Pushbuttons on the local control panel permit operator display of setpoints, pressures,
temperatures, alarm and trip settings and compressor runhours and status.
Setpoints, alarm and trip settings may be changed from the panel after entry of the
appropriate passcode.
The compressor may be selected to operate in one of three control modes:-
MANUAL, LOCAL or REMOTE MODES.
Safety interlocks, alarm, trip, startup and shutdown sequence controls are automatic in
all three modes.
In MANUAL mode, the each compressor may be individually started and stopped and the
pack capacity raised and lowered by operator pushbutton control from the local panel.
In LOCAL automatic mode, the compressor is started and stopped under control of the
suction pressure setpoint.
REMOTE automatic mode allows up to six RCC-50 units to be connected via a two-wire
communication link (RS485) to provide 6-unit system control.
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 10
GENERAL SPECIFICATION
Power 110 or 230 Vac 50 hz 30VA (dependent on model type)
Operation 0 to 50ºC
Approx. Dimensions:
Control panel: 300 x 220mm
Control unit: 300 x 230 x 90mm
The GUARDIAN RCC-50 control unit comprises a printed circuit board in an IP65 ABS
enclosure for mounting at the rear of the compressor pack control panel with the display
unit mounted on the door and has overall dimensions:- 300 x 230 x 90mm.
The unit is fitted with two-part screw-clamp terminals for the connection of the
appropriate input/output signals. (See input/output section)
The GUARDIAN RCC-50 control panel comprises a membrane, pushbutton and display
panel mounted on the front of the control unit.
The membrane front panel has a Black background with white lettering and blue buttons with
dimensions 300x220mm.
AVAILABLE UNIT MODELS (RCC-50)
C1LF 1 compressors with 4x25% loading selection
4 condenser fans
8 trips
2 alarms Low Liquid Level
Condenser Fan Fail
1 input External Max demand unload i/p
C1L4 1 two-stage compressor with 0,30,60,80,100%
loading selection with intermediate pressure
4 condenser fans
8 trips
3 start signals
2 alarms Low Liquid Level
Condenser Fan Fail
1 input External Max demand unload i/p
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 11
RCC-50 Input/Output Signals
C1L4
Analogue inputs
A1 Suction pressure 4 to 20mA -1 to 24 bar g
A2 Discharge pressure 4 to 20mA -1 to 24 bar g
A3 C1 oil pressure 4 to 20mA -1 to 24 bar g
A4 Intermediate pressure (dSrL only) 4 to 20mA -1 to 24 bar g
A5 Suction temperature PT1000
-50 to 180°C
A6 Discharge temperature PT1000
-50 to 180°C
A7 Oil temperature PT1000
-50 to 180°C
A8 Intermediate temperature (dSrL only) PT1000 -50 to 180°C
A9 (Optional liquid level) 0 to 5V dc 0 to 100%
