
If vo.u attempt to -o-perate an 11 amp AC appliance it will run fine for several minures.
The circuit breaker will eventually trip, proteciiirg ttre llearl rrom ;;;il; "perarion over
its rated ourpur. At higher powers theliicuit brealer wili tnp sooner.
When the breaker trips it will pop o!l: extending about 114 inch. To reset simply push
the breaker back in firmly and the unit will restart.
GROUND FAULT CIRCUIT INTERRUPTION:
HF12-1200U: The outlets on the front panel-are equipped with an integral ground fault
circuit intenupter (GFCI). In the case of a giould fautt, ttiii device will ind,'up't the outfut
of the Heart, and the reser burton will pop-out. To resei, push the uurio" uu"-t in.
On the GFCI there are two buttons, the reset and the test button. Monthly you musr test
ll9 G.FCI by turning the unit on and pushing.the test butron. The re.set u"ii""lnlutd pop out.
If it does not pop out, you must taki the uiir in for service.
- Important note: The GFCI test will not work properly if the unit is in idle. you must put
a load on the unit to perform the monthly test.
IIF12-1200UW: In order to conform to the National Electrical Code, certain branch
circuits -t!at may be operated with the HF600-12M musr be equipped with a Grct, such as
fasl a1d Seymour Cat. No. 1 591Rw. Consult the code for details. A CFCI outiit is included
in the box with the inverter.
PROTECTION FROM OVBRHEATING:
BecausetheHeartislo!guite lffiVoefficient, there will be heat built up in the unitduring
the operation of loads which-are close to the.rated ourpur. If a 1200 wait toaO is run lonfi
enough the therrnal protection in the Heart will come into play.
Wound into the center of the transformer is a thermal sensor that will shut down the Heart
if internal tlmperatures approach the maximum rating of ttre components. If this happens the
overload LED will come on, glowing red.
When this occurs you must give the unit time to cool down before re-starting. When the
fTlgets cool enough to start back ,rp, the overload LED will turn gt6n nirr,r,r overload
LED. turns green you may re-staft the unit by turning the power sivirch ro the off position,
pausing for a moment, then turning it on again
HIGH AND LOW BATTERY VOLTAGE PROTECTION:
The Heart will accept battery voltage ranging from 10.5 to 14.5 volts. If rhe voltage of
the battery bank falls ouiside of t-his ranle ttreio# uattery ieD will .o*" on, glowing red.
I.hg lo*. battery light will glow for a fewmoments while ;ho;;r ;;;;;;; iofierate. rr tr,e
high or low batrery voltage_persists the unit will shut itself d;;;;;h; i;; b^,;;y LED will
extinguish and the overload lighr wiu be left on, glowing $een.
The low battery cut out is designed to prevent the banery bank from discharging totally
and thereby incuning permanent dimage. There is a time delay built into this circuit which
l:'.
t:
1,.
Bi