Heavy Duty Power Systems HDI 7000RWB User manual

OWNER’S MANUAL
AIR-COOLED DIESEL GENERATOR SET
Model HDI 7000RWB
Heavy Duty Power Systems
Phone#:208-949-1121

PREFACE
PREFACE
Thank you for purchasing products from our company .We appreciate your
business. The following manual is only a guide to assist you and is not a
complete or comprehensive manual of all aspects of maintaining and repairing
your generator. The equipment you have purchased is a complex piece of
machinery. We recommend that you consult with a dealer if you have doubts or
concerns as to your experience or ability to properly maintain or repair your
equipment. You will save time and avoid the inconvenience of having to go
back to the store if you choose to write or call us concerning missing parts,
service questions, operating advice, and/or assembly questions. Our air-cooled
diesel generators have some of the following features:
Lightweight construction
Air cooled
Four-stroke diesel internal combustion engine
Direct fuel injection system
Recoil starter or an optional electric starter
Large fuel tank
Automatic voltage stabilizer
NFB circuit protector
AC and DC outputs
Low oil pressure sensor
H.D brand air-cooled diesel generators are widely used when electrical power
poweris scarce. Our generators provide a portable mobile solution in supplying
for field operations during project construction. Some other known applications
include pipeline construction and metal welding when electrical power is not
available.
This manual will explain how to operate and service your generator set.
If you have any questions or suggestions about this manual, please contact
your local dealer or us directly. Consumers should notice that this manual
might differ slightly from the actual product as more improvements
are made to our products. Some of the pictures in this manual may
differ slightly from the actual product as well. H.D POWER
reserves the right to make changes at any time without notice and
without incurring any obligation.

TABLE OF CONTENTS
TABLE OF CONTENTS
Chapter 1 Technical Specifications and Data……………………….1
1-1 Technical specifications and data…………………………………….1
1-2 Basic operating parameters……………………………………………2
1-3 General dimensions and overview of the generators……………….2
Chapter 2 Operating the Diesel Generator…………………………...3
2-1 Main points of safety during operation of the generator..…………..3
2-2 Preparation before operation………………….………………………4
2-3 Checking the operation of the diesel engine….……………………..7
2-4 Starting the generator set…………………….………………………..7
2-5 Proper operation of the generator set……….……………….……….8
2-6 Loading……………………………….………………………………….9
2-7 Stopping the generator……………………………………………….10
Chapter 3 Maintenance……………………………………………………..11
3-1 Maintenance schedules………………………………………………11
3-2 Storing for long periods of time……….……………………………..12
Chapter 4 Troubleshooting…………………………….………………….13
4-1 Troubleshooting procedures…………………………………………13
4-2 Questions and doubts……………….………………………………..13
Chapter 5 Generator Parts Diagrams and Listings…….………..14
Chapter 6 Circuit diagram………………………………………………….20

TECHNICAL SPECIFICATIONS AND DATA
1
CHAPTER 1 TECHNICAL SPECIFICATIONS
AND DATA
1-1 Technical specifications and data
H.D Single-cylinder diesel generator
Model
Item HDI7000BD HDI 7000RWB
Rated frequency (Hz) 60 60
Rated voltage (V) 220、230、240、110/220、
115/230、120/240 380/220、400/230、420/240
Rated output power (kVA) 4.6 4.6
Max output power (kVA) 5.0 5.0
Rated rotation speed
(rpm) 3600 3600
Power factor cosφ1 1
Phase number Single
Pole number 2 3
Excitation
Transistorized self-excitation , Brushless self-excitation constant
voltage (AVR)
ATS type without ATS without ATS
Fuel consumption (g/kw.h) 340 340
Fuel tank capacity
(L)(US.gal) 14.5(3.8) 14.5(3.8)
Continuous running time
(hr)(at rated power) 8 8
Noise level [dBA/7m]
(zero load~full load) 69-74 69-74
Net weight (kg)(US.lbs) 165(363) 165(363)
Overall dimension
[mm](L×W×H)(US.inch)
920×520×700
(36.2×26.5 ×27.6)
920×520×700
(36.2×26.5 ×27.6)
Starter system electric starter electric starter
Fuel type 0# (summer),-10# (winter),
-35#(chill cold) diesel
0# (summer),-10# (winter),
-35#(chill cold) diesel
Lube oil brand CD or better than CD CD or better than CD
Engine model CF186F(E) CF186F(E)
Engine type
Single cylinder,
4-stroke,air-cooled,vertical,
diesel engine
Single cylinder,
4-stroke,air-cooled,vertical,
diesel engine
Bore × stroke(mm) 86×72 86×72
Displacement(cm3) 0.418 0.418
Compression ratio 19:1 19:1
Rated power
[kW(Hp)/rpm] 6.3(8.6)/3600 6.3(8.6)/3600
Max. power
[kW(Hp)/rpm] 7.0(9.5)/3600 7.0(9.5)/3600
Rotation direction(from
the flywheel) clockwise clockwise
Note: Get this power only after 30 hours’ initial run.
Single