A10 (Optional pack load %) 0 to 10V dc 0 to 127%
A11 Not used
Calculated inputs
Total pack capacity
Equivalent Suction temperature
Equivalent Discharge temperature
Equivalent intermediate temperature
Diff discharge pressure
Diff oil pressure
Diff pump pressure
Hours run
Digital inputs
Trip 1 High discharge temperature trip
Trip 2 L.P Safety trip
Trip 3 H.P safety trip
Trip 4 Oil Level trip (surge drum high)
Trip 5 Oil flow trip
Trip 6 M.C.B overload trip
Trip 7 Emergency stop
Trip 8 System trip (intercooler high)
12/24V dc inputs
Input A Max demand reduce load
Input B Keyswitch
Input C Condenser fan fail
Input D Liquid Level Alarm
Mains inputs
Input E Liquid pump running
Input F Condenser fans running
Input G External start/stop
Input H Not used
input I External reset pushbutton
Relay outputs
R1 Motor 1 contactor
R2 Loading 30%
R3 Loading 60%
R4 Loading 80%
R5 Loading 100%
R6 Not used
R7 Not used
R8 Not used
R9 Not used
Extension outputs
OP1 Not used
OP2 Not used
OP3 Not used
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 12
RCC50 Fuse Ratings
FUSE Rating Littlefuse part CCT protection Terminal
s
F101 125 mA 0453 .125 Com 2 RS485 B line TB11-2
F102 125 mA 0453 .125 Com 2 RS485 A line TB11-3
F103 125 mA 0453 .125 Com 1 RS485 B line TB4-2
F104 125 mA 0453 .125 Com 1 RS485 A line TB4-3
F105 1 A - T 0454 001. Display CN1
F106 1 A - T 0454 001. Extension CN2
F201 1 A - T 0454 001. 24 Vdc supply TB12A-1
F202 1 A - T 0454 001. 12 Vdc supply TB12-4
F203 125 mA 0453 .125 24 Vdc supply TB5-2
F204 3.5 A - T 0454 03.5 24 Vac Incoming TB3-1
F401 125 mA 0453 .125 24 Vdc supply TB10A-4
TB10-4
TB6-16
TB6-12
TB6-8
TB6-4
TB7A-5
F402 125 mA 0453 .125 5 Vdc supply TB7-5
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 13
RCC50 FUSES and LED LAYOUT
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
TB1-9
TB1-10
TB1-11
TB1-12
TB1-13
TB1-14
TB1-15
TB1-16
TB1-17
TB1-18
TB1-19
TB1-20
TB1-21
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
TB3-1
TB3-2
TB3-3
TB3-4
TB3-5
TB3-6
TB3-7
TB3-8
TB3-9
TB3-10
TB3-11
TB3-12
TB6-4
TB6-3
TB6-2
TB6-1
TB6-8
TB6-7
TB6-6
TB6-5
TB6-12
TB6-11
TB6-10
TB6-9
TB6-16
TB6-15
TB6-14
TB6-13
TB10A-4
TB10A-3
TB10A-2
TB10A-1
TB7-4
TB7-3
TB7-2
TB7-1
TB7A-3
TB7A-2
TB7A-1
TB7A-5
TB7A-4
TB7-5
TB8-3
TB8-2
TB8-1
TB8-6
TB8-5
TB8-4
TB8-9
TB8-8
TB8-7
TB8-12
TB8-11
TB8-10
TB9-3
TB9-2
TB9-1
TB9A-3
TB9A-2
TB9A-1
TB9-6
TB9-5
TB9-4
TB11-3
TB11-2
TB11-1
TB12A-
3
TB12A-
2
TB12A-
1
TB12-3
TB12-2
TB12-1
TB12-4
TB12-5
TB4-1
TB4-2
TB4-3
TB5-1
TB5-2
TB5-3
TB5-4
TB5-5
TB5-6
TB10-4
TB10-3
TB10-2
TB10-1
1
2
3
4
5
6
CN 2
EARTH
1
2
3
4
5
6
ON
RL 1
RL 2
RL 3
RL 4
RL 5
RL 6
RL 7
RL 8
RL 9
RL A
RL B ip T8
ip T7
ip T6
ip T5
ip T4
ip T3
ip T2
ip T1
TRIP INPUT
