Haskris WW3 User manual

Revision: 00
Effective Date: 17 October 2022
MANUAL
MODEL WW3 & WW4
FOR CANON MEDICAL

Page 2 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
Table of Contents
I. Haskris Contact Information .................................................................................4
II. Installation: Confirm MRI and Heat Exchanger Model
MRI Model......................................................................................................5
Heat Exchanger Model ....................................................................................5
III. Installation: Mounting, Clearances, Connections
Mounting........................................................................................................6
Clearances......................................................................................................7
Connections....................................................................................................8
IV. Installation: Electrical, Connection to Outdoor Chiller
Electrical ......................................................................................................11
Connection to Outdoor Chiller ........................................................................ 12
V. Installation: Filling the Reservoir
Filling the Reservoir....................................................................................... 13
VI. Installation: Final Checks
Phase Monitor............................................................................................... 14
Controller Faults ........................................................................................... 14
Pre-Startup Checklist.....................................................................................15
VII. Optional Modbus or BACnet Communication Capability
Building Management System ........................................................................16

Page 3 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
VIII. Startup
Phase Monitor............................................................................................... 17
ON/OFF Switch .............................................................................................18
Pump Priming ...............................................................................................19
IX. Controller Display
Main Display .................................................................................................20
Status Modes................................................................................................20
Adjusting Set Value (sv) ................................................................................21
Units of Measure........................................................................................... 21
Faults...........................................................................................................22
X. Heat Exchanger Features
City Water Backup ........................................................................................24
Local Monitoring ...........................................................................................25
XI. Maintenance
Frequency .................................................................................................... 26
Water Quality ...............................................................................................26
Electrical Inspection ......................................................................................26

Page 4 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
I. Haskris Contact Information
Contact Haskris with any questions about a unit and/or the information in this manual. Haskris has a
team of engineers available to answer questions, troubleshoot issues, or provide supplemental
information as needed.
Phone: 001 847 956 6420

Page 5 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
II. Installation: Confirm MRI and Heat Exchanger Model
MRI Model
Details: Confirm the MRI model. Contact Canon for assistance.
Heat Exchanger Model
Instructions: There are several different heat exchanger models for cooling Canon MRIs. Use the MRI
information to identify the appropriate heat exchanger model. These instructions include details for
the two Haskris models.
Canon MRI Model
Haskris Heat Exchanger Model
Vantage
Atlas
Titan 1.5T
WW3
Titan 3T
Galan
WW4
Orian
Fortian
Not provided by Haskris
MRI and Heat Exchanger Models

Page 6 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
III. Installation: Mounting, Clearances, Connections
Mounting
•The WW is designed to be floor mounted with rear of the unit secured to a wall. Adjustable
leveling legs are included. Use of the leveling legs is optional.
•Secure to wall through wall mount brackets in two locations.
WW4 front view showing wall-mount brackets

Page 8 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
Connections
•Piping schematic below shows the plumbing connections.
•Drawings below show the location of the fluid connections on the unit.
WW / MANIFOLD
(INDOOR) SUPPLY
SUPPLY
SUPPLY
RETURN
RETURN
CITY WATER
RETURN
DRAIN & OVERFLOW - 1"
E
H
I
G
GACC / AMP CIRCUIT
F1
MAGNET GRADIENT
COIL CIRCUIT
FLOW SWITCH
REFRIGERATOR /
COMP CIRCUIT
F2 BFP CITY
WATER
IN
JK
SUPPLY
RETURN
RF CIRCUIT
DD
SUPPLY
RETURN CUSTOMER
EQUIPMENT OR
HASKRIS OPC
HASKRIS
WW
F
WATER LOOP
CHILLED WATER /
GLYCOL LOOP
LEGEND
D = ANTI-VIBRATION JOINTS; SUPPLIED AND INSTALLED BY CUSTOMER / CONTRACTOR.
E = WW/ MANIFOLD SUPPLY SIDE BALL VALVES; SUPPLIED WITH WW / MANIFOLD.
F = FLOWMETER (40 GPM, SUPPLIED BY CUSTOMER/CONTRACTOR).
G = WW / MANIFOLD RETURN SIDE BALL VALVES; SUPPLIED WITH WW / MANIFOLD.
H = CITY WATER INLET BALL VALVE; SUPPLIED WITH WW /MANIFOLD.
I = WW / MANIFOLD DRAIN / OVERFLOW CONNECTION; DRAIN VALVE SUPPLIED WITH WW / MANIFOLD (VALVE IS INTERNAL)
J = SHUT OFF VALVE; SUPPLIED AND INSTALLED BY CUSTOMER / CONTRACTOR.
K = PRESSURE REGULATOR (70 PSI MAXIMUM) SUPPLIED AND INSTALLED BY CUSTOMER /CONTRACTOR.
F1 = FILTER SUPPLIED WITH MRI SYSTEM;INSTALLED BY CANON ENGINEER.
F2 = 100 MICRON FILTER SUPPLIED AND INSTALLED BY CUSTOMER / CONTRACTOR.
BFP = BACK FLOW PREVENTER SUPPLIED AND INSTALLED BY CUSTOMER / CONTRACTOR.
NOTE: (1) CITY WATER SHALL NOTEXCEED 55 PSI.
(2) IN THE EVENT OF POWER LOSS OR CHILLER FAILURE CITY WATER WILL PROVIDE COOLING TO THE REFRIGERATOR
COMP CIRCUITONLY. WHEN IN CITY WATER BYPASS THE DRAIN MUST BE OPEN.
(3) RF CIRCUIT IS NOT APPLICABLE TO WW3 MODEL

