commissioning and maintenance guide

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 2(31)
Version 1.0 All rights reserved © Halton
Contents
1 Introduction ......................................................................................................................................... 3
1.1 About this document .................................................................................................................... 3
1.2 Copyright and disclaimers............................................................................................................. 3
1.3 Safety notes .................................................................................................................................. 3
1.4 Contact information...................................................................................................................... 5
2 Product description.............................................................................................................................. 6
2.1 Overview ....................................................................................................................................... 6
2.2 Operating principle ....................................................................................................................... 7
2.3 Structure and materials ................................................................................................................ 8
3 Installation ........................................................................................................................................... 9
3.1 Before you start ............................................................................................................................ 9
3.1.1 Installation process ................................................................................................................ 9
3.1.2 Installation information ......................................................................................................... 9
3.2 Step by step instructions............................................................................................................. 14
3.2.1 Connecting the damper to the ductwork ............................................................................ 14
3.2.2 Connecting the wiring .......................................................................................................... 17
4 Commissioning................................................................................................................................... 18
4.1 Before you start .......................................................................................................................... 18
4.1.1 Commissioning process........................................................................................................ 18
4.1.2 Airflow controller display..................................................................................................... 18
4.1.3 Modbus RTU communication .............................................................................................. 19
4.1.4 Factory settings.................................................................................................................... 19
4.2 Start up........................................................................................................................................ 20
4.3 Basic controller settings.............................................................................................................. 21
4.4 Resetting the parameters ........................................................................................................... 23
5 Maintenance ...................................................................................................................................... 24
6 Technical reference data.................................................................................................................... 25
6.1 Dimensions and weight............................................................................................................... 25
6.2 Installation parameters............................................................................................................... 26
6.3 Modbus RTU variables ................................................................................................................ 29

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 3(31)
Version 1.0 All rights reserved © Halton
1 Introduction
1.1 About this document
This guide provides guidelines for installing, commissioning and maintenance of the Halton
ultrasound damper.
1.2 Copyright and disclaimers
The contents of this document are strictly confidential and for information purposes only. Disclosing
the information in this document without an appropriate contract or permission by Halton to any
third party is prohibited. This document remains the sole property of Halton and may not be
duplicated, borrowed, copied, amended, modified, reproduced, transmitted or distributed to any
third party without the prior written consent of Halton. Any information held in this document or
associated materials may only be used for the purpose specified in this document.
Halton disclaims any and all liability related to this document. Halton gives no explicit or implied
warranties in terms of this document. Any permitted use of the information included herein is at
your own risk. Halton may amend or replace the information included in this document at its sole
discretion without further notice and liability.
All intellectual property rights or applications thereof, including without limitation copyright, model
rights, patents, trade secrets, trade names, trademarks, know-how (whether registered or
unregistered) attributable to this document remain the sole and exclusive property of Halton. No
rights or licenses are granted.
1.3 Safety notes
All information in this section is important and relevant for your safety. Please pay special attention
to these icons and the accompanying messages when used later in context in this manual.
Warnings
Warning signs indicate a risk of personal injury including death. There is also a potential risk of
material damage. Pay attention to the following signs when performing any tasks or moving in the
area:
WARNING!
This symbol indicates a potential hazard, obstacle or condition requiring special attention.

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 4(31)
Version 1.0 All rights reserved © Halton
DANGER OF ROTATING UNIT PARTS!
This symbol indicates a hazardous location with a risk of personal injury including death and material
damage.
DANGER OF OVERHEAD LOADS!
This symbol indicates a hazardous location with a risk of personal injury including death and material
damage.
DANGER OF PERSONAL INJURY!
This symbol indicates a hazardous location (excluding the above-mentioned danger areas) with a risk
of personal injury including death and material damage.
Cautions
Caution signs indicate a risk of personal injury or material damage. To ensure your own safety,
consider the following cautions:
CAUTION!
This symbol indicates a hazardous location with a risk of material damage that can also lead to
personal injury.
CAUTION! HEAVY OBJECT
Do not lift objects over 20kg (44lbs) alone. Use a lift or seek assistance.

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 5(31)
Version 1.0 All rights reserved © Halton
CAUTION!
Risk of personal injury or material damage.
Notes
NOTE: Notes are statements to which you should pay special attention.
1.4 Contact information
You can find the contact details from www.halton.com/contact.