STATUS
RELAYOUTPUT
STATUS
F202 OK
F201 OK
EXT OUTPUT
STATUS
C D E F G
F105 OK COM 2
F105 OK
F401 OK
F203 OK
INPUT
STATUS
A B C D
H
G
F
E
RxTx
Rx
Tx
COM 1
F106 OK
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 14
RCC-50 Termination Wiring - SSrL model selection
Single-stage Compressor with Three Stages of Loading Control
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
TB1-9
TB1-10
TB1-11
TB1-12
TB1-13
TB1-14
TB1-15
TB1-16
TB1-17
TB1-18
TB1-19
TB1-20
TB1-21
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
TB3-1
TB3-2
TB3-3
TB3-4
TB3-5
TB3-6
TB3-7
TB3-8
TB3-9
TB3-10
TB3-11
TB3-12
TB6-4
TB6-3
TB6-2
TB6-1
TB6-8
TB6-7
TB6-6
TB6-5
TB6-12
TB6-11
TB6-10
TB6-9
TB6-16
TB6-15
TB6-14
TB6-13
TB10A-4
TB10A-3
TB10A-2
TB10A-1
TB7-4
TB7-3
TB7-2
TB7-1
TB7A-3
TB7A-2
TB7A-1
TB7A-5
TB7A-4
TB7-5
TB8-3
TB8-2
TB8-1
TB8-6
TB8-5
TB8-4
TB8-9
TB8-8
TB8-7
TB8-12
TB8-11
TB8-10
TB9-3
TB9-2
TB9-1
TB9A-3
TB9A-2
TB9A-1
TB9-6
TB9-5
TB9-4
TB11-3
TB11-2
TB11-1
TB12A-3
TB12A-2
TB12A-1
TB12-3
TB12-2
TB12-1
TB12-4
TB12-5
TB4-1
TB4-2
TB4-3
TB5-1
TB5-2
TB5-3
TB5-4
TB5-5
TB5-6 Dig IP A
Dig IP B
Dig IP C
Dig IP D
RS 485 A / +
RS 485 B / -
RS 485 E / 0V
24 V dc
0 V dc
Com 1 Dig IP E
Dig IP F
Dig IP G
Dig IP H
24 V ac
0 V ac
C
NC
NO
C
NCRelay
10 (A)
NO
Relay
11 (B)
Dig IP T1
Dig IP T2
Dig IP T3
Dig IP T4
Dig IP T5
Dig IP T6
Dig IP T7
Dig IP T8
NC
C
NO
NC
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
Relay
1
Relay
2
Relay
Relay
Relay
Relay
Relay
Relay
Relay
8
7
9
6
4
5
3
NEUTRAL
(Suppression common)
0 V dc
12 V dc
Dig OP 16 (G)
Dig OP 15 (F)
Dig OP 14 (E)
Dig OP 13 (D)
Dig OP 12 (C)
24 V dc
RS 485 A / +
RS 485 B / -
RS 485 E / 0V
Com 2
0 V dc
An OP 1
An OP 2
+ VE
- VE
0 V dc
+ VE
- VE
0 V dc
+ VE
- VE
0 V dc
+ VE
- VE
0 V dc
+ VE
- VE
0 V dc
+ VE
- VE
0 V dc
An IP 6
Pt1000
An IP 5
Pt1000
An IP 1
Pt1000
An IP 2
Pt1000
An IP 3
Pt1000
An IP 4
Pt1000
0 V dc
0 V dc
5 V dc
An IP 13
An IP 14
/ Pt100
/ Pt100
/ Pt100
/ Pt100
/ Pt100
/ Pt100
(0-10 V)
(0-10 V)
(0-10 V dc)
(0-10 V dc)
24 V dc
An IP 16
0 V dc (4-20 mA)
24 V dc
An IP 7
0 V dc (4-20 mA)
0 V dc
24 V dc
An IP 9
0 V dc (4-20 mA)
0 V dc
24 V dc
An IP 10
0 V dc
(4-20 mA)
0 V dc
24 V dc
An IP 11
0 V dc (4-20 mA)
0 V dc
24 V dc
An IP 12
0 V dc (4-20 mA)
0 V dc
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(12 / 24 V)
(12 / 24 V)
(12 / 24 V)
(12 / 24 V)
Supply
Return
24 V dc
An IP 8
0 V dc (4-20 mA)
0 V dc
TB10-4
TB10-3
TB10-2
TB10-1
RS485 E / 0V
RS485 B / -
RS485 A / +
RS485 E / 0V
RS485 B / -
RS485 A / +
0 V dc
An OP 1
An OP 2
34 12
RS485 E / 0V
RS485 B / -
RS485 A / +
RS485 E / 0V
RS485 B / -
RS485 A / +
0-5 A ac
0-5 A ac An IP 15
Line
Neutral
Dip 18
Dip 17
5 V
0 V
SCL
SDA1
2
3
4
5
6
CN 2
EARTH
1
2
3
4
5
6
ON
Not used
Not used
