Gulf+Western ACWC-SC User manual

MODEL
ACWC-SC
Screw Type
AIR
COOLED
PACKAGED
CHILLERS
SERVICE
MANUAL
I & 0 6500A
INSTALLATION,
OPERATION
&
MAINTENANCE
INSTRUCTIONS
TABLE OF
CONTENTS
DESCRIPTION PAGE NO.
Inspection
&
Handling
...........................................................................................
2
Location
&
Mounting
.
.......
...
......
...............................................
...................
.
.....
....
2
Wiring
..............................................................................................................
2
Chiller
Piping
.....................................................................................................
2
Start-Up
........................................................................................................
2 & 3
Maintenance
....
.
....
.
.......
.....
...........
.
........
.
.............
...
....
....
........
..
.........................
3
Slide Valve
Unloading
System
..................................................................................
4
Low
Ambient
Operation
.........................................................................................
5
Control
Settings
..................................................................................................
5
Unit
Operating
Limitations
......................................................................................
5
Sequence
of
Operation
......................................................................................
6 & 7
Models ACWC-160SC
Thru
200SC
Sequence
of
Operation
......................................................................................
8 & 9
Model
ACWC-215SC
Control
Wiring
Diagram
..................................................................................
10 &
11
Models ACWC-160SC
Thru
200SC
Control
Wiring
Diagram
....................................................................................
12-15
Model ACWC-215SC
Power Wiring Diagram
.............
....
....
...
..
...
....
..
.....
.
...
..
....
..
.......
......................
.
........
16
Across-The-Line
Start
Power
Wiring
Diagram
..........................................................................................
17
Star-Delta
Electrical Data
...................................................................................................
18
Cooler
Pressure
Drops
..........................................................................................
18
Unit
Loading/Suspension
Points
..............................................................................
18
Troubleshooting
Guide
....
..
...........
....
...........
...
..........
.
...........
.....
.....
..
....
...
............
.19
Causes & Prevention
of
Freeze-Up
............................................................................
19
Start-Up
Check
List
.....................................
.
.....
.. ..
...
.
..........................................
20
Operating
Data
...
.....
...........
....
.
...
....
.....
..
................
.
......
...........................
...
......
.. 20
BOHN
HEAT TRANSFER
A Gulf+Western
Company
Danville,
Illinois
61832•{217)446-3710
..
!
I

INSPECTION
&
HANDLING
When
unit
is received,
it
should
be
checked
for
visible
or
concealed
damage
. If
damage
has
occurred
it
should
be reported
to
the carrier
imm
e
diately
.
o.nd
clo.im
filed
.
Models
ACWC
160SC
thru
215SC are
factory
mounted
on
two
(2)
permanent
angle beam,
carbon
steel skids. Ei
ght
(8) 2W'
lifting
eyes
are
provided
in the
skids
to
allow
rigging.
Spreader bars
must
be
used between
rigging
lines
to
prevent
damage
to
the
unit. Rollers
may be used
under
the
skids
to
facilitate
moving
the
unit
a
short
distance
. Physical damage to the unit, after acceptance,
Is
not the
responsibility of the factory.
LOCATION
&
MOUNTING
Model
ACWC
Air
Cooled
Packaged Water
Chillers
are
designed
for
outdoor
application
and
may
be
mounted
on
roof
or
at
ground
level.
Air
flow
through
the
condenser
is vertical and the
unit
may be
located
adjacent
to
outside
of
building
or
on
roof
without
regard
for
prevailing
wind
direction.
Since
these
units
are
air
cooled,
the
flow
of
air
to
and
from
the
condenser
coil
must
not
be impeded.
There
must
be
no
obstruction
above the
unit
that
would
tend
to
deflect
discharge
air
downward
where
it
could
be
recirculated
back
to the
inlet
of
the unit. The
required
overhead
air
space
should
be a
minimum
of
eight
(8) feet.
Ductwork
must
not
be applied
to
the fan
outlets
.
The
unit
must
be
installed
with
sufficient
clearance
for
air
entrance
to
the
condenser
coil
and
for
servicing
access. The
unit
should
be
located
no
closerthan
four
(4) feet
from
any wall
or
other
obstruction
.
Clearance
must
be
provided
at
either
end
of
the
unit
to
permit
removal
of
tubes
from
the
chiller
.
Unit
must be set on a
solid
and level
foundation
.
On
roof
installations
the
unit
should
be
mounted
on
support
beams
which
span
load-bearing
walls
to
prevent excessive
vibration
.
On
ground
level
installations,
the
unit
should
be
mounted
on a
substantial
base
that
will
not
settle. A
one-piece
concrete
slab
with
footings
extended
below
the
frost
line is recommended. A space
should
be left between the
slab
and
the
building
to
prevent
the
transmission
of
sound
and
vibration
.
Vibration
mounts
may
be used
for
roof
mounted
units
or
other
locations
where noise
might
be
objectionable.
WIRING
A
unit
wiring
diagram
showing
the required
power
supply
character-
istics
and all
factory
supplied
wiring
details is
provided
with
unit.
Separate, field
supplied,
disconnects
must be installed in the
power
supply
and
should
be
within
the
sight
of
the unit.
Separate 115
volt
power
source
must be field
supplied
to
provide
power
for
control
and heater
circuits
.
2
CHILLER
PIPING
The
chiller
inlet
(return)
water
pipe
should
be
connected
to the water
connection
closest
to
the
control
panel end
of
the
unit
and the
outlet
(:.upply)
vvdte• 1-'ifJt::
<..v""""'t"'u
tv
u,.,
wat.,r
<,;urrrr.,<,;llun
on
the
opposite
end
of
the cooler(s).
A
flow
switch
must
be installed in a
straight
horizontal
section
of
the
chilled
water
piping
.
Gauges
should
be installed in
the
piping
to
and
from
the
chiller
to
measure
the
pressure
drop
and to
insure
the
proper
(GPM)
flow
rate
in
accordance
with
submittal
data. A
strainer
should
be
installed
in
the
piping
on the
inlet
side
of
the
chiller
and
vibration
eliminators
should
be
employed
on both the inlet and
outlet
pipes.
Air
vents
should
be located at all high
points
in the
piping
system. Vents
should
be located
to
be accessible
to
servicing
.Drain
connections
should
be
provided
at all
low
points
to
permit
complete
drainage
of
chiller
and
piping
system.
The
chilled
water
piping
should
be
insulated
to
reduce heat
pickup
and
to
prevent
condensation
.
If
the system is
for
year-round
operation
or
if
it
will
not
be
drained
in the winter,
the
chilled
water
piping
should
be protected againstfreezing by
electric
heating cable
or
other
suitable means.
Upon
completion
of
chiller
piping,
start
the
system water
pump
and
purge
air
from
the
system.
Air
purging
should
be
done
from
the
high
points
in
the
water
circuit.
Purging
of
the
chiller
barrel may be
accomplished
through
the
vent
pipe
located
on
the
top
of
the
chiller
compartment.
Failure
to
purge
air
from
the
water
circuit
will
result in
inadequate
waterflow
and maycause the
unit
to
cutout
on
low
water
flow
freeze
protection.
START-UP
Refer
to
start, test, and
check
list
included
with
this
manual.
Check
all
electrical
and
mechanical
connections
for
shipping
looseness and
tighten
all screws on electrical
terminals
.
Activate the 115
volt
chiller
and crankcase heater
circuit
24
hours
prior
to
unit
start-up
.
Rotateeach fan
prior
to
start-up
. Fans
should
turn
freely.
Check
belt
tension
and
pulley
alignment.
After
two
(2) weeks
of
operation,
readjust
belt
tension
to
accommodate
for
belt stretching.
Check
all
control
settings
as
specified in Table
1.
Check
the
compressor
oil level
through
the
crankcase
sight
glass.
The
oil
level
should
be
to
the
top
of
the glass. If
the
level is low, add
oil in
accordance
with
the
directions
in the
maintenance
instruction
(page 3).
..
~·
.
--..,_

. CAUTION:
The
discharge
line valve
must
be open
before
starting
the
compres-
sor
.
Liquid
line valves
must
also be open
for
sustained
operation
.
All compressorsare solia mountea on 1sopads,therefore,
compressor
hold-down
bolts
must
not
be loosened.
Loosening
these
bolts
will
cause excessive
vibration
of
the
compressor
and may result in
refrigerant
line breakage.
Prior
to
start-up
check
all
compressor
hold-down
bolts
for
tightness.
MAINTENANCE
CONDENSER
Units
equipped
with belt drive fans have
inherently
protected
motors
. Fan belts,fan
bearings
and
motor
bearings
require
periodic
maintenance
as
follows:
1. Fan Belts
-After
two
(2) weeks
operat
i
on
,
the
belts will have
nearly
reached
their
permanent
stretch,
therefore
, each belt
should
be
checked
again and
proper
adjustments
made.
To
maintain
good
fan and
motor
operation
,the belt tension
should
be
checked at three (3)
month
intervals.
2.
Fan
Bearings-
Each fan shaft is
prov
i
ded
with
ball
bearings
of
the
relubricatable
type
. Each bearing is provided
with
grease
fittings,
accessible
through
the
individual
motor
access panels. It
is
recommended
the bearings be greased
by
adding
4
to
5 shots
with
a hand
gun
.The suggested greasing interval is
indicated
on a
sticker
attached to the unit.
3.
Motor
Bearings-
Each
motor
is
equipped
with
ball bearings. Ball
bearings
consume
a very small
amount
of
lubricant
,
but
enough
must
be
present
at all
time
to prevent
motor
injury.
The
length
of
time
a bearing can run
without
having grease added
or
replaced
will
depend
upon
the
operating
conditions
.
Under
normal
operating
conditions
,the
motor
bearings
should
be
lubricated
at
2000
hour
operating
intervals
.
The
lubricant
should
be
from
a
clean closed
container
and
should
be an
anti-friction
type
bearing
grease-free
from
solid
fillers
or
other
harmful
ingredients
.
Lubricant
should
have a safe
operating
temperature
of
2000° F.
The
air
inlet
of
the
condenser
coil
should
be
kept
clean
through
a
regular
preventative
maintenance
program
.
COMPRESSOR
1.
OIL LEVEL -
The
oil
level in the
compressor(s)
should
be
checked
periodically,
with
the
compressor
either
running
or
stopped
. If
the
oil
level is
below
one-half
(
'12
) the
sight
glass, oil
must be added.
Oil
should
be added
only
with
the
compressor
shut
off
.
To
do
so,
turn
the
return
water
thermostat
(T1) to a
higher
temperature
setting
, and
wait
for
the
unit
to
pumpdown
and
shutoff.
Place the
system "
ON-OFF
"
switch
in the "OFF"
position
. Close
the
line
valve in the
discharge
line between
compressor
and
condenser
.
Refrigerant
pressure
inside
of
the
compressor
will
now
be
approximately
80 to 90 PSIG.