Page 11 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
IV. Installation: Electrical, Connection to Outdoor Chiller
Electrical
•Comply with proper local electrical codes.
•Contact a licensed electrician to perform the electrical installation.
•The electrician should verify that the wiring is adequate in the installation area.
•Refer to the heat exchanger specification document or the unit’s nameplate label for detailed
electrical requirements.
•Do not mount or support any electrical service disconnect directly to the heat exchanger.
Electrical connection: Use a dedicated service disconnect and time delay fusing. Connect incoming
electrical to the distribution block in the electrical box.
Distribution Block

Page 12 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
Phase monitor: Heat exchangers include a phase monitor. Refer to the fault indicators provided on
the phase monitor and contact a licensed electrician to correct any faults.
Phase monitor
Phase fault LED status patterns
Connection to Outdoor Chiller
Purpose: Some heat exchanger systems come with a Haskris outdoor chiller. For these systems, the
heat exchanger must be wired to the chiller to ensure that Haskris will get remote notifications of
heat exchanger faults.
Installation: A 150ft (45.7m) cable is provided for this connection. Connect the provided cable to the
orange terminal strip in the chiller’s electrical box. Connections are 1-to-1 and are labeled.

Page 13 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
V. Installation: Filling the Reservoir
•Close all supply and return ball valves.
•Remove the cap from the reservoir.
•Fill the reservoir with drinking/spring water, up to just below the overflow drain port.
•Replace cap after filling.
•Make sure additional drinking/spring water is on hand to top off the tank during startup when
the unit’s pump fills the external piping.

Page 14 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
VI. Installation: Final Checks
Phase Monitor
Check: If the voltage and phase from the service disconnect is correct, the phase monitor should
have a solid green LED. If the phase monitor has a solid or flashing red LED, contact a licensed
electrician to correct the fault.
Controller Faults
Check: Press the button on the controller. The screen should say NO ALARMS. If any faults are
described, consult Haskris to resolve these.

Page 15 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
Pre-Startup Checklist
Directions: Email completed checklist to se[email protected] at least 10 days in advance of start-up.
Model: Serial Number:__________________________
Site Name:_____________________________ Address:_________________________________
_____________________________
Location:
❑Unit is securely mounted and level.
❑Minimum of 36” clearance exists on the front of the unit, and minimum of 18” clearance exists above
and to the sides of unit.
Fluid Connections:
❑All piping is of non-ferrous materials and complies with local codes.
❑Beginning and end of hard pipe runs are terminated with vibration isolators or a short length of hose.
❑Isolation ball valves are installed between WW and building water or glycol loop connections.
Electrical Power:
❑Incoming voltage and circuit breaker size for incoming power match unit’s nameplate.
❑Confirm proper electrical power and phase by checking the phase monitor’s status indicator.
Communication:
❑Communication wiring between the WW and OPC is installed (if Haskris chiller was provided).
Fluid fill:
❑The tank is full of drinking/spring water. The tank should be filled to about 3” from the top of the tank,
just below the overflow.
❑Additional drinking/spring water is on-hand for service contractor to top off system when start-up is
performed.
Installation Completed By (Please Print):
Company: ____________________________________ Phone:___________________ Email: __________________
Name: __________________________________________________________ Title: ____________________________
Signature: ___________________________ Date: __________
Nominal Power: CHECK NAMEPLATE
Record Voltage at
Disconnect
(V)
L1-L2
Confirm and Record Size of Time
Delay Breaker (Fusing) Supplying
WW (A)
L2-L3
L1-L3