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 6(31)
Version 1.0 All rights reserved © Halton
2 Product description
2.1 Overview
Halton Max Ultra Circular (MUC)
Circular airflow management damper using the ultrasound technique for airflow measurement.
Application areas
•Standard VAV and CAV applications
•Supply and exhaust installations
Key features
•Insensitive to dust collection
•Enables flexibility in terms of space layout
•Individually calibrated for higher accuracies
•Low pressure loss for reducing the noise level
•Can be connected to Buildings Management System (BMS)

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 7(31)
Version 1.0 All rights reserved © Halton
2.2 Operating principle
Fig.1. Halton Max Ultra Circular (MUC) has two ultrasound sensors for airflow measurement.
The damper can function either as a supply or an exhaust unit. It maintains the required airflow
through ultrasound measurement, regardless of variations in the room conditions or duct pressure.
The damper has an airflow controller, two ultrasound sensors for airflow measurement, and an
actuator for controlling the damper blade.
The airflow controller can be controlled via:
•Modbus RTU,
•the control panel,
•an analogue signal.
All three control modes are synchronized between each other. The airflow measurement includes
temperature and duct type connection compensations, providing accurate and reliable airflow
measurements even at small safety distances.
Room conditions can be adjusted
•manually from an end-user interface

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 8(31)
Version 1.0 All rights reserved © Halton
•by different sensors such as occupancy or room pressure sensors, thermostats or timers
•remotely from a building management system (BMS)
The airflow setpoint can be modified between the minimum and maximum settings from the room
controller interface or a BMS.
2.3 Structure and materials
No.
Part
Material
1
Casing
Galvanised steel or stainless steel
(EN 1.4404, AISI 316L)
2
Duct seal gasket
Rubber
3
Shaft
Galvanised steel or stainless steel
(EN 1.4404, AISI 316L)
4
Blade
Galvanised steel or stainless steel
(EN 1.4404, AISI 316L)
5
Blade gasket
EPDM rubber
6
Actuator
Plastic, steel, PVC cable
7
Cable
Ethernet cable (LSZH)
8
Ultrasound sensor and temperature sensor
Plastic ABS
9
Airflow controller
Plastic ABS

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 9(31)
Version 1.0 All rights reserved © Halton
3 Installation
3.1 Before you start
3.1.1 Installation process
The installation is carried out by Halton Field Service or an approved partner.
Follow the installation process chart to install the Halton Max Ultra Circular (MUC) damper.
Fig.2. Halton Max Ultra Circular (MUC) installation process chart
3.1.2 Installation information
Installation options
There are three possibilities to position the damper. Sensors can be directed outwards, side or
inwards.
Safety distances and accuracy
Disturbances in the ductwork such as duct bends, T-branches and sound attenuators cause
turbulence and an uneven airflow. This can lead to fluctuation and inaccuracy in measurement
values.
NOTE: The recommended safety distance is greater or equal to one duct diameter distance, to
ensure the optimal accuracy.
Halton Max Ultra Circular (MUC) technical performance:
•Velocity range 0,5 — 10,0 m/s

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 10(31)
Version 1.0 All rights reserved © Halton
•General Measurement Uncertainty
Accuracy ±5 %
Minimum Safety distance 1D
•Expected Measurement Uncertainty, when correct installation parameter is applied
± % or l/s depending, which is the greatest of the percentage or the absolute value for the
specific product size.
Dim. 100 = ±5 % or ±1,00 l/s
Dim. 125 = ±5 % or ±1,25 l/s
Dim. 160 = ±5 % or ±2,5 l/s
Dim. 200 = ±5 % or ±4,0 l/s
Dim. 250 = ±5 % or ±6,5 l/s
Dim. 315 = ±10 % or ±10 l/s
NOTE : The measurement uncertainty is defined in laboratory conditions and may be greater in
practical installations, where non-optimal installation situations or multiple consequent disturbances
may exist.
Fig.3. Minimum safety distances
If the straight duct between the damper and disturbance is less than five times the duct diameter
distance, then the installation factor needs to be added to the airflow controller during
commissioning.
NOTE: The installation factors can be found in the 6.2.Installation parameters chapter.
Wiring and controller connections
The wiring must be carried out by professional technicians following local regulations. For the power
supply, a safety-isolating transformer must be used.

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 11(31)
Version 1.0 All rights reserved © Halton
Controller connections
Terminal
Name
Comment
1
GND
Ground
2
24 V DC/AC
Power supply input
3
GND
Ground
4
Standard RS-485 B
Data receive/send line B
5
Standard RS-485 A
Data receive/send line A
6
GND
Ground
7**
AI3
Input for NTC 10k temperature sensor (optional)
8
GND
Ground
9
AI1
Input for airflow or damper reference signal
10
GND
Ground
11
AO1
Output for airflow or damper feedback signal
12*
AI2
Analogue actuator feedback signal
13*
AO2
Analogue actuator reference signal
14*
GND
Ground
15*
24 V DC/AC
Power supply output for the analogue actuator
* Connected to Siemens GDB 161.1E actuator.
** Not included in delivery