The
low
pressure
cut-out
setting is
35 PSIG,
but
the residual
discharge
pressure (upstream
of
the
discharge
check
valve)
will
equalize
back
into
the
suction
side
after
the
compressor
stops.
3
Locate
the
discharge
pressure
port
adjacent
to
solenoid
valve
UL-3
(see
drawing
below)
; remove
the
cap and release the
residual pressure
by
pushing
in on the pressure
port
fitting
itself.
Pump
oil
into
this
flU'
t
u11til
u,.,
uil
level
Is
to the
tOP
Of
the
sight
glass.
Replacethe
discharge
port
cap
. Re-open the discharge line valve.
Do not allow compressor to run with discharge valve closed.
Place
the
system
"ON-OFF"
switch
in
the
"
ON
"
position
.
Using
a
jumper
wire, makea
"short
"
for
five (5)
seconds
between
terminal
#4
on
terminal
block
TER5 and the
switched
terminal
of
a
solenoid
valve
feeding
the
circuit
you
have
just
"blown
" (e.g.
terminal
#121
on TER4 to energize
SOL
1).Reset return
water
thermostat
(~1)
to
the
operat
ional
temperature
setting and
allow
unit
to
return
to
normal
operation
.
2.
RECOMMENDED
OIL-
The
unit
is
factory-charged
with
BOHN
SR-30
refrigeration
oil.
Do not add any other type of oil
to
this factory charge.
Do not operate compressor
If
oil level
is
below one-half
('h)
sight
glass.
If
the
oil
level is
below
the
minimum
specified
above, and
BOHN
SR-30 is
not
on hand, you may drain the entire factory oil charge,
then refill
with
SUNISO 4GS
refrigeration
oil. The
factory
(BOHN)
oil is
of
the
synthetic
type
and will not mix
with
SUN
ISO 4GS. Do
not
attempt
to
operate
the
screw
compressor
with
any
oil
other
than these
two
specified above.
It
is
suggested
that
a
gallon
or
more
of
BOHN
SR-30
oil
be
obtained
and kept on
hand
at the
job
site. The
substitution
of
SUNISO
4GS oil, as
outlined
above,
will
result
in a
2%
to
4%
capacity
loss, and
no
reduction
in
input
K.W.
3.
COMPRESSOR REPAIRS (Internal) -
Contact
factory
or
an
authorized
BOHN
Service
Agency
if a
compressor
malfunction
is
suspected.
4. COMPRESSOR REPAIRS (External) -
Proper
operation
of
unloaded
start,
loading
, and
unloading
is
controlled
by solenoid
valves UL-1 ,
UL-2
and UL-3.
Any
of
thesethree (3) solenoid valves
may be repaired
or
replaced in the field,
as
required.
HIGH
PRESSURE
PORT

SLIDE
VALVE
UNLOADING
SYSTEM
1ne
tlonn
screw
compressor
capacity
control
system
for
infinite
modulation
consists
of
a
slide
valve and
hydraulic
piston
/
cylinder
operator
internal
to
the
compressor;
plus
three
hydraulic
solenoid
valves (UL-1,
UL-2
&
UL-3)
piped
externally.
The
slide
valve
forms
a
portion
of
the
chamber
wall in
which
the
rotors
turn;
thus,
its
position
with
respect
to
the
rotors
determines
the
effective
rotor
length
and
thereby
the
percent
of
full load
capacity
.
Upon
compressor
start-up
,
UL-3
is opened.
This
allows
oil pressure
to
act
upon
the
hydraulic
piston,
holding
it in
the
fully
unloaded
position
.
After
30 seconds,
during
which
time
full
oil
flow
is
established
to
all
bearings
surfaces,
UL-3
is
closed
.
At
this
point,
the
temperature
controller
is free
to
open
and close UL-1
or
UL-2
in
response
to
the
supply
water
temperature
.
The
slide
valve
will
move
to
the
left
(loading)
by
force
of
discharge
pressure
,
whenever
UL-1
opens
to
permit
flow
to
the
oil
return
(low
Load Unload
¢::J
c::>
Oil Pressure
Slide Valve
Oil
Pressure Lines
Screw
Rotor
pressure) line.
The
slide
valve
will
move
to
the
right
(unloading)
whenever
UL-2
opens
the
oil
supply
(high
pressure) line,
since
the
force
of
the
oil
exceeds
that
of
the
discharge
gas.
The
temperature
controller
sends a series
of
power
(energizing)
"
pulses
"
to
the
appropriate
solenoid
to
adjust
to
load
conditions
.
The
further
the
supply
water
temperature
is
from
the
controller
set
point,
the
longer
is
the
duration
of
the
pulses.
The
series
of
pulses
will
continue
until
the
controller
is satisfied. As
the
water
temperature
approaches
the
set
point
,
the
pulses
become
quite
brief
to
prevent
overshooting
the
set
point.
This
method
of
compressor
unloading
in
conjunction
with
supply
water
sensing
minimizes
action
/
reaction
lag
time
and
overshoot
resulting
in an
exceptionally
precise
and
stable
control
of
supply
water
temperature
.
UL-1
Oil
Return
Hydraulic
Piston
Oil
Supply
Vent
to
Suction
The
following
table
lists
solenoid
valve
position
for
all
three
operating
modes.
UL-1 UL-2 UL-3
Starting
Close Close
Open
Loading
Open
Close
Close
Unloading
Close Open Close
4
r
~
'-...../'

-
(.
"'-._./
LOW
AMBIENT
OPERATION
Due
to
the
wide
range
of
applications,
it
is
sometimes
necessary
to
operate
the
Air
Cooled
Packaged
Water
Chillers
at
ambients
below
summer
conditions.
Without
proper
control,
when
ambients
drop
below
60°
F.
the
pressure
differential
between
the
condenser
and
the
evaporator
is
below
the
level
to
insure
proper
thermal
expansion
valve
operation
. As a
result,
the
unit
may
cycle
on
low
pressure
control
with
the
possibility
of
evaporator
freezing.
Three
types
of
system
control
are
available
allowing
the
units
to
operate
at
the
ambients
indicated:
FAN
CYCLING
MEDIUM
AMBIENT
CONTROL
TO
30°
F.
(STANDARD
EQUIPMENT
-FACTORY
INSTALLED)
A
fan
cycling
control
is
standard
on
all
Air
Cooled
Packaged
Water
Chillers
to prov1de
prop
er
operating
head pressures, in
ambient
conditions
to 30° F.
This
is an
automatic
operation
in
which
the
condenser
fans
are
cycled
on
and
off
, as
required,
in
response
to
head
pressure.
With
two
compressors
running
,
three
fans
are
cycled
(in
sequence)
on
five-fan
units;
four
fans
on
six-fan
units
; and five
fans
on
seven-fan
units.
With
one
compressor
running,
all
but
the lead fan are
cycled
in
sequence, in
response
to head pressure.
This
arrangement
provides
positive
start-up
control
down
to
+30°
F.
by
delaying
the
condenser
fan
operation
until
a
predetermined
head
pressure
is
obtained.
GRAVITY
(Discharge) DAMPERS
LOW
AMBIENT
CONTROL
TO
oo
F.
(OPTIONAL
EQUIPMENT-
FACTORY
INSTALLED)
All
condenser
fans
are
equipped
with
gravity
dampers
mounted
on
the
fan
discharge
to
minimize
the
effect
of
prevailing
winds;
and
to
prevent
convection
drafts
up
through
the
condenser
coil
in
still
air.
All
compressors
are
enclosed
in
individual
insulated
housings.
An
auxiliary
heater
is
included
to
supplement
the
standard
crankcase
heater
;
the
temperature
within
the
compressor
compartment
is
thermostatically
controlled
.
The
standard
condenser
fan
cycling
package,
operating
in
con-
junction
with
the
discharge
dampers
,
will
maintain
suitable
head
pressure
down
to
oo F.
ambient.
A
90-second
time
delay
relay
provides
an
electrical
bypass
around
the
low
pressure
freezestat
to
prevent
nuisance
tnp-out
during
cold
start-up.
ACWC-SC
CONTROL
SETTINGS
PRESSURE
ACTUATED
LEGEND
FACTORY
SETTING
High
Pressure
Control
HP-1
Cut-In
300 PISG
(Manual
Reset) HP2 & HP3
Cut-Out
365 PSIG
Pumpdown
Control
PD1
Cut-In
55 PSIG
(Auto
Reset) PD2 & PD3
Cut-Out
35 PSIG
Fan
Cycling
Pressure
Control
2 Fan
Cell
Cut-In
(PSIG)
Cut-Out
(Adjustable)
FCP 1 280 170
FCP 2 295 180
3 Fan
Cell
FCP 1 260 160
FCP 2 275 175
FCP 3 290 215
4 Fan Cell
FCP 1 260 160
FCP 2 275 175
FCP3
285 210
FCP4
295 235
Low
Pressure Freeze
Control
LPF 1
Cut-Out
54 PSIG
(Manual
Reset)
--
LPF 2 & LPF-3
TEMPERATURE
ACTUATED
LEGEND
FACTORY
SETTING
Chiller
Low
Water
Temperature
Thermostat
T2
Cut-Out
37°
F.
Chiller
Water
Cycling
Thermostat
(Adjustable)
T1
Dial Set
At
55°
F.
Chiller
Heater
Thermostat
Included
With
Cut
-In 40°
F.
(Non-Adjustable
CBH1
Heater
Cut-Out
45°
F.
Oil
Temperature
Safety
Control
OTS
1
(Adjustable)
OTS
2
Cut-Out
240°
F.
Manual
Reset
OTS3
Capacity
Control
Thermostat
(Adj.)
Mode
Control
Position
T3
Dial Set
At
44°
F.
UNIT
OPERATING
LIMITATIONS
1.
Maximum
ambient
air
to
condenser
is 115° F. (60
Hertz
operation).
2.
Maximum
allowable
cooler
water
pressure
is 150 PSIG.
3.
Maximum
allowable
water
temperature
to
cooler
is 75°
F.
4.
Units
must
not
have leaving
water
temperatures
of
42°
F.
or
lower
unless
used
with
a
glycol
solution.
5.
Unit
must
be
allowed
to
pumpdown
at the
end
of
each
operating
cycle
(except
on
safety
control
shutdown).
5

KEY
TO
WIRING
DIAGRAM
INDEXING
SYSTEM
The
wiring
diagrams
and
sequence
instructions
on
the
following
pages have been devised
to
simplify
the
understanding
and
tracing
of
circuit
theory.
The
following
key
shows
how
the
indexing
system can be used.
12
Line
number
on
wiring
diagram
[12]
Line
number
in
text
(RS)
Component
identification
symbol
in
text
(Relay #5)
~
Normally
open
contact-
line
number
location
~
Normally
closed
contact-
line
number
location
@
Holding
coil
-
line
number
location
&
Note
number
EXAMPLE
30
~
§] §]
SEQUENCE
OF
OPERATION
MODELS
ACWC
160
To
200
SC
The
following
sequence
of
operation
is
typical
for
the
ACWC
160
to
200
SC
(see Pages 10
and
11
for
typical
wiring
diagram).
