6.2.2 HEATING CIRCUIT
BS-03
4)
Operation pump ..........................
Affects the operating status of the heating circuit
5)
* Weather ................................
Automatic or manual activation of multiple clock programs
** Clock program .......................
Setting the heating and setback phases for the NORMAL heating program
* Clock program (cold) .............
Setting the heating and setback phases for the NORMAL heating program
* Clock program (mild) .............
Setting the heating and setback phases for the NORMAL heating program
* Clock program (warm) ...........
Setting the heating and setback phases for the NORMAL heating program
6)
Target temperature da ...............
A room unit is required to control the set room temperature
7)
Target temperature night .............
A room unit is required to control the set room temperature
8)
*** Room influence .....................
0% - 100% influences the flow temperature / T1°C - T3°C influences the heating circuit pump
9)
Heating curve ..............................
Affects the flow temperature – (higher set value = higher flow temperature)
10)
Night off AT .................................
Affects the heating circuit during the setback phase
11)
* AT-Limits cold/mild ................
Switching threshold for changing between the COLD and MILD clock programs
11)
* AT-Limits mild/warm .............
Switching threshold for changing between the MILD and WARM clock programs
12)
AT-Shutdown ..............................
Affects the heating circuit during the heating phase
back to the costumer level .......................
look at Chapter 6.2
INFO
* The menu button is onl visible if **Multiple clock program** is activated in the commissioning menu.
** When the multiple clock program is activated, this menu button is not visible.
*** The menu button is onl visible if the room device/room station is activated in the commissioning menu.
4) Auto ........................ When the NORMAL heating program is activated, the heating circuit is switched ON and OFF full automaticall
according to the heating and setback times set in the clock program. If the outside temperature exceeds the value set
in the OT switch-off parameter, the heating circuit switches off.
Off ........................... The heating circuit is switched off.
Permanent .............. The heating circuit pump runs continuousl (no mixer control).
5) Auto ........................ Automatic changeover between the multiple clock programs COLD, MILD and WARM depending on the outside
temperature. You can set the outside temperature switching threshold for automatic changing of the multiple timer
programs in the OT limit COLD/MILD and MILD/WARM menus.
Cold ......................... Onl heating mode according to the COLD timer program.
Mild ......................... Onl heating mode according to the MILD timer program.
Warm ....................... Onl heating according to the WARM timer program.
6) Control to the DAY SET TEMPERATURE is onl possible during the heating phase of the heating circuit and requires a room device/room
station assigned to the heating circuit. This automaticall adjusts the heating curve so that the desired room temperature can be reached
in an weather.
- Without a room unit, heating can onl be operated according to a preset heating curve without taking the room temperature into
account. Increasing the target da temperature onl causes the preset heating curve to be shifted "up".
- If the outside temperature exceeds the value set in the OT switch-off parameter, the heating circuit switches off.
7) Control to the NIGHT-TIME TARGET TEMPERATURE is onl possible in the lowering phase of the heating circuit after the outside
temperature has fallen below the value set in the Night from AT menu and requires a room device/room station assigned to the heating
circuit. This automaticall adjusts the heating curve so that the desired room temperature is achieved.
- Without a room unit, onl reduced heating operation according to the preset heating curve is possible without taking the room
temperature into account. Increasing the night-time target temperature onl causes the preset heating curve to be shifted "up".
- If the outside temperature exceeds the value set in the Night off AT parameter, the heating circuit switches off again.
8) 0% – 100% .............. When the outside temperature is high (plus degrees) and the room temperature is too low, increasing the room
influence enables the desired room temperature to be reached more quickl .
T1C° - T3°C ............. If the set room temperature is exceeded b the set value, the heating circuit pump is switched off.
9) A higher heating curve causes a higher flow temperature at the same outside temperature.
10) If the outside temperature set in the Night off AT parameter is not reached during the lowering phase, the heating circuit switches on.
Attention: No frost protection function until the outside temperature set in the Night off AT menu is undershot.
11) Setting of the switching threshold for changing between the clock programs COLD/MILD and MILD/WARM.
Attention: The change between the weather-dependent clock programs depends on the average temperature of the previous da
and ma take place with a time dela until one da later.
12) If the set outside temperature is exceeded during the heating phase, the heating circuit switches off.