Heat-Flo, Inc.| Indirect-Fired Water Heaters Page| i
IMPORTANT INFORMATION –READ CAREFULLY
NOTE: The equipment shall be installed in accordance with those installation regulations required in the area where
the installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction
shall be consulted before the installations are made.
All wiring on water heaters must be in accordance with the National Electrical Code (latest edition) and/or local
regulations in the US, and in accordance with the Canadian Electrical Code (latest edition) and/or local regulations
in Canada.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury,
or loss of life. Read and understand the entire manual before attempting installation, start-up, operation, or service.
Installation and service must be performed only by an experienced, skilled installer or service agency.
This water heater contains very hot water under high pressure. Do not unscrew any pipe fittings or attempt to
disconnect any components of this water heater without positively assuring that the water is cool and has no
pressure. Always wear protective clothing and equipment when installing, starting up or servicing this water heater
to prevent scalding injuries. Do not rely on the pressure and temperature gauges to determine the temperature and
pressure of the water heater. This water heater contains components that become very hot when the boiler is
operating. Do not touch any components unless they are cool.
Failure to follow all instructions in the proper order can cause personal injury or death. Read all instructions,
including all those contained in component manufacturers’ manuals before installing, starting up, operating,
maintaining, or servicing the water heater.
CAUTION
To reduce the risk of excessive pressures and temperatures in this water heater, install temperature and pressure
protective equipment required by local codes but no less than a combination temperature relief valve certified by a
nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or
materials, as meeting the requirements for Relief Valves and Automatic Shutoff Devices for Hot Water Supply
Systems, ANSI Z21.22-latest edition. This valve must be marked with a maximum set pressure not to exceed the
marked working pressure of the water heater. Install the valve into an opening provide and marked for this purpose
in the water heater, and orient it or provide tubing so that any discharge from the valve will exit only within 6 inches
above, or at any distance below, the structural floor, and cannot contact any live electrical part. The discharge
opening must not be blocked or reduced in size under any circumstances.
These water heaters with single-wall stainless steel heat exchangers meet the Uniform Plumbing Code for
installation in potable water systems provided that:
The boiler water, including additives, is practically non-toxic, having a toxicity rating of class 1 as listed in
Clinical Toxicology of Commercial Products, latest edition.
The boiler water pressure is limited to maximum 30 psig by an approved safety or relief valve.
The heat transfer medium is potable water or contains only substances that are recognized as safe by the U.S.
Food and Drug Administration. (FDA)
The pressure of the heat transfer medium is maintained less than the normal minimum operating pressure of
the potable water system.
The maximum boiler water supply temperature to the indirect heat exchanger must not exceed 240 deg. F
(115 deg. C).
Improper water quality will reduce the life of the water heater. Hard water, sediment, high or low PH and high levels
of chlorides in the domestic water should be avoided. Be sure that PH levels fall between 6 and 8 and dissolved
chlorides are less than 100 ppm. A filter must be used where sediment is greater than 5 microns in size in the water
supplied to the unit. A water softening system is recommended for areas with hard water. In cases where water
quality is unknown, a qualified water treatment expert should be consulted.