Refer
to
the
wiring
diagram
furnished
with
unit
for
specific
information.
Control
Identification
Symbol
Circuit
Line
Number
Important Notel
The
compressor
crankcase
heater
must
be
energized
and remain
active
for
a
minimum
fa
24
hours
prior
to
unit
start-up.
PRELIMINARY
SEQUENCE
Place
control
circuit
"ON-OFF"
switches
(SW1
thru
SW4) in
the
"OFF"
position,
and set
the
staging
thermostat
(T1)
to
its
highest
temperature.
Activate
the
115
volt
electrical
service
to
terminals
#2 and #4
[1
and
3] on
terminal
board
(TEAS)
to
distribute
power
to
the
control
circuit
up
to
the
control
circuit
switches.
Crankcase
heater relay
contacts
(R19) (3]. (R20)
[5].
and
(R21) [7] are
closed
and are
supplying
power
to
the
compressor
crankcase
heaters.
Power
is also
supplied
to
the
chiller
barrel
heater
(CBH1)
(11].
the
receiver heaters (RH1,
2,
3) (8,
9,
10]
(optional),
and
the
low
ambient
crankcase
heaters
(SCH1,
2,
3)
[3,
5,
7]
(optional).
Close
the
main
power
disconnect
switch.
Check
to
see
that
the
red
indicating
light
on
the
phase loss
monitor
(PLM1) is
lit
(NOTE: There
will be two phase loss monitors, (PLM1) and (PLM2),
on
208-230 volt
models).
This
light
must
be on
to
indicate
proper
phase
rotation
for
the
compressor(s)
. If
the
light
is
not
on,
the
main
control
circuit
to
the
compressors
will
not
be
energized.
Reverse
any
two
phase legs
at
the
Main Incoming Power Terminal Block.
DO
NOT
reverse
the
leads on
the
phase loss
monitor,
for
this
will
allow
the
compressor
to
run
backwards,
causing
severe damage, and WILL VOID
THE
COMPRESSOR WARRANTEE!
Start-up
the
chilled
water
pump.
The
water
flow
is
confirmed
when
the
water
flow
switch
completes
an
electrical
circuit
across
terminals
#12 (58] and #13 [60]
of
terminal
board (TEAS).
Terminals
#14 [61]
6
@@&
~
See
Note
Number
3
The
holding
coil
for
the
first
contact
shown
on
this
line
(reading
from
left
to
right)
can
be
found
on
line
#44;
the
holding
coil
for
the
second
contact
can be
found
on
line #74.
The
contacts
for
the
holding
coil
shown
on
this
line
can
be
found
on
lines 66, 23, and 54.
The
contact
on
line
23 is
normally
closed
.
This
is
the
number
which
identifies
the
line
of
wiring
shown
at
the
left.
and #15 [63]
provide
an
interlock
for
the
water
pump
starter(s);
either
contact
(R14). (R16),
or
(R18) [62]
will
close
any
time
a
compressor
is
running.
Set
the
staging
thermostat
(T1)
to
the
design range
of
operation
(e.g.
54°
F.
return
water). Set
the
capacity
control
thermostat
(T3)
to
the
design
range
of
operation
(e.g. 44°
F.
supply
water).
Place
the
four
(4)
control
circuit
switches
(SW1-SW4) in
the
"ON"
position
,
thus
energizing
the
balance
of
the
control
circuit.
The
system will
be
In
the "Time-In" mode for five minutes before any
compressor will start.
STAGE 1
LOADING
Upon
demand
for
cooling,
the
first
step
of
the
staging
thermostat
(T1)
will
close
,
energizing
relay (TD10) (63] and
staging
relay (R1)
[62].
closing
(R1)
contacts
7-4 [22]. 8-5 [25].
and
9-6 (16]. If
the
safety
controls
and
switches
are closed,
the
control
circuit
[16]
for
compressor
No.1
and
liquid
line
solenoid
(SOL
1) (25]
will
energize,
allowing
the
compressor
to
start. Fan
contactor
(C13) (21]
will
also
close,
bringing
power
to
the
line
side
of
fan
cycling
pressure
controls
(FCP1) and (FCP2) (see
Power
Wiring
Diagram-
Pages 16
and 17). Fan
motor
#1
will
start
as
soon
as
the
head
pressure
reaches
the
"cut-in"
setting
of
(FCP1
).
NOTE: ALL FAN
MOTORS
ARE
CONTROLELD
BY
THEIR OWN
FAN
CYCLING
CONTROL
AND
WILL
CUT
IN
AT
DIFFERENT HEAD PRESSURES.
Relay (R19) [20]
contact
7-1
[3] opens,
de-energizing
compressor#1
crankcase
heater(s). Relay (R14) (19]
contact
8-5 (24] closes,
energizing
(TD7) [23].
This
will
force
compressor
#1
to
run
for
five
minutes.
COMPRESSOR
#2
CANNOT
BE
STARTED
UNTIL
(TD7)
TIMES
OUT.
Time
delay relay (TD1 0) [63]
contact
C-NC
(26]
holds
the
compressor
in an
unloaded
condition
for
30 seconds. When relay (TD10)
times
out,
it
will
energize
relay (R4) [27].
closing
contacts
9-6 [71] and 7-4
[74].
This
allows
the
capacity
control
thermostat
(T3)
to
energize
solenoid
valve
(UL
1-1) [71].
loading
the
compressor;
or
to
energize
solenoid
valve (UL2-1) [74].
unloading
the
compressor.
,
-~
\....__./

,.
-......__/
Relay (R14) (19]
contact
7-4 [62] closes,
which
completes
the
interlock
circuit
for
the
water
circulating
pump.
~TAGE! Z
LOADINu
Upon
a
further
increase in return watertemperature, the second step
of
the
staging
thermostat
(T1) will close. If the
lock-out
timer
(TD5)
and
the
lock-in
timer
(TD7) [64] have
timed
out, relays (R2) [64] and
(TD11) [65]
will
be energized,
closing
(R2)
contacts
9-6 [32]. 8-5
[40]. and 7-4 [37]. If the safety
controls
and switches are closed,
the
control
circuit
[32]
for
compressor
#2
and
liquid
line
solenoid
(SOL2) [40] will energize,
allowing
the
compressor
to start.
Relay (R20) [36]
contact
7-1
[5] opens,
de-energizing
crankcase
heater(s).
Contact
9-6 [44] closes,
energizing
fan
contactor
(C14)
(44].
bringing
power
to
the
line
side
of
the
balance
of
the
fan
cycling
pressure
controls
(see
power
wiring
diagrams)
. Fan
motor
#3
will
start
as
soon as
the
head pressure reaches
the
"cut-in"
setting
of
(FCP3).
Relay (R16) [35]
contact
8-5 [39] closes,
energizing
(TD8) (38].
This
will
force
compressor
#2
to run
for
five minutes. Compressor
#3
cannot be started until (TDS) times out.
Time
delay
relay (TD11) [65]
contact
C-NC
(41]
holds
compressor#2
in an
unloaded
condition
for
30 seconds. When (TD11) times out,
it
will energize (R5) (42].
closing
contacts
9-6 (72] and 7-4 (75].
This
allows
the
capacity
control
thermostat
(T3)
to
energize
solenoid
valve
(UL
1-2) [72].
loading
the
compressor;
or
to
energize
solenoid
valve (UL2-2) [75].
unloading
the compressor.
STAGE 3
LOADING
Upon
a
further
increase in return watertemperature, the
third
step
of
the
staging
thermostat
(T1)
will
close. Ifthe
lock-out
timer
(TD6) and
the
lock-in
timer
(TD8) (66] have
timed
out
, relays (R3) (66]. (R7)
(68].
and
(TD12) [67] will be energized. Relay (R3)
contacts
9-6 [48].
7-4 [53]. and 8-5 [56] close. If
the
safety
controls
and
switches
are
closed, the
control
circuit
[48]
for
compressor
#3
and
liquid
line
solenoid
(SOL3) [56] will energize,
allowing
the
compressor
to
start.
Relay (R21) [52] energizes,
opening
contact
7-1
[7],
de-energizing
compressor
#3
crankcase
heater(s). Relay (R18) (51]
contact
8-5
[55] closes,
energizing
(TD9) [54].
This
will
force
compressor
#3
to
run
for
five minutes.
Relay (R7)
contact
9-6 [70] closes,
energizing
solenoid
valve
(UL
1-
1).
thus
locking
compressor
#1
in
the
fully
loaded position. Relay
(R7)
contacts
8-2 [71] and 7-1 [74]
open
to
disconnect
the
capacity
control
thermostat
(T3)
from
compressor
#1
capacity
control
solenoid valves.
Time
delay relay (TD12) [67]
contact
C-NC
[57]
holds
compressor
#3
in an
unloaded
condition
for
30 seconds. When (TD12)
times
out
,
it
will
energize relay (R6) [58].
closing
contacts
9-6 [73] and 7-4 [76].
This allowsthe
capacity
control
thermostat
(T3) to energizesolenoid
valve
(UL
1-3) [73].
loading
the
compressor
;
or
to energize solenoid
valve (UL2-3) [76].
unloading
the compressor.
Compressor
#1
is
fully
loaded.
Compressors
#2
and
#3
are being
capacity-modulated.
7
PUMPDOWN
SEQUENCE
STAGE 3
PUMPDOWN
A
dccrca:>e
in
return
water
temperature
will
t;iiU>Se
the
third
step
or
the
staging
thermostat
(T1)
to
open,
thereby
de-energizing
staging
relay (R3),
opening
contacts
8-5, 9-6, and 7-4.
Liquid
line
solenoid
(SOL3)
will
de-energize,
stopping
the
flow
of
refrigerant
to
chiller
circuit
#3. The
compressor
will
continue
to
run
until
the
chiller
circuit
has been cleared
of
refrigerant
and the
suction
pressure is
approximately
35 PSIG.
Low
pressure
control
(LP3)
contact
will
then
open,
de-energizing
compressor
contactors
(C5) (49] and (C6)
[50].
stopping
compressor
#3; and
de-energizing
relays (R18) and
(R21
).Relay (R18)
N.C
.
(normally
closed)
contact
2-8 (54] energizes
lock-out
timer
(TD6).
preventing
compressor
#3
re-start
for
.five
minutes. Relay (R21) energizes
the
compressor
crankcase heater(s).
Staging
thermostat
(T1) also de-energizes relay (R7).
opening
contact
9-6, releasing
compressor
#1
from
continuous
full-load
operation.
Relay (R7)
contacts
8-2 and
7-1
close,
allowing
the
capacity
control
thermostat
(T3) to operate
capacity
control
solenoid
valves (UL1-1) and (UL2-1)
as
required.