Motor load current
(using XX : 5 A CT)
Not used
Not used
Not used
Oil Pressure
Discharge Pressure
Suction Pressure
Max demand unload
Condensor fan fault
Keyswitch
Liquid level low
Motor load current
(using 0-10V Transducer)
Not used
Not used
Oil Temperature
Discharge Temperature
Suction Temperature
Not used
Not used
Not used
Output (Compressor motor RUN)
Output (Loading valve No 1 LOAD)
Output (Loading valve No 2 LOAD)
Output (Loading valve No 3 LOAD)
Output Condensor stage 1 RUN)
Output (Condensor stage 2 RUN) / (Liquid injection / Oil cooling RUN)
Output (Condensor stage 3 RUN) / (Oil heater RUN)
Output (Condensor stage 4 RUN)
Output (Starting Bypass valve RUN)
Input (Discharge temperature high = CUTOUT)
Input (Suction preessure low = CUTOUT)
Input (Discharge pressure high = CUTOUT)
Input (Oil level low = CUTOUT)
Input (Oil differential / Flow fail = CUTOUT)
Input (Motor circuit breaker open = CUTOUT)
Input (Emergency stop switch active = CUTOUT)
Input (General safety fault active = CUTOUT)
Safety inputs are group selectable
Tpos = 230 / 110 V is active fault
Tneg = 230 / 110 V is clear
Output (Alarm condition ACTIVE)
Output (Trip condition ACTIVE)
OR
Input (Not used)
Input (Compressor --- Rpos = ENABLE / Rneg = DISABLE)
Input (Not used)
Input (Not used)
Not used
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 15
RCC-50 Termination Wiring - dSrL model selection
Dual-stage Compressor with Four Stages of Loading Control
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
TB1-9
TB1-10
TB1-11
TB1-12
TB1-13
TB1-14
TB1-15
TB1-16
TB1-17
TB1-18
TB1-19
TB1-20
TB1-21
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
TB3-1
TB3-2
TB3-3
TB3-4
TB3-5
TB3-6
TB3-7
TB3-8
TB3-9
TB3-10
TB3-11
TB3-12
TB6-4
TB6-3
TB6-2
TB6-1
TB6-8
TB6-7
TB6-6
TB6-5
TB6-12
TB6-11
TB6-10
TB6-9
TB6-16
TB6-15
TB6-14
TB6-13
TB10A-4
TB10A-3
TB10A-2
TB10A-1
TB7-4
TB7-3
TB7-2
TB7-1
TB7A-3
TB7A-2
TB7A-1
TB7A-5
TB7A-4
TB7-5
TB8-3
TB8-2
TB8-1
TB8-6
TB8-5
TB8-4
TB8-9
TB8-8
TB8-7
TB8-12
TB8-11
TB8-10
TB9-3
TB9-2
TB9-1
TB9A-3
TB9A-2
TB9A-1
TB9-6
TB9-5
TB9-4
TB11-3
TB11-2
TB11-1
TB12A-3
TB12A-2
TB12A-1
TB12-3
TB12-2
TB12-1
TB12-4
TB12-5
TB4-1
TB4-2
TB4-3
TB5-1
TB5-2
TB5-3
TB5-4
TB5-5
TB5-6 Dig IP A
Dig IP B
Dig IP C
Dig IP D
RS 485 A / +
RS 485 B / -
RS 485 E / 0V
24 V dc
0 V dc
Com 1 Dig IP E
Dig IP F
Dig IP G
Dig IP H
24 V ac
0 V ac
C
NC
NO
C
NCRelay
10 (A)
NO
Relay
11 (B)
Dig IP T1
Dig IP T2
Dig IP T3
Dig IP T4
Dig IP T5
Dig IP T6
Dig IP T7
Dig IP T8
NC
C
NO
NC
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
C
NO
Relay
1
Relay
2
Relay
Relay
Relay
Relay
Relay
Relay
Relay
8
7
9
6
4
5
3
NEUTRAL
(Suppression common)
0 V dc
12 V dc
Dig OP 16 (G)
Dig OP 15 (F)
Dig OP 14 (E)
Dig OP 13 (D)
