8. Troubleshooting Guide
Problem Possible Reason
Corrective Action
Unit will not start, with power
switch turned ON. Controller
display is off and fans are not
spinning.
Power not applied. Check Power supply and ensure
proper voltage in the line.
Unit runs for a period of time
and then shuts OFF.
Controller display turns off
and fans stop spinning.
Line circuit breaker tripped
due to overload.
Ensure line circuit breaker
matches maximum fuse size on
nameplate. Check that there
are no other electrical
components on this line.
1) The heat load is too high.
1) Refer to performance charts
in Section 4. Correct heat load,
if necessary.
2) Controller has incorrect
temperature setting.
2) Correct set point according to
Digital Controller instructions,
Section 7 of this manual.
Unit is running, but does not
maintain desired liquid
temperature.
3) Digital Temperature
Controller is not operating
properly.
3) Consult Factory.
Unit is running, but the Low
Fluid Indicator LED is lit.
Insufficient fluid level in
reservoir.
Fill up reservoir following air
purge instructions, Section 5 of
this manual.
Unit is running, but the liquid
level in reservoir is
decreasing.
Unit or outside System has
a leak.
Check the System for leaks. Fix
if possible. If the leak is
suspected to be within the Unit,
shut the Unit OFF and
disconnect from outlet, then
consult Factory.
1) System coolant line is
clogged.
1) Check outside System coolant
line for clogged tubing, closed
valves, or for a kink in the
tubing.
2) 5 minute restart delay
required.
2) Turn off unit, wait 5 minutes,
then restart. Check for coolant
flow in reservoir.
3) The System head is too
great for the pump.
3) Relieve System pressure by
removing or redesigning flow
restrictions. Consult pump
capacity charts in Section 4.
4) Fluid is frozen in the
Unit.
4) Change the set point to an
appropriate temperature or
change the liquid mixture to
lower the freezing point.
Unit is running, but there is no
coolant flow. Low Fluid
Indicator LED on the front
panel is not lit.
5) The Unit pump is not
running.
5) After checking 1-4 above,
Consult Factory.
Unit still does not run or
perform to specifications. Consult Factory.