STAGE 2
PUMPDOWN
A
further
decrease in return
water
temperature
will
de-energize
staging
relay (R2),
closing
liquid
line
solenoid
(SOL2). When
chiller
circuit
#2
has
pumped
out,
low
pressure
control
(LP2) opens,
stopping
compressor
#2
; and
de-energizing
relays (R16) and (R20).
Relay (R16) N.C.
contact
(8-2) [38] energizes
lock-out
timer
(TD5),
preventing
compressor
#2
re-start
for
five minutes. Relay (R20) (36]
energizes
compressor#2
crankcaseheater(s); and also de-energizes
fan
contactor
(C14) (44].
stopping
the
fan
motor(s)
servicing the
two-circuit
condenser
slab.
STAGE 1
PUMPDOWN
Step 1
of
the staging
thermostat
(T1) will
open
when
the
return
water
temperature
is reduced to
the
set
point
.
This
de-energizes
staging
relay
(R1
),
closing
liquid
line
solenoid
(SOL
1),
stopping
refrigerant
flow
to
chiller
circuit
#1.
Compressor#1
continues
to
run
until
chiller
circuit
#1
pressure is
down
to
the
low pressure
control
(LP1) set
point.
The
(LP1)
contact
opens
,
de-energizing
compressor
contac
-
tors
(C1) (17]. (C2) (18],
and
fan
contactor
(C13) [21].
stopping
compressor
#1
and the remaining fan
motor(s).
Relay (R14) N.C.
contact
8-2 (23] energizes
lock-out
timer
(TD4),
preventing
compressor
#1
re-start
for
five
minutes
; relay (R14)
contact
7-4 (62] opens,
removing
the
circulating
pump
starter
interlock
. Relay (R19)
de-energizes,
closing
contacts
7-1
[3].
energizing
compressor
#1
crankcase heater(s).
SAFETY
CONTROLS
Each
refrigerant
circuit
is
protected
by seven standard safety
controls,
and one
optional
safety
control.
1.
High Pressure (HP)
2.
Low
Pressure Freeze (LPF)
3. High
Discharge
Temperature
(OTS)
4.
Low
Oil
Temperature
(LOT)
5.
Compressor
Solid
State
Module
(CSTM)
6.
Low
Water
Temperature
(T2)
7.
Low
Pressure (LP)
8.
Compressor
Starter Overloads (OLH)
(Optional)
If any
of
these devices
should
open
due
to
abnormal
conditions,
the
compressor
will
automatically
stop. All
controls
must
be
manually
reset,
except
Low
Oil
Temperature
(LOT),
Low
Pressure (LP) and
Compressor
Solid
State
Module
(CSTM),
which
resets itself
after
a
two
minute
bleed-down
period. The
compressor
motor
windings
are
also
equipped
with
a
thermal
protector,
automatic
reset,
which
is
not
shown
on the
wiring
diagram.

SEQUENCE
OF
OPERATION
MODEL
ACWC
215 SC
The
following
sequence
of
operation
is
typica
l
for
the
ACWC
215 SC
(see pages 12
to
15
for
typical
wiring
diagram
).
Refer
to
the
wiring
diagram
furnished
with
unit
for
specific
information.
( )
Control
Identification
Symbol
[ ]
Circuit
Line
Number
Important Notel
The
compressor
crankcase
heater
must
be
energized
and remain
active
a
minimum
of
24
hours
prior
to
unit
start.
PRELIMINARY SEQUENCE
Place
control
circuit
"
ON-OFF
"
switches
(
SW1
thru
SW5) in
the
"OFF"
position
, and set
the
staging
thermostat
(T1
)
to
its
highest
temperature.
Activate
the
115
volt
electrical
service
to
terminals
#2 and #4 [1 and
3] on
terminal
board
(TER5)
to
distribute
power
to
the
control
circu
it
up
to
the
control
ci
rcuit
switches.
Crankcase
heater
relays (R20) [3],
(R21) (5], (R22)
[8],
and
(R23) (10] are
closed
and are
supp
lying
power
to
the
compressor
crankcase
heaters.
Power
is also
supplied
to
the
chiller
barrel
heaters
(CBH1)
[17] and
(CBH2)
[20],
the
receiver heaters (RH1 , 2, 3,
4)
(12, 13, 15, 16]
(optional)
,and
the
low
ambient
crankcase
heaters (SCH1 , 2, 3, 4) [3,
5,
8, 10]
(optional)
.
Close
the
main
power
disconnect
switch.
Check
to
see
that
the
red
indicating
lights
on
the
phase loss
monitors
(PLM1 ) and (PLM2) are
lit. These
lights
must
be on
to
indicate
proper
phase
rotation
for
the
compressor(s).
If
the
lights
are
not
on,
the
main
control
circuit
to
the
compressors
will
not
be
energized
. Reverse
any
two
phase legs at
the
main Incoming power terminal block. DO
NOT
reverse
the
leads
of
the
phase loss
monitor
,
fo
r
this
will
allow
the
compressor
to
run
backwards,
causing
seve
re
damage
,
and
WILL
VOID
THE
COMPRESSOR WARRANTEE!
Start-up
the
chilled
water
pump.
The
water
flow
is
confirmed
when
the
waterflow
switch
completes
an
electrical
circuit
across
terminals
#12 [89] and #13 [91]
of
terminal
board (TER5).
Terminals
#14 [92]
and #15 (94]
provide
an
interlock
for
the
water
pump
starter(s);
either
contact
(R11 ), (R12), (R13),
or
(R14) [95]
will
close
any
time
a
compressor
is
running
.
Set
the
staging
thermostat
(T1)
to
the
design
range
of
operation
(e
.g.
54° F.
return
water).
Set
the
capacity
contro
l
thermostat
(T3)
to
the
design
range
of
operation
(e.g. 44° F.
supply
water).
Place
the
five
control
circuit
switches
(SW1
thru
SW5) in
the
"
ON
"
position
,
thus
energizing
the
balance
of
the
control
circuit.
The
system will
be
in
the "time-In" mode for five minutes before any
compressor will start.
STAGE 1 LOADING
Upon
demand
for
cooling
,
the
first
step
of
the
staging
thermostat
(T1)
will
close,
energizing
relay (TD15) [94] and
staging
relay (R1)
(93],
closing
(R1)
contacts
7-4 [32], 8-5 [35], and 9-6 [26].
If
the
safety
controls
and
switches
are
closed
,
the
control
circuit
[26]
for
compressor
#1
and
liquid
line
solenoid
(SOL
1) (35]
will
energize
,
allowing
the
compressor
to
start.
Relay (R20) (30]
contact
9-6 (39] closes,
energizing
fan
contactor
(C13) (39],
bringing
power
to
the
line
side
of
fan
cycling
pressure
controls
(FCP1)
thru
(FCP6) (see
Power
Wiring
Wiring
Diagram
on
Pages 16
and
17). Fan
motor
#1
will
start
as
soon
as
the
head
pressure reaches
the
"
cut-in
"
setting
of
(FCP1 ).
NOTE: ALL FAN
MOTORS
ARE CONTROLLED
BY
THEIR OWN
FAN
CYCLING
CONTROL
AND
WILL
CUT
IN
AT
DIFFERENT HEAD PRESSURES.
Relay (R20)
contact
7-1
(3] opens,
de-energizing
compressor
#1
crankcase
heater(s). Relay (R11) [29]
contact
8-5 [34] closes,
energizing
(TD9) [33].
This
will
force
compressor
#1
to
run
for
five
minutes.
COMPRESSOR #3 (Stage 2)
CANNOT
BE
STARTED
UNTIL
(TD9) TIMES OUT.
Time
delay relay (TD15) ]94]
contact
C-NC
[36]
holds
the
compressor
in an
unloaded
condition
for
30
seconds
. When relay (TD15)
times
out,
it
will
energize
relay (R5) (37],
closing
contacts
9-6
[1
06] and 7-4
(112].
This
allows
the
capacity
control
thermostat
(T3)
to
energize
solenoid
valve
(UL
1-1)
[1
06],
loading
the
compressor
;
or
to
energize
solenoid
valve (UL2-1)
[1
12],
unloading
the
compressor.
Relay (R11 ) [29]
contact
7-4
[95]
closes,
wh
i
ch
completes
the
interlock
circuit
for
the
water
ci
rculating
pump
.
STAGING
2 LOADING
Upon
a
further
increase in return
water
temperature
,
the
second
step
of
the
staging
thermostat
(T1)
will
close. If
the
lock-in
timer
(TD9)
[95] and
lock
-
out
timer
(TD7) [95] have
timed
out
, relays (R2) [95]
and (TD16) [96]
will
beenergized,
closing
(R2)
contacts
9-6 [62], 7-4
(67], and 8-5 [70]. If
the
safety
controls
and
switches
are closed,
the
control
circuit
[62]
for
compressor
#3 and
liquid
line
solenoid
(SOL3) [70]
will
energize
,
allow
ing
the
compressorto
start.
Relay (R22) [66]
contact
7-1
[8]
opens
,
de-energizing
crankcase
heater
(s).
Contact
9-6 [74] closes,
energizing
fan
contactor
(C14)
[74],
bringing
power
to
the
line
side
of
fan
cycling
pressure
controls
(FCP7)
thru
(FCP12) (see
power
wiring
diagrams)
. Fan
motor#4
will
start
as
soon
as
the
head pressure reaches
the
"
cut-in
"
setting
of
(FCP7).
Relay (R13) [65]
contact
8-5 [69] closes,
energizing
(TD11) [68].
This
will
fo
rce
compressor
#3
to
run for five
minutes
.Compressor#2
cannot be started until TD11) times out.
Time
delay
relay (TD16) [96]
contact
C-NC
[71]
holds
compressor
#3 in an
unloaded
condition
for
30
seconds
.When (TD16)
times
out
,
it
will
energize
(R7) [72],
closing
contacts
9-6
[1
08] and 7-4 [113].
This
allows
the
capacity
control
thermostat
(T3)
to
energize
solenoid
valve
(UL
1-3) [108],
loading
the
compressor
;
or
to
energize
solenoid
valve (UL2-3) [113],
unload
ing
the
compressor.
STAGE 3 LOADING
Upon
a
further
inc
rease in
return
water
temperature,
the
th
ird step
of
the
staging
thermostat
(T1)
will
close
. If
lock-in
timer
(TD11) and
lock-out
timer
(TD6) [66] have
timed
out
, relays (R3) [97], (R9) [99],
and (TD17) (98]
wil
l be
energized
. Relay (R3)
contacts
9-6 [45], 8-5
and 7-4 [50]
close
. If
the
safety
controls
and
switches
are
closed
,
the
control
circuit
[45]
for
compressor
#2 and
liquid
line
solenoid
(SOL2) [53]
will
energize
,
allowing
the
compressor
to
start.