Page 16 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
VII. Optional Modbus or BACnet Communication Capability
Building Management System
Purpose: Some facilities have centralized building monitoring systems (BMS). The exchanger can be
monitored from the BMS using Modbus or BACnet communication.
Operation: The method of interfacing with the BMS varies depending on the specific design and
whether the heat exchanger is paired with a Haskris outdoor chiller. Contact Haskris for details.

Page 17 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
VIII. Startup
Phase Monitor
Purpose: The heat exchanger has a phase monitor to check incoming electrical power.
Operation: The phase monitor is factory adjusted by Haskris according to the proper electrical
settings for the heat exchanger. Do not adjust the knobs on the phase monitor without discussion
and approval from Haskris.
The phase monitor will show a solid green LED if the voltage and phase from the service disconnect
is correct. If the phase monitor has a solid or flashing red LED, contact a licensed electrician to
correct the fault.
•Reversal is caused by the 3 lines being in an improper sequence. To correct a reversal, switch
any 2 of the 3 line connections. Make this switch at the disconnect, not in the heat exchanger.
•Loss/unbalance is caused by a percentage difference in voltage between the 3 lines relative to
each other.
•Undervoltage is caused by a percentage difference in voltage between the 3 lines compared to
the line-line voltage knob setting.
•Overvoltage is caused by the voltage between the 3 lines being >10% over the line-line
voltage knob setting.
Phase monitor
Phase fault LED status patterns

Page 18 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
ON/OFF Switch
Location: The heat exchanger has a rotary ON/OFF switch located on the left side of the unit.
Operation: Rotate the switch to make the heat exchanger run when in the ON position (horizontal) or
stop when in the OFF position (vertical). If a fault occurs, turning the switch to OFF and then back
ON will reset the fault. Note that city water backup is active while switch is in the OFF position.
ON/OFF switch, vertical position

Page 19 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
Pump Priming
Purpose: All fluid is removed from the pump head prior to shipment from Haskris. When starting the
pump, it needs to be filled with fluid. This process is called priming the pump.
When the reservoir is full, the pump suction line is “flooded”. In some cases, this flooded suction will
automatically prime the pump. When the heat exchanger is turned ON, the pump will run. If the
controller display shows the pump generating pressure, then the pump is primed.
If the pump pressure gauge shows a low pressure <10 psi, then the pump did not automatically
prime. Follow the procedure below.
1. Identify the priming plug on the face of the pump head
2. Use a wrench to loosen the priming plug slightly. The plug should remain threaded into the
port, but air and liquid should be able to escape.
3. Allow air and a small amount of fluid to escape
4. Tighten the priming plug
Pump priming plug circled

Page 20 of 26
Email: service@haskris.com
Phone: 001 847 956 6420
IX. Controller Display
Main Display
Status
Indicates the state of the heat exchanger
Supply Set Value
The desired temperature for the water
Present Value - Supply
Measured supply temperature
Flow Rate
Measured value of the flow rate on each cooling circuit
Description of main display data
Status Modes
ON
The ON/OFF switch is in the ON position and the pump is running
City water backup is not active
Note that on some programs the status text is blank when the unit is ON
OFF /
City Water
The physical ON/OFF switch is in the OFF position
City water backup is active
OFF→Alarm /
City Water
An alarm or fault occurred and stopped the heat exchanger
City water backup is active
OFF by BMS
The site’s BMS is connected to the heat exchanger and sending it a signal to be OFF
City water backup is active
Description of status modes
Status
Supply Set Value
Units of Measure
Flow Rate –Coil
Flow Rate –Comp.
Present Value –Supply
Main display
Flow Rate –Amp
Flow Rate –RF Cabinet
(if applicable)
This manual suits for next models
1
Table of contents
Other Haskris Chiller manuals