Dig OP 12 (C)
24 V dc
RS 485 A / +
RS 485 B / -
RS 485 E / 0V
Com 2
0 V dc
An OP 1
An OP 2
+ VE
- VE
0 V dc
+ VE
- VE
0 V dc
+ VE
- VE
0 V dc
+ VE
- VE
0 V dc
+ VE
- VE
0 V dc
+ VE
- VE
0 V dc
An IP 6
Pt1000
An IP 5
Pt1000
An IP 1
Pt1000
An IP 2
Pt1000
An IP 3
Pt1000
An IP 4
Pt1000
0 V dc
0 V dc
5 V dc
An IP 13
An IP 14
/ Pt100
/ Pt100
/ Pt100
/ Pt100
/ Pt100
/ Pt100
(0-10 V)
(0-10 V)
(0-10 V dc)
(0-10 V dc)
24 V dc
An IP 16
0 V dc (4-20 mA)
24 V dc
An IP 7
0 V dc (4-20 mA)
0 V dc
24 V dc
An IP 9
0 V dc (4-20 mA)
0 V dc
24 V dc
An IP 10
0 V dc
(4-20 mA)
0 V dc
24 V dc
An IP 11
0 V dc (4-20 mA)
0 V dc
24 V dc
An IP 12
0 V dc (4-20 mA)
0 V dc
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(110 / 230 V ac)
(12 / 24 V)
(12 / 24 V)
(12 / 24 V)
(12 / 24 V)
Supply
Return
24 V dc
An IP 8
0 V dc (4-20 mA)
0 V dc
TB10-4
TB10-3
TB10-2
TB10-1
RS485 E / 0V
RS485 B / -
RS485 A / +
RS485 E / 0V
RS485 B / -
RS485 A / +
0 V dc
An OP 1
An OP 2
34 12
RS485 E / 0V
RS485 B / -
RS485 A / +
RS485 E / 0V
RS485 B / -
RS485 A / +
0-5 A ac
0-5 A ac An IP 15
Line
Neutral
Dip 18
Dip 17
5 V
0 V
SCL
SDA1
2
3
4
5
6
CN 2
EARTH
1
2
3
4
5
6
ON
Not used
Liquid level
(Using 4-20 mA Transducer)
Motor load current
(using XX : 5 A CT)
Not used
Not used
Intermediate Pressure
Oil Pressure
Discharge Pressure
Suction Pressure
Max demand unload
Condensor fan fault
Keyswitch
Liquid level low
Motor load current
(using 0-10V Transducer)
Liquid level
(Using 0-10 Vdc Transducer)
Intermediate Temperature
Oil Temperature
Discharge Temperature
Suction Temperature
Not used
Not used
Not used
Output (Compressor motor RUN)
Output (Loading valve No 1 LOAD)
Output (Loading valve No 2 LOAD)
Output (Loading valve No 3 LOAD)
Output (Loading valve No 4 LOAD)
Output (Liquid Injection / Oil cooling RUN)
Output (Oil heater RUN)
Output (Not Used)
Output (Starting Bypass valve RUN)
Input (Discharge temperature high = CUTOUT)
Input (Suction preessure low = CUTOUT)
Input (Discharge pressure high = CUTOUT)
Input (Surge drum level High = CUTOUT)
Input (Oil differential / Flow fail = CUTOUT)
Input (Motor circuit breaker open = CUTOUT)
Input (Emergency stop switch active = CUTOUT)
Input (General safety fault active = CUTOUT)
Safety inputs are group selectable
Tpos = 230 / 110 V is active fault
Tneg = 230 / 110 V is clear
Output (Alarm condition ACTIVE)
Output (Trip condition ACTIVE)
OR
OR
Input (Not used)
Input (Compressor --- Rpos = ENABLE / Rneg = DISABLE)
Input (Condensor RUN)
Input (Liquid pump RUN)
Not used
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 16
OPERATION
RCC-50 PANEL LAYOUT
GUARDIAN RCC-50 control panel comprises a membrane pushbutton and display panel
mounted on the front of the control unit.