Relay (R21) [49] energizes,
opening
contact
7-1
[5],
de-energizing
compressor
#2
crankcase
heater(s). Relay (R12) [48]
contact
8-5
[52] closes,
energizing
(TD1
0)
[51].
This
will
force
compressor#2
to
run
for
five
minutes
. Compressor #4 cannot be started until (TD10)
times out.
Relay (R9)
contact
9-6
[1
05] closes,
energizing
solenoid
valve
(UL
1-
1),
thus
locking
compressor
#1
in
the
fully
loaded
position
. Relay
(R9)
contacts
8-2 [106] and
7-1
[112]
open
to
disconnect
the
capacity
control
thermostat
(T3)
from
compressor
#1
capacity
control
solenoid
valves.
Time
delay
relay (TD17) [98]
contact
[54]
holds
compressor#2
in an
unloaded
condition
for
30
seconds.
When (TD17)
times
out,
it
will
energize
relay (R6) [55],
closing
contacts
9-6 [109] and 7-4 [114].
This
allows
the
capacity
control
thermostat
(T3)
to
energize
solenoid
valve
(UL
1·2)
(1
09], loading
the
compressor;
or
to
energize
solenoid
valve (UL2-2) (114],
unloading
the
compressor.
Compressor
#1
is
full
loaded
.
Compressors
#2 and #3 are
being
capacity-modulated
.
STAGE 4 LOADING
Upon
a
further
increase in return
water
temperature,
the
fourth
step
of
the
staging
thermostat
(T1)
will
close.
If
the
lock-in
timer
(TD1 0)
and
the
lock-out
timer
(TD8)
[1
00] have
timed
out,
relays (R4)
[1
00],
(R1
0)
(1
02], and (TD18)
[1
01]
will
be
energized
. Relay (R4)
contacts
9-6 [79], 7-4 (84], and 8-5 [87] close. If
the
safety
controls
and
switches
are
closed
,
the
control
circuit
[79]
for
compressor
#4 and
liquid
line
solenoid
(SOL4) [87]
will
energize
,
allowing
the
com
pres-
sor
to
start.
Relay (R23) [83] energizes,
opening
contact
7-1
(7],
de-energizing
compressor
#4
crankcase
heater(s). Relay (R14) [82]
contact
8-5
(86] closes,
energizing
(TD12).
This
will
force
compressor
#4
to
run
for
five
minutes
.
Relay
(R1
0)
contact
9-6
[1
07] closes,
energizing
solenoid
valve
(UL1-3
,
thus
locking
compressor
#3 in
the
fully
loaded
position
.
Relay
(R1
0)
contacts
8-2
(1
08] and
7-1
[113]
open
to
disconnect
the
capacity
control
thermostat
(T3)
from
compressor
#3
capacity
8
control
solenoid
valves.
~
\
\....__/
~
~

'-.._/
r
~
Time
delay relay (TD18) (101]
contact
C-NC
(88]
holds
compressor
#4
in
an
unloaded
condition
for30
seconds.When (TD18)
times
out,
it
will
energize relay (R8) [89].
closing
contacts
9-6
[11
0) and 7:4
(116].
Thio
o.llowo
tho
capacity
control
thormootat
(T'l)
to
..
norgi:zo
solenoid
valve
(UL
1-4)
[11
OJ,
loading
the
compressor
;
or
to
energize
solenoid (UL2-4) [115),
unloading
the
compressor
.
Compressors
#1
and #3 are
fully
loaded.
Compressors
#2
and #4 are being capacity-modulated.
PUMPDOWN SEQUENCE
STAGE 4
PUMPDOWN
A decrease in return
water
temperature will cause the
fourth
step of
the staging
thermostat
(T1)
to
open,
thereby
de-energzing staging
relay (R4),
opening
contacts
8-5, 9-6, and 7-4.
Liquid
line solenoid
(SOL4) will de-energize,
stopping
the
flow
of refrigerant
to
chiller
circuit
#4.
The
compressor
will
continue
to
run
until
the
chiller
circuit
has been cleared
of
refrigerant and the suction pressure is
approximately
35
PSIG.
Low
pressure
control
(LP4)
contact
will
then open,
de-energizing
compressorcontactors
(C7) [80) and (C8)
[81),
stopping
compressor
#4
; and
de-energizing
relays (R14) and
(R23).Relay (R14) N.C.
(normally
closed)
contact
2-8 [85] energizes
lock-out
timer
(TD8), preventing
compressor
#4
re-start
for
five
minutes. Relay (R23) energizes
compressor#4
crankcase heater(s).
Staging
thermostat
(T1) also de-energizes relay (R10),
opening
contact
9-6, releasing
compressor
#3
from
continuous
full-load
operation. Relay
(R1
0)
contacts
8-2 and
7-1
close,
allowing
capacity
control
thermostat
(T3)
to
operate
capacity
control
solenoid
valves
(UL1-3) and (UL2-3)
as
required.
STAGE 3 PUMPDOWN
A
further
decrease in return
water
temperature
will
de-energize
staging relay (R3),
closing
liquid
line solenoid (SOL2). When
chiller
circuit
#2
low-side
has
pumped
out
,
low
pressure
control
(LP2)
opens,
stopping
compressor
#2;and de-energizing relays (R12) and
(R21
). Relay (R12) N.C.
contact
2-9 [51) energizes
lock-out
timer
(TD6), preventing
compressor
#2
re-start
for
five
minutes
. Relay
(R21) energizes
compressor
#2
crankcase heater(s).
Staging
thermostat
(T1) also de-energizes relay (R9),
opening
contact
9-6, releasing
compressor
#1
from
continuous
full-load
operation. Relay (R9)
contacts
8-2 and
7-1
close,
allowing
the
capacity
control
thermostat (T3)
to
operatecapacity
control
solenoid
valves
(UL
1-1) and (UL2-1)
as
required.
STAGE 2 PUMPDOWN
A
further
decrease in return
water
temperature
will
de-energize
staging relay (R2),
closing
liquid
line solenoid (SOL3). When
chiller
circuit
#3
has
pumped
out,
low
pressure
control
(LP3) opens,
stopping
compressor#3;
and de-energizing relays (R13) and (R22).
Relay (R13) N.C.
contact
2-8 [68) energizes
lock-out
timer
(TD7),
preventing
compressor
#3 re-start
for
five
minutes
. Relay (R22)
energizes
compressor
#3 crankcaseheater(s); and alsode-energizes
fan
contactor
(C14) [74).
stopping
the fan motor(s) on the
"lag"
half
nf
thA
condAn!':Ar
!':lab
.
STAGE 1 PUMPDOWN
Step1
of
the
staging
thermostat
(T1) will open when the return water
temperature
is reduced
to
the set
point
.
This
de-energizes staging
relay
(R1
),
closing
liquid
line
solenoid
(SOL
1
),
stopping
refrigerant
flow
to
chiller
circuit
#1
.Compressor#1
continues
to
run
until
chiller
circuit
#1
pressure is
down
to
the
low
pressure
control
(LP1) set
point.
The
(LP1)
contact
opens, de-energizing
compressor
contac-
tors
(C1) (27) and (C2) [28), and relay (R20),
stopping
compressor
#1
. Relay (R20) de-energizes fan
contactor
(C13),
stopping
the
remainingfan motor(s); and alsoenergizes compressor
#1
crankcase
heater(s).
The
(LP1)
contact
also de-energizes relay
(R11
).
Relay
(R11) N.
C.
contact
2-8 [33) energizes
lock-out
timer
(TDS), prevent-
ing
compressor
#1
re-start
for
five minutes. Relay (R11)
contact
7-4
[95) opens, removing the
circulating
pump
starter
interlock
.
SAFETY CONTROLS
Each
refrigerant
circuit
is protected
by
seven standard safety
controls
, and one
optional
safety control.
1.
High
Pressure
(HPO)
2.
Low
Pressure Freeze (LPF)
3.
High Discharge Temperature (OTS)
4.
Low
Oil Temperature (LOT)
5.
Compressor
Solid State
Module
(CSTM)
6.
Low
Water Temperature (T2)
7.
Low
Pressure (LP)
8.
Compressor
Starter Overloads (OLH) (optional)
If
any
of
these devices
should
open
due
to
abnormal
conditions
, the
compressor
will
automatically
stop. All
controls
must be
manually
reset,
except
Low
Oil
Temper-
ature (LOT),
Low
Pressure (LP) and
Compressor
Solid
State
Module
(CSTM),
which
resets itself
after
a
two
minute
bleed-down
period.
The
compressor
motor
wind-
ingsarealso
equipped
with
a
thermal
protector,
automatic
reset,
which
is
not
shown on the
wiring
diagram.
STAR-DELTA STARTING
OPEN
TRANSITION
·The
following
starting sequenceappliesto the
power
wiring diagrams
on Page 17
as
well
as
the
control
wiring
on Pages 10
thru
15
. Detail
"A"
on Page 10 is
typical
of
all screw
compressor
star-deltastart, and
will
be used
as
an example.
Staging
relay (R1)
contact
9-6 [16) closes,
energizing
star
contactor
(S1)
[168)
and the 5 second
transition
timer
(TD1) [16A). The (S1)
power
contacts
close,
tying
the
center
legs
of
the
motor
windings
together
into
the
"star"
(wye)
configuration.
The
(S1) N.
C.
(normally
closed)
auxiliary
contact
[18] opens
to
prevent
contactor
(C2)
from
energizing.
The
(S1) N.O.
(normally
open)
auxiliary
contact
[17)
closes,
energizing
(C1) [17].
The
(C1)
power
contacts
close,
applying
power
to
the
motor
.The (C1) N.O.
auxiliary
contact
closes,
9
locking
(C1) in the energized
position
.
The
compressor
operates in the star
mode
until
(TD1) times
out
(5
seconds) at
which
time
(TD1)
contact
(168) opens, de-energizing
(S1
).
The
(S1) N.C.
contact
[18) closes,
energizing
contactor
(C2)
[18),
closing
(C2)
power
contacts,
thereby
completing
the Delta
wiring
configuration.
(C2) N.
C.
auxiliary
contact
[16A] opens,
preventing (S1)
from
energizing
until
the next starting sequence.
There
is an
instant
of
time
(the
"open
transition") between the
opening
of
(S1)
power
contacts
and
the
closing
of
(C2)
power
contacts,
in
which
power
across the
motor
windings
is
interrupted
.

0
~
..
Rrt-
OPTIOHAlr----
1~~
C8FI WHITE
DESIGNATIONS :
0 HOLDING COILS WITH
LINE
NO
.
2 1
~
I :
OPPrfiOfll
7
R.z2~
Ill
PCHI
zoow
142
WHITE
•
L_y
_
____j
I
..::=--~oPT
12GA
4 4 BLACK
..--.....
108-
RED
7
Rl9
t
112
I
~~
!lOW
I~
.
