Symptom Possible
Causes Corrective Action
Alarm 123 SPINDLE DRIVE FAULT
and Alarm 993 SHORT CIRCUIT
Alarm 2040 VECTOR DRIVE OR
SPINDLE-AMPLIFIER SHORT
CIRCUIT
The vector
drive
detected a
short circuit.
Inspect the Vector Drive and the Wye-Delta contactors for a short
circuit. For Delta-Wye Contactor Troubleshooting refer to: Wye-
Delta Contactor - Troubleshooting Guide. For Vector Drive short-
circuit inspection see section below.
Alarm 123 SPINDLE DRIVE FAULT
Alarm 648 DC BUS SHORTED
Alarm 292 HIGH VOLTAGE POWER
SUPPLY FAULT and Alarm 160
LOW INCOMING LINE VOLTAGE
There is a
problem with
the DC Bus.
Compare the measured DC voltage to the Diagnostic page.
Alarm 292 HIGH VOLTAGE POWER
SUPPLY FAULT and Alarm 647
REGEN LOAD SHORTED
There is a
problem with
the REGEN.
Measure the resistance across the REGEN leads.
Alarm 292 HIGH VOLTAGE POWER
SUPPLY FAULT and Alarm 200
HIGH VOLTAGE POWER SUPPLY
OVER–TEMPERATURE
Alarm 2038 VECTOR DRIVE OR
SPINDLE AMPLIFIER–OVER
TEMPERATURE
There is a
problem with
the vector
drive cooling
fan.
Inspect the cooling fan.
Alarm 292 HIGH VOLTAGE POWER
SUPPLY FAULT and Alarm 444
REGEN REMAINED ON TOO LONG
There is a
problem with
the incoming
AC power.
Measure the incoming voltage to the machine.
The Machine Fails to Maintain
Spindle Orientation.
The vector
drive output is
unbalanced.
Measure voltage outputs across the vector drive terminals.