The membrane front panel (shown below) has a black background with white lettering and
green buttons with dimensions 300 x 200mm and houses:-
Number, Capacity & Motor load windows.
Suction, discharge, oil1 & oil2 windows.
mode lower stop raise start reset accept next view type
RCC-50
Reciprocating compressor Controller
CONTROL STATUS LED LAMPS
STAGE 1 to Stage 8 Status LED lamps indicate the current pack stage of loading.
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 17
LED LAMPS.
Stage 1 to 8 Used to display compressor control stage status
TRIPPED Flashing RED compressor tripped indicator
MANUAL Mode selections: OFF, COMPRESSOR, CAPACITY
AUTOMATIC Mode selections: LOCAL, REMOTE
‘type’ 7 led lamps. Selection for 4-digit LED displays
PRESSURE, TEMPERATURE, EQUIVALENT TEMPERATURE
DIFFERENTIALS, HOURS RUN, TIMERS & SAFETY TRIPS
‘view’ 7 led lamps. Selection for 4-digit LED displays
LATEST VALUE, SETPOINT, LOW ALARM,
HIGH ALARM, LOW TRIP, HIGH TRIP & SYSTEM
ALARM INPUTS
When detected, the following digital alarm inputs alternate the alarm messages below with
'TRIP' in the windows specified and flash the 'type' = TIMERS LED lamp.
Fans overload FAnS TriP SUCTION
Liquid level alarm LEvL TriP DISCHARGE
Accept and reset procedures are the same as for other trips.
SYSTEM STATUS DISPLAYS
System status and set-up data may be displayed by selecting the following;
Press “@type” until “SAFETY TRIPS” is selected.
Press “@view” until “SYSTEM” is selected.
The data is displayed in the in the SUCTION, DISCHARGE, OIL1 and OIL2 windows by
pressing “@next.” Only displayed if keyswitch ON, or passcode = 3
Enter System Setup Mode
SUCTION OIL1
==SE tUp=
DISCHARGE OIL2
==== =YES
Press “@accept” to enter system set-up mode
Terminate passcode operation.
SUCTION OIL1
pASS code
DISCHARGE OIL2
==== End=
Press “@accept” to remove passcode
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 18
Control status displays.
SUCTION OIL1
Cont roL=
DISCHARGE OIL2
YYYY YYYY
DISCHARGE
OIL2
YYYY= suct ion=
Remote master suction control.
DISCHARGE OIL2
fuLL LoAd
Remote but at maximum load.
DISCHARGE OIL2
=sLI dE==
Remote slave in load sharing.
DISCHARGE OIL2
stAn dbY=
Remote mode, stopped but ready.
DISCHARGE OIL2
=LOC AL==
Compressor in local mode
DISCHARGE OIL2
Inhi bit=
Local mode but inhibited.
DISCHARGE OIL2
nnAN UAL=
Compressor in manual.
DISCHARGE OIL2
==== OFF=
Compressor OFF.
Relay ouput status.
SUCTION OIL1
=Out pUtS
DISCHARGE OIL2
1234 5678
- Is displayed if relay is OFF
1
to 8 Is displayed if relay is ON.