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 12(31)
Version 1.0 All rights reserved © Halton
Wiring
Fig.4. Wiring example for Halton Max Ultra Circular (MUC) with a parallel configuration
Fig.5. Wiring diagram for parallel configuration (Modbus optional)

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 13(31)
Version 1.0 All rights reserved © Halton
Fig.6. Wiring example for Halton Max Ultra Circular (MUC) with a master-slave configuration
In the following example, the supply unit is controlling the exhaust unit.
Fig.7. Wiring diagram for master-slave configuration (Modbus optional)

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 14(31)
Version 1.0 All rights reserved © Halton
3.2 Step by step instructions
3.2.1 Connecting the damper to the ductwork
Before you start
•Check the inside of the damper for damage and loose parts.
•Remove any contamination from the ductwork.
•Support the installation with a suitable suspension system. Load suspension systems only
with the weight of the unit. Adjacent components and connecting ducts must be supported
separately.
•Wear protective gloves.
CAUTION!
Risk of personal injury or material damage.
Procedure
Position the damper so that the display is visible.
NOTE: See safety distance in installation information chapter.
There are three possible positions of the damper:
oOutwards
oSide

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 15(31)
Version 1.0 All rights reserved © Halton
oInwards
1. Push ducts onto the damper. The damper is fitted with seal gaskets.
2. Drill the holes for pop rivets.

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 16(31)
Version 1.0 All rights reserved © Halton
3. Fix the duct to the damper with pop rivets such that it cannot be moved.
NOTE: The fixing material is not included in the delivery.
Results
The damper is installed.
What to do next
Use tape to ensure tightness, if necessary.

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 17(31)
Version 1.0 All rights reserved © Halton
3.2.2 Connecting the wiring
ELECTRICAL HAZARD!
Before carrying out any work, turn off the power supply to avoid injury from electrical current.
Procedure
1. Unscrew the controller cover.
2. Connect input, output and communication wires.
NOTE: See Installation information in installation information chapter.
3. Put controller cover back to place and fasten the screws.
4. Switch on the power supply.

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 18(31)
Version 1.0 All rights reserved © Halton
4 Commissioning
4.1 Before you start
4.1.1 Commissioning process
The main steps in the commissioning process are:
•Controller settings
•Setting the installation parameter
•Setting the Modbus communication parameters (optional)
4.1.2 Airflow controller display
Halton Max Ultra Circular (MUC) airflow control has a control panel with display and four push
buttons.
Fig.8. Control panel
The LCD display can show 16 characters in 2 lines.
You can toggle between different parameter settings by pressing the arrow buttons. When the
'Setting' parameter is on view you can go back to parameter pages by pressing the OK button. If no
button is pressed, the display goes back into default view. LED lights indicate Modbus
communication. The red light indicates RS-485 Rx communication packet from master. The green
light indicates RS-485 Tx communication packet to master.

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 19(31)
Version 1.0 All rights reserved © Halton
4.1.3 Modbus RTU communication
Halton Max One Circular (MUC) can communicate to BMS system via Modbus RTU. Whit Modbus
register user can read and set parameter values. Modbus parameter list can find end of document.
To set parameters via Modbus, user need send password to MUC before it approve changes. When
set Holding register or Coils, first send register value what like to change and after that send 9055
value to Holding register 40905.
4.1.4 Factory settings
The airflow rates for Halton Max Ultra Circular (MUC) are preset at the factory. If the airflow rates
are not specified by the customer, the default factory settings are 0 for the minimum airflow rate
and the 10 m/s flow velocity for the maximum rate.
The maximum airflow rates in the following table are given with a flow velocity of 10 m/s. Applies to
all Halton Max Ultra Circular (MUC) actuator models.
NS
Maximum airflow (l/s) @ 10 m/s
Maximum airflow (m3/h) @ 10 m/s
100
78
283
125
122
441
160
201
723
200
314
1130
250
490
1767
315
779
2805
Table 1. Halton Max Ultra Circular (MUC) factory settings

Halton Max Ultra Circular (MUC) - Installation, commissioning and maintenance guide 20(31)
Version 1.0 All rights reserved © Halton
4.2 Start up
Press the OK button to move to the next step. Press the ESC button to move to the previous step.
Procedure
1. When the controller is powered, the
software version number is displayed.
2. The measured airflow is displayed in
m/s.
3. The measured airflow is displayed in
m3/h.
4. The measured airflow is displayed in
l/s.
5. The damper blade position is
indicated in percentage (0-100%).
6. The temperature measurement is
displayed.
7. The room temperature measurement
is displayed.