12GA
CB2
I =
~
POWER
SUPPLY
115V/60'\,/IIf
0 NORMALLY CLOSED CONTACTS WITH
LINE
NO
.
0
NORIIIALL'f
Of>EN
CONTACTS WITH
LINE
NO
.
6 NOTE WITH LINE
NO
.
TYPICAL.
FOR
UGHT
OPTION
ON
ALARM CIRCUITS
1,2
8 3.
(NOT
SUPPLIED WITH
BELL
OPTION.)
STAR
DELTA
STARTING
!I SEC
DETAIL
"A"
)
~222
,I
113
PCH2
zoow
I
.-=---~oPT
I BLUE 7 RZO
114
I~
!lOW
I~
.
I l
~22
61
'''
~-;--~
0
~
YEUOW 7
R21
r-c=
-~_j
116
~;~~OPT.
OPTIONAL
""~
l
~
-
-109
REO
~
201
RHTI
204
RH
I =
1!31
WHITE
CBI rT
t::tl.)
o- BLUE
_R;_I
202
RHTZ 20!1
RH2
I
12
GA
I
-,,PC
..
::.
I
I
YELLOW.~
203
RHT3
206
RH
3 I I
RHPC ===::::J
1...---o~
110
BlACk
OPTIONAL TH
CBH
I
IH
~H~:E
0-r--
207
BLACK
~--;~
R22\+--------------_.
I 8
Co
_ _
r--r==e-
:-------"l
OPTIONAL
r _j=PUoll I
or
~
I
I I
':JT
OPTIONAL ! :
: ' 1
~:·o
1J
J J! CST
•.
LEi
r
"cd
Ii!
:vuu
L
A--
y
---
---
,J
I
Tl
,...
f~
1
i..J
i
LPFI
2
14
HPI
118
Lon
215
ors1
216
11
~~
119
R
LPI
v 9
Rl
6
120
I!Jr
c;7
HTR
12ovl
145
f"'T
.1
L-
~
M
R-
.0.
8 R
r:;-
R
C:,
8
Ml
M2
-
1/S
2 ':L7~
i·d·
T2
Tl
273 9
RI4
6
~
LPFI
GFI
~SEE
21.3
r-~sr-
S~~;.N
OETAIL"AMQ
[
~
WIRED
WHEN
SUPPLIED J
~
~PfiO"HAL
~HI
OLH2
~3
r
~-'-----~
-....,-2
10 ...,
211...,212
~
.._
__
_.!R~E£_0
----<,::SW;:._;,'
1----Q
117
-e-
L--e-
WHITE
7lJI
4 RED
C).
W
224
~
I COMPRESSOR CIRCUIT I 2
225
A TOT r l
I 4 8
HGS
I
8f1
5 7
T07
1
I
SJ,._
~~
5
5111
~N1
8
Rl9
5
SOLI
~TI-o2
146
I
~
226
121
UL3-I
TO
IO>~H$)C'-------------:<!?;-------<>-1...o--1
~
30
SEC
RED 122
NO
227
R4
}------'
10-
STAR
DELTA
STARTING IIT - - 0
~OPTIONAL
OPTIONAL
~
ALARM
CIRCUI
CIRCUIT
2
!!iSEC
DETAIL
"B"
9 BLUE !
~
~
:I I I : I cSTw'
i9
oSEc
wmE
LP'Il:
2
-,-,-,.Jy
J25-UiT-,-,-,-0-iS~Y~
34
11
Tl
-:i
R
LP2
y9
R2
6
Nl
"=Z._
HTR
120vl
147
I [
L-
c;
N
R-
c:!r.-
8 R
~-
Y R itt B
Ml
tl2
128
~
235
r
~~~
r
127
T2
Tl
[
GF
2
9~~~6
~
SEE
LPF
2
J:
-
~g-
S~~.:N
DETAIL
~81:::":\
II
'--,~,~,--+<,
_,.,
I
~IRED
WHEN
SUPPLIED
~
OPTiONAL
0LH4
OLH5 OLH6
[
Co::\'---
--~
228 229
230
~
123
BLUE SW3 Q
-
~
COMPRESSOR CIRCUIT 2
rlJ"'
:
:::E
A
T0
5 8
w;;:
6
~
8
TDB
8
R2
5 75
N~N
T
R20
128 SOL 2 148
I
NC
244
8 5 129
UL3-2
~30
SEC
BLUE
NO
245
R5J-----..J
1----
l.--
_~.-
'
- )
~
~
li!m
~
§]
~
ETI!3
~
13*91821
~'i!il·~
~
8
®
@
®
®
®
®
®
@
@
@
@).§)
€X§
@)
®
l9
@)
1!3
8
~
~
®§
00
@
&6
&
&
&
&
&
&,
&
&
l
~
u
.
§
j
-
"
~
u
z
.
~
J
l
"
~
u
I
J
-4
<
.,
0
>
r
0
0
z
-4
~
0
r
~
~
z
G)
>
0
~
0
~
en
0
-1
:I:
~
c
N
0
0
C/)
0

STA
R DEL
TA
STARTING
DETAIL
"c"
LE
GEND
ST
ANDARD
CONTACTOR
-
COioiPRESSOR
Cl3-14
CONT
ACTOR -CONDENSER
FAN
CBI
CIRCUIT
BREAKER-
CONTROL CIRCUIT
CB
l,
4 CIRCUIT
BREAKER-
HEATERS
CHILLER BARREL HEATER
CSTMI
·3
!
COMPRESSOR
SOLID
STATE
NODU
LE
HPI
-3
IH
IGH
PRESSURE
CONTROL
LOT
1-3
LOW
OIL TEMPERATURE
LPI
- 3
LOW
PRESSURE
CO
NTROL
LPF
I · 3 I
LOW
PRESSURE
FREEZE
OTS
I·
3 IOIL TEMPERATURE SAFETY
PLM 1 I
PHASE
LOSS
MONITOR
Rl
-3
!R
ELAY-STAG
I
NG
RELAY -CAPACITY CONTROL
RELAY -
LOCK
IN
SWITCH-
MASTER
Rl4,
16, IB IRELAY -TNTEIIILOCK
R
19
-21
I
RELAY-CRANI<CASE
SOLI
· 3 I
SOLENOID-LIQUID
LINE
SWl
- 4 I SWITCH-
COMPR
. CIRCUITS
THERMOSTAT -
SEQUENCER
TZ
] THERMOSTAT-
LOW
TEMPERATURE
THERMOSTA
T-
CA
PACITY CONTROLLER
TO
4-8
I TINE
DELAY-
CYCLING
~~
;o~~2
~:=~
~~~:
~
~
~
A~~~~~
~c~~
:TROL
I
OPTIONAL
TERMINAL B
OAR
D-CUSTOMER W
IRING
0
TERMINAL BOARD-FACTORY WIRING Q
UNLOADERS-SOLENOIO COMPRESSOR
AMBIENT
HIGH
TEMPERATURE
THEA"'
.
GF
1-
3 I GROUND
FAU
LT
PROTECTION
HOT
GAS
SOLENOID
LOW
AMBIENT THERMOSTAT
OLH
1-9
OV
ERLOAD HEATERS -STARTERS
PCH
I · 3
PR
IMARY COMPRESSOR HEATER
PL
I·
9 PILOT LIGHTS
R 22
RELAY-
SECONDARY HEATERS
RH
1·3
RECE
IV
ER
HEATER
RECEI
V
ER
HEATER
PRESSURE
CONTROL
RECEIVER
HEA
T
ER
THERMOSTAT
CIRCUIT
BREAI<[R-
RtC
. HEATER
SCH
I·
3
SECONDARY
CRA
NI<CASE
HEATER
TC
1-3
TRANSITION
CONTACTOR
TO
1-3
TI
NE DELAY -TRANSITION
CONTACTOR
TO
13
-
15
I
TINE
DELAY-
LOCI<
·OUT
LPF
STARTER -
COMPRESSOR
VOLT LOSS M
ONITOR
SSEC ALARM
CIRcunl
QI IYELLOW r;==
CIRCUIT3
1 · ' I
REMOTE
SWITCHES!
TO
8£
WIRED
IN
SERIES
TO
PUMP
M
OTO
R
INTERLOCK.
NOTES
I T2
AND
T3
TEMP.
SENSORS LOCATED
IN
WATER
OUTLET,
Tl
IN WATER
INLET
.
2. WHEN
TO
13,14
a IS ARE SUPPLIED,
WIRES
FROM
120,127
a 133 TO
T2
BE
CO
JojE
218,
236
8
255
RESPECTIVELY.
l.
WHEN
LATI
IS
NOT
SUPPLIED, WIRE
265
BECOMES
13
.
4.
WHEN
GF!,GF2 8 GF3
ARE
NOT
SUPPLIED,
WIRES
213,
231
8
250
BECOME
117,
124
8
130 RESPECTIVELY.
5
FOR
CONTACTOR
COILS
Cl
THRU
C
6,
Cl3
8
C
14,
SEE
MAIN
POWER
DIAGRAM
FOR
CONTACTS
6. ALARM LIGHT OPTION AND ALARM BELL
OPTION
ARE
NOT
SUPPLIED SIMULTANEOUSLY.
7.
WHEN
VLN I
IS
NOT
SUPPLIED,
WIRE
209
8ECOio4ES
272
.
@ &
~
@
@
&.
@ &
® &
&
§ol>ol<•l
L:.J
..
I•~
~
@
~
00
00
®
NO
,.,
..
R6}-----_j
58@
~
,.
WHITE
60
&/!::,.
"
\1s\2
2
\z5
l
~
~
\32137149
€€.>
@)
~@§>
~
..
1701~1~
70
@
UL I-1 .•• 1
00
&
140
72
@
ULI
-3
" ®
UL2
· 1
WHITE H @@
...
UL2
·2
" ®
'"
UL2
-3
76
®
77
"
l
~
"
5
~
u
{
-t
<
.,
0
)>
r
0
0
z
-t
::D
0
r
:e
::D
z
C)
)>
0
:e
0
~
0)
0
-t
:I:
::D
c:
N
0
0
en
0

~
"'
@]
••
il
0
I-I
O
LDING
COILS
WITH
:..I
NE N
O.
J
NO~
hi
ALLY
CLOSED
CO
N
TAC
TS
WITH
LINE
NC'.
:J NORMALLY
OP
EN
CONT
A
CTS
WITH
LINE
NO
6 NO
TE
WITH
LtNE
NO,
T
:~
2
PO
WER
SUPPLY
II~V/60
'\.1
/
I fll
4 BLACK
"'
~
30
~~
,,.
T~
~~0
[,
f--
I
""'
200W
oinoHAC
-'"·~
I
~
-
~
I I
I CB I
--
~
- RED
,---------.._~
@
@
@
e
TYPICAL
fOR
LIGHT OPTION
ON
ALARM
CIRCUITS 11
2,3
a 4 .
(NOT
SUPPLIED WITH
BELL
OPTIOfrll.)