Relay output is dependent on model configuration.
Inputs
SUCTION OIL1
=InP UtS=
DISCHARGE OIL2
Abcd EfgH
A Max demand unload input
b
Optional keyswitch input
c
Low liquid level alarm.
d
Condenser fan fail
E-H Not fitted.
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 19
Trip inputs.
SUCTION OIL1
=tri pS==
DISCHARGE OIL2
1234 5678
- Is displayed if trip input is OFF
1
to 8 Is displayed if trip input is ON.
Trip input message depends on model configuration.
Trip inputs can be selected (tPoS or tneg) to act if active trip
signal is positive or negative. .
SAFETY TRIP INDICATIONS
When detected, the following safety trips alternate the trip messages below with 'TRIP'
in the windows specified and flash the 'type' = SAFETY TRIPS LED lamp.
Accept and reset procedures are the same as for other trips.
The messages depend on the model configuration
Trip Model RCC-50 message flash window
T1 Discharge temp hi trip dt-H Trip OIL2
T2 L.P. cutout L.P. Trip SUCTION
T3 H.P. cutout H.P. Trip DISCHARGE
T4 oil flow switch FLO. Trip OIL2
T5 oil level LEu. Trip OIL1
T6 motor circuit breaker nncb Trip SUCTION
T7 emergency stop stoP Trip DISCHARGE
T8 safety trip (other) sfty Trip OIL
GUARDIAN RCC-50 Issue V1.0 a 25/09/06

Guardian Controls International Ltd 20
DISPLAY PUSHBUTTON OPERATION
Display of all compressor measured values, setpoints, alarm and trip limit settings is
performed by repeated pressing of either the 'view' and / or 'type' pushbuttons.
At each button press the associated selection LED lamp advances by one in a clockwise
direction indicating the type or setting of the value displayed in the;
SUCTION, DISCHARGE, OIL1, OIL 2, CAPACITY% and LOAD% windows.
‘view’
To display the latest temperature values, the 'view' pushbutton is pressed repeatedly
until the LATEST VALUE LED lamp is lit.
‘type’
The 'type' pushbutton is then pressed repeatedly until the TEMPERATURE
LED lamp is lit.
The SUCTION, DISCHARGE, and OIL windows now display the latest measured
values of suction, discharge and oil temperatures respectively.
“@:@view” = “LATEST VALUE”
“@:@type” = “TEMPERATURE”
SUCTION OIL1
=-10 ====
DISCHARGE OIL2
==70 ====
To display the high alarm settings for pressures, the 'view' pushbutton is pressed
repeatedly until the HIGH ALARM LED lamp is lit, and then the 'type' pushbutton
is pressed repeatedly until the PRESSURE LED lamp is lit.
The SUCTION, DISCHARGE, OIL and OIL 2 windows now display the high alarm limit
settings, if applicable, for suction, discharge, oil and oil 2 pressures respectively.
“@:@view” = “HIGH ALARM”
“@:@type” = “PRESSURE”
SUCTION OIL1
==-5 ====
DISCHARGE OIL2
==85 ====
All pressures are displayed in the range: -1.0b to 24.0b where b= bar gauge
All temperatures are displayed in the range -50C to 125C where C= degrees centigrade
LOAD% and CAPACITY% are 0% to 125% where % is of maximum scale.
displayed in the range
GUARDIAN RCC-50 Issue V1.0 a 25/09/06
Table of contents
Other Guardian Controls International Controllers manuals
Popular Controllers manuals by other brands

Maestra
Maestra 8080 user manual

Mitsubishi Electric
Mitsubishi Electric AG-150A Instruction book

Mitsubishi Electric
Mitsubishi Electric Melservo MR-J3-10B instruction manual

Consort
Consort CRX2-03 Installation and user guide

Danfoss
Danfoss VLT HVAC Basic Drive FC 101 quick guide

Centork
Centork 482 Series Installation and Maintenance user Manual