EX23-R PoE Switch
FRONT
BACK
CAUTION
Drawing PoE power lowers the maximum operating temperature. Please
refer to the data sheet for the exact de-rating specifications.
EX23-R Factory defaults
To reset to factory defaults, jumper port 1 to port 2 using a 1-KAB2107
cable and power cycle the unit.
NOTE
Reset to factory defaults will cause ports to auto negotiate. However,
Ports 5 and 6 must be manually configured to 100Mb full duplex (status
LED will be orange) for reliable PTP function. Contact HBM Customer
Service for assistance with manual configuration.
Setting up the EX23-R
The EX23-R is designed to be used straight out of the box.
1. Connect the 1-NTX003 power supply or 1-KAB2115 power
pigtail cable from the power connector on the EX23-R to a
10-36VDC power source.
NOTE
Connect only the red and black wires of the 1-KAB2115 cable. Do NOT
use a 1-KAB2110 cable to power the EX23-R from the CX23-R,
eDAQXR EXRCPU or eDAQXR-lite EXRLCPU.
2. Connect the desired devices to the Ethernet ports using
1-KAB2100, 1-KAB2106 or 1-KAB2107 Ethernet cables,
depending on the device.
Configuring the EX23-R
1. Connect a PC to any open EX23-R port
using a 1-KAB2106 cable.
2. Open an internet browser and navigate to:
IP Config: 192.0.2.1/ip_config.htm or
Firmware: 192.0.2.1/upload.htm
3. Log on using the default credentials:
username:
admin
password:
(blank)
EX23-R status LEDs
Power LED Description
Off Power input not in range
On Unit is powered
Flashing (2 Hz) Power error
Flashing (8 Hz) Firmware update
Several issues can cause a power error:
nOver temperature
nOver voltage or over current input power
nInternal power supply not working
Ethernet LED Description
Off No link
Green Gigabit link is up
Orange 10 or 100 Mb link is up
EX23-R Quick Start Guide EX23-R Quick Start Guide