Haskris LX Series Installation guide

Copyright © 2020 Haskris REV102920
1
www.haskris.com 776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph:+1-847-956-6420 | fx:+1-847-956-6595 | email:[email protected]
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 1: Temperature Control
• Your Haskris will have one of three different types of controller. Use table 1-1 to identify the relevant controller.
• The controller may appear different than examples. Contact Haskris if you are not sure what type you have.
• Adjust supply temperature while under heat load.
• Allow 15-30 minutes for the supply temperature to stabilize after an adjustment.
• Consult a dew point chart to select a supply uid temperature that will minimize condensation.
• If no heat load is applied, the unit may “over-cool”.
Electronic Temperature Controllers
ON/OFF
Cycling Control
Section 1.1
Parametric
Control
Section 1.2
Programmable
Logic Control
Section 1.3
Table 1-1

Copyright © 2020 Haskris REV102920
2
www.haskris.com 776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph:+1-847-956-6420 | fx:+1-847-956-6595 | email:[email protected]
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 1.1: ON/OFF Cycling Control
• The controller maintains temperature by cycling refrigeration ON/OFF using a set point and a differential.
• Supply uid temperature will oscillate between a set point and +4°F (+2.2°C) above the set point.
Set Point Adjustment
1. Press the MENU button. Display shows “OFF”.
2. Press the MENU button again. Display shows
the current set point.
3. Adjust the set point using the UP and DOWN
arrow buttons.
4. Press MENU to save the new set point.
Display shows “OFF”.
5. Press the UP and DOWN arrow buttons
simultaneously to return to the current supply
temperature reading.
Set Point Adjustment
1. Press and hold the SET button for 1 second.
Display shows the current set point.
2. Adjust the set point using the UP and DOWN
arrow buttons.
3. Press the SET button again to save the new
set point and return to the current supply
temperature reading.

Copyright © 2020 Haskris REV102920
3
www.haskris.com 776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph:+1-847-956-6420 | fx:+1-847-956-6595 | email:[email protected]
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 1.2: Parametric Control
• Refrigeration runs continuously to maintain steady supply uid temperature under a steady heat load and steady ambient conditions.
• Non-refrigerated units use a facility water regulating valve to maintain steady supply uid temperature under a steady heat load.
• The LEDs labeled PV display the present value of the uid temperature.
• The LEDs labeled SV display the set point value.
Set Point Adjustment
1. Press the UP and DOWN arrows to adjust set
point value.
High/Low Temperature Alarm Adjustment
Alarm set points depend on the
application specications and unit
design. Contact Haskris to conrm
factory settings.
1. Press the button once. PV displays
A1.SP. SV displays an alarm set point.
2. Before adjusting the alarm set point, record the
original setting. Press the UP and DOWN arrows
to adjust the alarm set point.
3. Press the button again. PV may display
A2.SP. If the setting is not used or not adjustable,
A2.SP will not appear. Adjust if necessary.
4. Press the button to return to the normal
temperature display.

Copyright © 2020 Haskris REV102920
4
www.haskris.com 776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph:+1-847-956-6420 | fx:+1-847-956-6595 | email:[email protected]
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 1.3: PLC Control
• Refrigeration runs continuously to maintain steady supply uid temperature under a steady heat load and steady ambient conditions.
• Non-refrigerated units use a facility water regulating valve to maintain steady supply uid temperature under a steady heat load.
• The Main Screen lists present value of the uid temperature, set point, and other operating conditions.
• Alarm conditions, including date and time information, are reported and logged on the controller.
Set Point Adjustment
1. Press to move the blinking cursor after SV
2. Press and to adjust set point value
Alarm Condition
If alarm condition occurs, the button will
ash red:
1. Press to view the most recent current alarm
2. Press and to scroll through current
alarms
To view log of past alarms:
1. Press
2. Press until Alarm Log is highlighted
3. Press
4. Press and to scroll through past
alarms
Main Screen
Alarm Screen