S
TAR
DELTA STARTING
DETAIL "A"
ALARM CI
RCUIT
CIRCUIT I
0-f---.
I :
•.,']'~'
I '
8----=:::J
~
OPTIONAL
1
~
-fiiONAL
7
~2~
1 0
BLUE
7f
12GA
C B
3~
--
~
l~9
WHITE
ce
0
~"
' .
'"
[]3-;-o::J
~
~o----!.Q9
YELLOW 7
0
J'r
)i ! 10---
~
"v
I
L_
·l
PL
MI
T
,.
OPTIONAL
~LOW
I~
"+
~
~
I
--
L:
~
11
2 BLACK
BLACK
209
211 BLACK
OFTIC'NAL
I
R~
~
~
6NAL
I~
OFTi"ONAL
7
R,2~
1
"'
~
CBH2
r-------~
I
AHT2
212
R31
)-
-i-'-------""=""-
------
-~
~--~
OPTIONAL
I T
~
_O
>TIOHAC
N
RED
I TD
20
90
SE
C I
m
CSTMI
_ _
::j_
__
_j
: b !
""
1 W"'TE
Lfop!T
218
\rt"
lfc£0
WHEN
SUPPLIED
0'"1
OL"'
O<.H3
~
~
217
~
RED
121
R
LUlL
-
-L__
\ '
..
(
•
9
20
[!E)
21~
2
23~
2
2
(0
e
(0
@
@
26 @
27
@
29
1
27
1
33
1
9~
1
30
L:J
35
1
3s
l
& l
&
11.
~
&
-t
<
"tt
0
)>
r
0
0
z
-t
::D
0
r
:e
::D
z
G')
)>
0
:e
0
1\)
.....
(II
(/)
0

('
,
..
REO
A
Ss-------J
I
32
[!i]
@
~
C0"'4
PRES
SOR
CIRCUIT
I
)>
""'
TOO
33~
@
~
-t
" @ j <
~2.0
~
,.,
@X§)
,
"'
"
TOI!I
NC
,.
e 0
30
SEC
...
,.
)>
NO m
37~
r
181
BLUE
~~·.
BLUE
"'
8 j " @ & 1
0
z~~t
0
" e z
-t
S
TAR
DELTA
STARTING
~~R~R
0
~
c~RCUITI
I I I
(o2i)
I •
u@J
&
lJ
@
&.
0
r
(..)
1 _
TOZ
242
~1
2
..
~~
I I ···-· IN
r.c.z
,;;,
,.......,..
I I I I I I
LPFZ
,,.
""
~·
LOT 2
,,Q
OTS
2 I I I
129
R
LP2
v Q
R3
...
llO
l l
~I"=="
NTR
12ovl
l1es
I e
~
~
.,
" -
@ & "
lJ
..
~
-
[ I
237
~
47
& z
4
411
[4e[~•[tol~l
C)
BLUE "9l.:J4o[s,[ i
)>
DETAIL
"B'
I 0
BLUE
so§"]
@ 8
~
COMPRESSOR
CIRCUIT
2
51~
e j
I
VLioll
0I T 2 @
1\)
"
00
......
:'-r:
t I @ (11
0
,.
BLUE
0)
55~
en
250
0
,.

STAR DELTA STARTI
NG
....
.
...
,
....
I I I I I I
~~-
c.:::..__l___
1
59~
& l
e & .
" @ .
-i
e &
~
-<
;:;
.,
& .
z
. 0
s'
js3jse
\
95
\
5
SEC
-I I I t I
YELLOW
s
~
~
I
~
)>
DETAIL
"C"
c
·~~
u
~rOIH
!
r
8 @ 0 0
68
~
e . 0
0
••
e j z
70
EX3
-i
138
;
·
~
e :lJ
T
DI6
~
0
71
0
YELLOW
30
SEC
,
..
e
7Z
~
r
NO
~
I I
18ll
73
=e
-1>-
BR
OW
N g R22 6 BROWN
,.
,
Cl4
14
@
6l
:t
23
6 :lJ
" e
STAR DELTA STARTING
~~~
Ru~
Tc~currl
I I
76
EJ
& z
nPTinN.I.I
C)
@ &
)>
.&.: 0
9
~
=e
e &
;:;
. 0
z
& .
.
I\)
l
eo
\
e5
\
95
1
~
......
U1
5SEC
I I
BROWN
·~
~
I
e:
t
~
J
r5
j
er
\
I I 0
en
DETAIL "D" c 139
~~
~-
7
R<t
c ...
....
,
.....
.
84
El
@>
J
0
85
~
@
@
SWI
-- •
~
0 7
00
NC
144
@)
TO 18 "
!0
SEC BROWN
"'
u
ffi
NO

(
LEGEND
STANDA
RD
...
v~•••~wown
v--·
"~~vw"
Cll-14
CONTACTOA -CONDENSER
FAN
CBI-
2 CIRCUIT
MEAkER
-CONTROL CIRCUIT
C83-4,7
CIRCUIT
BREAKER-
HEATERS
CB
H
1-2
CHILLER
BARREL
HEATER
CSTMI-4
COMPRESSOR
SOLID STATE
MOOULE
HPI-4
HIGH
PRESSURE
CONTROL
LOT
1·4
LOW
OIL
TEN PERATURE
L.PI-4
LOW
PRESSURE CONTROL
LPF
1-4
LOW
PRESSURE FREEZE
OTS
1-4
OIL
TEMPERATURE SAFETY
PL.M
1-2
PHASE LOSS MONITOR
R 1
-4
RELAY -STAGING
R!S
- 8 RELAY -
CAPACITY
CONTROL
R
9·10
RELAY-
LOCK IN
SW
I
SWITCH
WASTER
Rll-14
RELAY-
INTERLOCK
R
20-23
REU.Y-
CRANkCASE
SOL
1-4
SOLENOID-
LIQUID
LINE
sw
2-5
SWITCH-
COMPRESSOR CIRCUITS
" THE t
•»OSTAT
-SEQUENCER
T2
THERMOSTAT-
LOW
TEMPERATURE
T3
THERMOSTAT-
CAPACITY CONTROLLER
TO
5·8
TIME
DELAY
CYCLING
~
(}1
TO
·-12
TIME
DELAY-
5
MIN
, LOCK
·I
N
TO
15-18
TIME
DELAY-
CAPACITY CONTROL
TER 5 TERWINAL 80ARO·CUSTONER
WIRING
0
TERWINAL
BOARD-
FACTORY
WIRING 0
Ul
I
THRU4
llhll
.
040FR~-
~01
FhiOIO
COt.IPti~~!IOR
OPTIONAL
AHT
1-2
AMBIENT
HIGH
TEWPERATURE THERN.
CBF
1-2
CONTROL
BOX
FANS
GROUND
FAULT
PROTECTION
HGS I I
HOT
GAS
SOLENOID
LOW
ANBIENT
THERWOSTAT
OLH 1-12 IOVERLOAD
HE4TERS
-STARTERS
PCHI-4
IPRIWARY
COloiPRESSOR HEATER
PL
1-12
PILOT
LIGHTS
R
30
·31
RELAY-
SECONDARY HEATERS
RH
1-4
RECEIVER
HEATER
AHPC
1- 4 RECEIVER
HU.TER
PRESSURE
CONTRO
L
RHT
1-4
RECEIVER HEATEA
THUMOSTAT
CB
5-6
I CIRCUIT
BREAKER-
REC
. HEATER
SECONDAI!:Y CRANKCASE HEATER
TC
1-4
ITRAHSITION
COHTACTOR
TlloiE
DELAY-
TRANSITION
CONTACTOR
TO
20-23
I TINE DELAY -LOCK
OUT
LPF
STAI!:TE"-
COMPRESSOR
\ILt.tt-2
IVOLT
LOSS NONITOR
TO
FLOW
SWITCH.
REMOTE
SWITCHES
TO
BE
WIRED
IN
SERIES.
TO
PUMF
MOTOR
IHTEALOCK
13 t BLACK
TER5
NOTES
I.
T2
AND
TJ
TEMP
SENSORS
LOCATED IN
WATER OUTLET, Tl IN
WATER
IHLET
.
Z.
WHEN
TO
20·23
ARE
SUPPLIED,
WIRES
FROt.t
124,131,137
6
143
TO
T2
BECOME
223,241,259
&
279
RESPECTIVELY.
3.
WHEH
LATI
IS
NOT
SUPPLIED, WIRE
289
BECOWES
13
.
4.
WHEH
Gfl-4
ARE
NOT
SUPPLIED,
WIRES
218,237,254
ll
274
r.ECOME
121,128,
134 6
140
RESPECTIVELY.
6.
FOR
CONTACTOR
COILS C1-
8,
13
8 14,
SEE
WAIN
POWER
DIAGRAM
FOR
CONTACTS.
6 ALARM LIGHT OPTION
AND
ALARM
BELL
OPTION ARE
NOT
SUPPLIED
SIWULTANEOUSL't".
7
WHEN
VLM
1-2
ARE
NOT
SUPPLIED,
WIRES
213 a
270
8ECOWE 214 8
12
RESPECTIVELY.
BLACK
14!5
BLACK
!5
MIN
1761
LOAD
UL2-3
I
90
~I
~
-<
lu/32/3sJ@
.,
0
94
8 l>
95~
r
96
~
0
97
~lso/ss/
@€) 0
~
z
~
~
::D
100
179/84/871
<E:€)
-0
101
~
•!
r
102!1oij~
i~
~
, -
::D
~
~i
-
10< z
e
-~
100 C)
106
00
l>
@ 8 0
108
®3
~
109 @ 0
110 e N
....
I
c.n
'"
~
en
~
0
"'
'"
@
"'
@
...

ACWC
160-200 SC
~
PC
8 7
..
'
~~;,;L"m
,.
.m
fCPI
r--~
I
~
j - I
W.i~
'::t
l
U$
DETAil
FOR ONE
TER'-IINAl
BLOCK TAOOHS
I I I I
~"
i
ACWC
215 SC
..
'
'•
,t
PLiol
l/
19
\'
lv
c••
~-TOPTIONAL
I TOCONTI!OI.CIIICUIT
••
TYPICAL
POWER WIRING
ACROSS-THE-LINE
START
Dl.
SI
r-,
' A •
L
lti
_jOf'fiOIU.L
for~
' A •
LY.J
USE COPP£R COHOUCTORS OHLT
LEGE
ND
OV£11l.OolOIIUTU-SUIIT£11
CQNTACTOOI-CO'IPIIESSOII
~~~~~~
)
~~:::~::"~C:~:S£11
UN
FCPI·IO
FA~
CYClfi'IG
PRESSURE
COOITIIOL
GilD
GIIOUNOINGlltG
III
II
loi:Ov.JIII-COHD£NS£RFAN
I'CII
J CIRCUIT i!III£AK(III ·C00.1"111ESSOII
I'C87·1
CIJICUITIIII[AK£11-FAII
M
OTOOI
Pfll
·ll
POWEll FUS£
·T
IIANSf
OII
MUI
"'-MI·l
PHASE
lOSS
III
ON
I!Ofl
l[lll·l
l(II
III
IN
..
