5
Power module configuration
Follow these guidelines to configure power modules for the device:
•Determine the total number of power modules based on the
actual power consumption, the power module slot number, and
power redundancy design.
•Determine the power module redundancy design based on the
power source conditions.
{When two mains power inputs are provided, you can
configure the power modules in N+N redundancy. N+N must
be not greater than the total number of power module slots.
{When one mains power input is provided, you can configure
the power modules in N+1 or N+N redundancy. N+1 or N+N
must be not greater than the total number of power module
slots.
•For easy usage and maintenance, configure a circuit breaker for
each power input. The rated current of the circuit breaker must
be a minimum of 20 A.
Power cords
The PSR3000-54AHD power module must be used in conjunction
with power cords listed in Table 4.Determine the power cord based
on the power source conditions.
Table 4 Power cords available for the PSR3000-54AHD
Type Product code
High voltage DC power cord CAB-HVDC Pwr-3m-336V
AC PDU power cord CAB-PDU Pwr-3m-PW3C450V
AC power cord CAB-AC-Pwr-3m-PW3C450V