Copyright © 2020 Haskris REV102920
5
www.haskris.com 776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph:+1-847-956-6420 | fx:+1-847-956-6595 | email:[email protected]
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 2: Indicator Lights
Section 2.1: ON/OFF or Power
• Some units have a green light indicating the unit’s ON/OFF status.
• Some units indicate that they are ON by lighting the temperature controller.
Section 2.2: Liquid Level
• Some units with a tank have a light to indicate whether the liquid level in the tank is sufcient.
• Some units have a “FULL” light. This must be lit for the unit to function.
• Some units have a “Liquid Level Low” indicator. This must not be lit for the unit to function.
Section 2.3: Liquid Temperature Fault
• Some units have a “Liquid Temperature Fault” indicator. This means that the liquid temperature
is above or below the alarm set points.
Section 2.4: Refrigerant Pressure High or Building Water Fault
• Some units with a high refrigerant pressure safety switch include either a “High Pressure
Indicator” or a “Building Water Fault” indicator.
• Units require either fresh air or a source of cooling water to discharge heat. If ow of fresh air
or cooling water through the condenser is insufcient, refrigerant pressure increases. When the
pressure is too high, a safety switch will stop the unit and light this indicator.
• The high pressure switch can be manually reset after the refrigerant pressure decreases to
a safe level. The switch may be located on the base of the chiller or near the condenser. The
switch has a button that can be pressed to reset the switch.
Section 2.5: Refrigerant Pressure Low
• In refrigerated units, a low refrigerant pressure switch stops the unit if the compressor suction
line pressure is too low.
• This can indicate a refrigerant leak. Contact a local refrigeration technician to repair the leak
and recharge the system with refrigerant.
• This indicator may appear on startup. This is normal.
- Turn the system power ON, and wait until the compressor starts.
- Cycle the system OFF and ON 3 to 4 times before permanently switching the system ON.

Copyright © 2020 Haskris REV102920
6
www.haskris.com 776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph:+1-847-956-6420 | fx:+1-847-956-6595 | email:[email protected]
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 3: Strainers
• Some units have a nylon suction strainer in the tank to prevent debris from damaging
the pump. In LX-Series units, the strainer is threaded into a tting on the inside of the
tank at the bottom.
• Check the strainer regularly for debris or biological growth.
• If the mesh feels slippery or “slimy”, this indicates biological growth. Flush the system
according to the provided instructions.
• Replace the strainer whenever there is a signicant accumulation of debris or biological
growth.
• Replacement strainers are available from Haskris online at shop.haskris.com or over
the phone +1-847-956-6420.
• A dirty strainer can cause pump cavitation indicated by rapid pressure uctuations.
Failures due to cavitation are not covered under warranty.
• Some systems have brass wye strainers in the piping. These have a removable screen
that can be cleaned.
Section 4: Filters
• Some units include a supply line particle lter to capture debris.
• Record the running uid pressure at the completion of startup when the lter is clean.
• The running pressure can be read by viewing the uid pressure gauge near the pump or by
reading the controller display.
• Replace the lter when the pressure increases 5 psi to 6 psi (0.3 bar to 0.4 bar) above the
startup running uid pressure.
• Replacement lters are available from Haskris online at shop.haskris.com or over the phone
+1-847-956-6420.
Section 5: Drain Line
• Units include a drain hose connected to the bottom of the tank.
• Some units also include a plastic valve and hose barb connection.

Copyright © 2020 Haskris REV102920
7
www.haskris.com 776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph:+1-847-956-6420 | fx:+1-847-956-6595 | email:[email protected]
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 6: Water Quality and Treatment – Indoor Units
Fig. 2
Section 6.1: Maintaining Water Quality
• Periodically inspect the tank to make sure that the water is clear and that there has been no
accumulation of debris.
• Water should be drained and replaced regularly, once or twice per year at a minimum, in order to
maintain water quality.
Section 6.2: Flushing the System
• Flush the system when biological growth, signicant pH change, or signicant debris
accumulation is apparent.
Leaving the unit connected to the application will ush the entire system. Check with
the original equipment manufacturer (OEM) to conrm that hydrogen peroxide is
approved for the application. If hydrogen peroxide is not approved, disconnect
the application, and ush only the unit.
• In order to ush only the unit, connect a short hose directly from the Supply Connection to the
Return Connection. See Figure 1 and 2.
Flushing Procedure
1. Add 1 pint (0.5 L) of 3% hydrogen peroxide per every 15 gallons (57 L) of water to the tank.
2. Circulate the solution for 20-30 minutes.
3. Use the drain hose to drain the system.
4. Rell the system with clean, potable, distilled water.
5. Repeat as necessary to fully ush the system.
Section 6.3: Additives
• Water absorbs CO2 from the atmosphere. This reduces pH over time. Add sodium bicarbonate to
raise pH if needed.
• If biological growth persists even after regularly changing the water and ushing the system, use
laboratory/food grade (99% pure) propylene glycol to create a 10% solution.
• Haskris recommends that additives be used only as a means of last resort.
Fig. 1

Copyright © 2020 Haskris REV102920
8
www.haskris.com 776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph:+1-847-956-6420 | fx:+1-847-956-6595 | email:[email protected]
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 7: Water Quality and Treatment – Outdoor Units
Section 7.1: Additives
• For outdoor operation, a mixture of potable distilled water and laboratory/food grade propylene or
ethylene glycol is required to resist freezing in the winter.
Section 7.2: Maintaining Water Quality
• Glycol solution should be changed periodically to maintain uid quality.
• The frequency at which the glycol solution should be changed depends on environmental
conditions.
• Periodically use a pH test strip to check pH. If pH level is outside the range of 7 to 10, change the
glycol solution. If pH is below 7, a line ush should also be performed.
• Periodically use a refractometer to check the glycol percentage.
• If glycol percentage needs to be increased, add pure glycol of the same kind used when the unit
was originally lled.
• If glycol percentage needs to be decreased, add potable distilled water.
Section 7.3: Wye Strainer
• Some units have a wye strainer on the return uid connection.
• Clean the wye strainer every time the glycol solution is changed or the return pressure has
increased 10psi or more.