LIIOARO·
MA
IN
POWf~
HIU.
HRVI".I.l
iiOAIIO·CONO[NSlll
U~
Hll~
TUI011NALI04110
CUSTOiol£11
""IIH•G
N
OT
ES
6FCP9
110
All(~fii£0U111(00NIIOSC
2
fOil
Cl-14
S~l
CONTROl CIRCUIT
•tiii
"'G
OIAG~A
III
- - -
flllO
W
illiNG
- - F•
tTOIIT
W
IIIING
US£
COPP[R
COND
UC
T
ORS
ON
LY
R
EFER
TO
UN
IT
SPE
C
PLA
TE F
OR
VO
LTAGE
Cl$·14
CONT.I.tTOIII·COND€NSEIIFAN
CMI'I-4
tO
WI'RESSOIIIIIPQTQII
CIUI-2
00011
LATCHING
$0\,_(N()IQ
ftl'l·ll
fA
N
tTCLINGI'RUSUIIECONTIIOL
GilD
GIIOUHDI
NG
LUG
IIII
-I
flfO
TOR·COND£NSIII,AN
~11·4
CIIICUIT
PEAK(II-COioii'IIUSOII
I'CI7•1
CIRCUIT I
II!AKEII-
n.JI W
OTC)III
Pf'!I•U
I'O'IIIEIIFUSE-TIIAN!'OII
III
EII
"-1111-2
....
ASI:LDSS
III
OJIITOIII
T£1111-2 TER
III
IN.U.IOAIIID-IIIAHoii'O'IIIU
TEII!
-4 Tl:lllolllt.I.LIOAIIO•CONDENS£11F"""
fEllS
TEIIM
INAliOAIID-CUSJOM[IIWIIIING
NOTES
1.
..
4,
W
II.'CI'7,1,1S,IIlMNOTIIEQUIIIIEDD
N215SC.
t.I'OR Cl-14
lEE
CO
NT
II
Ol
CI
IICUIT WI
II
I
IIO
DIA
GII
A
III
---
,.
IL
O WIII INI
--
,A
CTOIIITWI
II
I
NI
16
..
'
11 9 l
puu
t
I9 9
o,
,.,
1
-r·DI'TIDNAL
)
TOCONTIIOLCI
II
CUrt
•sni'<OTt-,
,----
Fo~;l
•A
I
L_l,,_j
..
'
m.
II
I
II
e.-
l
!t
..
I 1 g I
PLM2/
19
?
lv
cwz
1
-rOP
T
IO
N
.I.L
--..;
'
lt:l t:l
t::i
l
,

\....../
~
N;t~t;"'
I 1 1 1
1"1.1111/
A I t
•(
YLIII
OI'TIOIIA
L)
11t
1
111111111
'
r+-h
I A I C !
1'\.11111/
""'
ACWC
160-200 SC
ACWC215
SC
TYPICAL
POWER
WIRING
STAR-DELTA
START
NOTES
1.
11
1 I
't,I
,IO
Ut
lOO
T U
IIIII
III:D
011
1
1
01
~
.
l,OII
CI·C
IOIII
tOU
IOOI.C•
•
tuiT
•I•IM!Ho\&
UII
UKCOfi'NII
COtiOUCTOM
OtiLT
lltEF£11
TO
U"IT
PlC
'LJ.Tt
'ClR
VOLTAGE
:
mull
I
~
l1
wu
1
...
i r
r.I
n if
·t
ni
...
.....
r:-. I
,n :
~~f
i
Otll
l
N~:E"
I _ I
~LIII/
o;
•(YUI:I:
OI'TI
OIIAl}
TO
CI:*TIIQ.
CM
eurT
rt
-h
I A I C !
PLII2:/
""'
&
·
r.;~-j
·
J''
S3 u
S4
:fW
;
;~:
I :trtl
~~~
f
I
e•••
J
~U4
NOTES
l
iiA,.II'a'
T
,I
,
IS
,
II4111MI'tiiiOUIIICIOIINK
1.-
CI·
CMKl~
el
!tCUITWIR
I
..
_IIAII
17
II
V Y 1
•111111
1

ELECTRICAL
DATA
60HZ.
TOTAL
UNIT
CHARACTERISTICS
COMPRESSORS
CONDENSER
FANS
VOLTAC:E
Min.
Clroult
Max.
Fuoo
&uggoatod
Rated
Locked
Full
Amps' Size3 Wire Size• Load Rotor Load
Model Name Circuit Circuit Circuit Circuit Circuit Circuit Qty. Type Amps Amps Amps
ACWC Plate Range 1' 2' 1' 2' 1' 2' H.P. Start Each Each Phase Each
208-230 187-253 322 460 450 600
160SC 460 414-506 326 -400 -
208-230 187-253 335 468 450 600
185SC 460 414-506 350 -400 -
208-230 187-253 339 468 500 600
200SC 460 414-506 358 450
--
208-230 187-253
501
501
700 700
215SC 460 414-506 222 222 300 300
4605 414-506 420 -500 -
"ATL-
Across
The
Line
'208-230 voltage
requires
two
field
wiring
supplies
(circuits).
'
Minimum
circuit
ampacity
is
per
N.E.C.
Section
430-24.
400 700 205
400 (3)60
ATL"
90
-
400 750
IJ.!.@_
205
(2)75
ATL"
208
IJ.!.@_
90
500 -(2)75 98
500 750 208
500 -(3)75
ATL
"
98
900 v 900/ 205
0000 0000 (4)60
ATL"
90
600 -90
3Use
time
delay (dual
element)
fuses
only
. Suggested fuse sizes based on N.E.C.
Section
440-22.
•Wire size based on
copper
conductors
with
75° C. in
sulation
per
N.E.C.
Table
#31
0.16.
5
Single
point
power
terminals
NOTE:
1228
491
1228
1415
491
562
1415
562
1228
491
491
Maximum
inrush
amps
is L.R.A.
of
lag
compressor+
R.L.A.
of
all
other
compressors+
F.L.A.
of
all fans.
Lag
Compressor:
75
H.P. on 185SC.
Model
ACWC 320 340
160SC 12.0 13.7
185SC - -
200SC - -
215SC -
---
01
()2
COOLER
WATER PRESSURE
DROP
(Feet of Water)
GALLONS PER
MINUTE
360 380 400 420 440 460 480 500
15.4 17.1 18.8 20.6 - - - -
10.6 11.9
13.1
14.3 15.7 17.1 18.6 20.2
- - 13.1
14
.3 15.7
17.1
18.6 20.2
---
11.1
12.2
13
.3 14.4 15.5
Q3
Qs
1}4
Qs
520 540 560
---
- - -
---
16..Z_
_1_7
.
~
19.4
13.2
3 6.6
13.2
3 6.6
13.2
3 6.6
13.2
3 6.6
6.6
580
-
-
-
20.8
7L51
slJl
6~~~-
138
Y,
~
8 + 107
Y,
~
LOADING
(LBS.)
Model
LOCATION
POINT
NUMBER Dim.
ACWC 1 2 3 4 5 6 7 8 8
160SC 2120 2120 2120 2120 1830 1830 1510 1510
74
185SC 2280 2280 2280 2280 1960 1960 1630 1630 129
200SC 2340 2340 2340 2340 2010 2010 1670 1670 129
215SC 2330 2330 2330 2330 2150 2150 2150 2150 129
18
Locked
Rotor
Amps
Each
92.0
46.0
92
.0
46.0
92
.0
46.0
92
.0
46.0
46.0
'

START-UP
CHECK
LIST
Equipment Inspection: a.
Unit
damaged on arrival
b.
Mater
i
al
received agrees
with
shi
pping
papers
I
""
Setting Unit: a.
Vibration
isolator
used
b.
Spring
isolator
adjusted
for
equal
height
c. If
rubber-in-shear
isolators
are used, is
unit
leveled by
shimming
Wiring:
a.
Power
wiring
complete
b.
Control
wiring
complete
c. Electric service adequate
for
load
d. Power
source
voltage
correct
for
motor(s)
used
e.
Motor
circuit
has
proper
size fusetrons
f.
System wired per
diagram
g. All lead
connections
tight
h.
Wiring
complies
with
local codes
Piping:
a.
Piping
complies
with
applicable
codes
b. External
piping
independently
supported
c.
Chilled
water lines insulated
Alignment: a. All belts adjusted and checked
for
tension
b.
All
pulleys
checked
and
adjusted
for
proper
pitch
,
tightness
and
alignment
Before Start-Up: a. Open
compressor
discharge
service valve
b. Open
liquid
valve(s)
c. Open
suction
, and
discharge
valves
to
pressure gauges
(if
supplied)
d.
Check
rotation
of
all fan
motors
e. All
motors
and bearings
lubricated
g. Start
auxiliary
equipment
(pumps, fans, etc.)
h. Is crankcase heater operating?
After Start-Up: a.
Check
high pressure
control
b.
Check
oil
temperature
safety
switch
c.
Check
and
adjust
low
pressure
or
temperature
freeze
control
-
d.
Check
and
adjust
operating
thermostat
e.
Check
and
adjust
low
pressure
operating
control
f.
Check
and
adjust
expansion
valve superheat
g.
Check
and adjust
capacity
control
thermostat
OPERATING
DATA
CHILLER
Voltage:
L-1
L-2 L-3
___
_
Pressure Gauge Readings:
a.
Suction
psig
b.
Discharge
psig
High pressure switch setting:
(Cut-In)
psig
----
psig (Out)
Checked Setting Yes No
Low Pressure Switch Setting:
(Cut-In)
psig
----
psig (Out)
Checked Setting Yes
No
Low
Pressure Freeze
Control
Cut
In
Cut
Out
Oil
Temperature
Safety
Switch
Cut
Out
If
Star-Delta start, time delay is seconds.
Temperature
of
air entering
condenser
oF.
Temperature
of
air
leaving
condenser
oF.
Temperature
of
chilled
water
entering
chiller
oF
.
Temperature
of
water (chilled) leaving
chiller
oF
.
Chilled
water
pressure entering
chiller
psig
Chilled
water pressure leaving
chiller
psig
..,._._..
YES
NO
i
~
I'
•. I
Table of contents
Popular Chiller manuals by other brands

Carrier
Carrier AquaEdge 19XRV series Start-up and service instructions

Polar Electro
Polar Electro UA014 instruction manual

Surna
Surna 1-18-01 Operating and maintenance manual

York
York YCAS0098EB Installation operation & maintenance

JBJ Lighting
JBJ Lighting mini ARCTICA DBI-050 owner's manual

Daikin
Daikin Navigator WWV Installation operation & maintenance