Copyright © 2020 Haskris REV102920
9
www.haskris.com 776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph:+1-847-956-6420 | fx:+1-847-956-6595 | email:[email protected]
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 8: Bypass Pressure Relief Valve
Section 8.1: Valve Setting Procedure
1. To nd the current pressure setting of the bypass valve, restrict the supply line by closing a hand
valve or kinking the hose. The pressure gauge indicates the current setting.
2. Remove the brass cap on the top of the adjustment screw, and loosen the locknut at the base.
3. Adjust the screw inward (clockwise) to increase the pressure setting. Adjust the screw outward
(counterclockwise) to decrease the pressure setting. Do not completely remove the screw. This
will cause a metal disc to fall off of the spring, requiring reassembling.
4. When the adjustment is complete, tighten the locknut and replace the cap.
Section 9: Refrigerant Sight Glass and Moisture Indicator
• Some refrigerated units include a liquid line sight glass and moisture indicator.
• This helps identify if the unit is low on refrigerant or if the refrigerant is contaminated.
• The sight glass should be clear and indicate “DRY” when the compressor is running.
• Constant bubbles owing indicate that the system is low on refrigerant.
• “WET” indicates that the refrigerant is contaminated.
• Turbulence and bubbles are normal immediately after the compressor turns ON, and immediately
after it turns OFF.
• Units with a positive displacement or turbine pump include one of the four types of modulating
bypass pressure relief valves shown at left.
• The valve has been preset from the factory for a maximum pressure in order to limit the supply
pressure to the application.
• The valve diverts ow whenever the running pressure of the system approaches the bypass
pressure setting.
• The bypass pressure setting must be above the pressure drop of the application and closed
loop piping.
• The running pressure of the system will increase if a restriction develops. This could occur due
to a closed valve or particle accumulation.

Copyright © 2020 Haskris REV102920
10
www.haskris.com 776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph:+1-847-956-6420 | fx:+1-847-956-6595 | email:[email protected]
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 10: Cleaning an Air-Cooled Condenser
• Air-cooled units collect dust and debris in the condenser during normal operation.
• Accumulated debris restricts air ow and reduces heat transfer which reduces the capacity
of the unit.
To remove debris, turn the unit OFF and use a vacuum to collect the debris.
See Figure 3 and 4.
• Use a brush to loosen compacted debris.
Section 11: Maintenance Checks
• Inspect the water (if applicable) in the tank. Make sure it is clean and the level is proper. (see
Section 6 or Section 7)
• Perform a system ush or line ush if you observe signicant accumulation of debris or biological
growth. (see Section 6.2)
• Inspect and clean or replace strainers and lters. (see Section 3, Section 4, Section 7.3)
• Clean air-cooled condenser coils and ns if necessary. (see Section 10)
Fig. 3
Fig. 4
Section 11.1: Schedule for Maintenance Checks
• After a new installation, perform these checks at least every 2 weeks for 3 months
• Beyond 3 months, perform checks at least 1 or 2 times per year.

Copyright © 2020 Haskris REV102920
11
www.haskris.com 776 North Oaklawn Avenue, Elmhurst, Illinois 60126 USA ph:+1-847-956-6420 | fx:+1-847-956-6595 | email:[email protected]
Operation and Maintenance
Haskris LX-Series, R-Series, WW-Series, OPC-Series
Section 12: Support
• If you have questions, encounter problems, or require technical support of your Haskris system,
please contact Haskris support:
Phone: 001 847 956 6420
Web: www.haskris.com
• Have the product serial number available when you call. This can be found on a panel near the
unit’s supply and return connections or on the main electrical enclosure.
This manual suits for next models
3
Table of contents
Other Haskris Chiller manuals
Popular Chiller manuals by other brands

Hoshizaki
Hoshizaki Lancer Polaris Beer Superchiller Installation, operation & service manual

Stulz
Stulz CyberCool 2 Original instructions

York
York ECOFRIOV2 R410A Specifications

Enerblue
Enerblue PURPLE User and maintenance manual

Halsey Taylor
Halsey Taylor SJ8 Installation, Care and Use Manual

Frigicoll
Frigicoll Kaysun KEM-90 DRS4 Engineering data book