OPERATING THE DIESEL GENERATOR
1-2 Basic operating parameters
1-2.1 Under the given conditions, the generator will output
the specified power in the table listed below.
Table 1
Height above sea level (ft) Ambient temperature (
o
F) RH
0+60 (+20
o
C) 60%
<3280.8 (<1000 m) 41~104 (5-40
o
C) 90%
1-3 General dimensions and overview of the
1-4 Operation Instruction
generators
1-3.1 HDI 7000RWB dimensions of the series generator.
Turn the switch “POWER” and circuit breaker switch “AC SW” to “OFF” position.see figure 1
as following:
Figure 1
2

Fill in small sum of fuel into the fuel tank, make sure fuel pipe is connected properly, and no
leakage in fuel supply system. Fill in fuel to proper level.
Connect the positive(+) battery cable to the battery positive(+) terminal. Connect the other end of
the positive (+) battery cable to the generator positive (+) terminal.
Connect the negative (-) battery cable to the battery negative (-) terminal. Connect the other end of
the negative (-) battery cable to the generator negative (-) terminal.
1-4.1 How to start generator’
Turn the switch “POWER” to “ON” position. The controller is energized. It indicates “000V” by
LED screen. Connect the plug of electrical appliances to the socket on the generator panel. Press
the green button “ON” , the generator will start automatically. AC voltage is indicated by
LED after generator starts.
Press the yellow button “MENU” , real-time voltage, currency, frequency and cumulative
time is indicated orderly. Indicator lights of frequency and cumulative time will turn on in the
right part of the panel.
If you need 120V AC output, please turn the transfer switch left to “120V” position, and turn
circuit breaker to “ON” position. If you need AC 120/240V, please turn the transfer switch right to
“120/240V” position, and turn circuit breaker to “ON” position.
When you use the transfer switch, please turn circuit breaker to “OFF” position at first.
1-4.2 How to stop and reset generator
Take off the load of generator; turn the circuit breaker to “OFF” position. Press the red button
“OFF” , the generator will stop automatically. Then turn the switch “POWER” to “OFF”
position.
When generator fails to start or when error happens, alarm light will stay on in the controller
module, and fault code will be displayed in the LED. The fault code will tell you the probable
reasons. Press the red button “OFF”, reset the module, remove the fault code, and alarm light goes
out at the same time. Re-start the generator after the fault is cleared.
If you want to lay the generator idle for a long time, please drain the fuel, disconnect the battery
before the generator is put away.
3

E01—start failure(Starting directive is sent to controller, but generator fails to start. The generator
will not try to start generator before fault is cleared)
E02—voltage > 250V (The data is detected 5 seconds after generator starts)
E04—frequency >67Hz (The data is detected 5 seconds after generator starts)
E05—frequency<53Hz (The data is detected 5 seconds after generator starts)
E06—battery voltage >19V (The data is detected before starting,. The generator can not start if
fault is inspected)
E07—battery voltage <10.5V (The data is detected before starting. The generator can not start if
fault is inspected)
E08—low oil pressure
1-4.3 Fault code
4

OPERATING THE DIESEL GENERATOR
5
CHAPTER 2 OPERATING THE DIESEL
GENERATOR
2-1 General main points of safety during
operation of the generator set.
In order to operate the generator set safely, please follow all the instructions
provided in this manual carefully. Doing so otherwise may lead to accidents or
equipment damage.
2-1.1 Fire prevention
The proper fuel for the diesel generator set is light diesel fuel. Do not use
gasoline, kerosene or other fuels other than light diesel fuel. Keep all
flammable fuels away from the generator as the generator may spark and
ignite these gases. In order to prevent fires from occurring and to provide
enough ventilation for people and the machine, keep the diesel generator at
least 1.5 meters away from buildings and or other equipment. Always operate
your diesel generator on a level site. If the generator is operated on an incline,
the lubricating system within the engine will not perform well and may lead
to failure of the engine.
2-1.2 Prevention from inhaling exhaust gases.
Never inhale exhaust gases emitted by the engine. The exhaust gases
contain toxic carbon monoxide. Never operate your generator in places with
poor ventilation. In order to operate this machinery indoors, a suitable
ventilation system for the building is required to draw the poisonous exhaust
gases out.
2-1.3 Prevention from accidental burns
Never touch the muffler and its cover when the diesel engine is running. Never
touch the muffler and cover after the diesel engine has been used, as the
muffler remains hot for a good period of time.
2-1.4 Electric shock and short circuits
Never touch the generator if the generator is wet. Also never touch the
generator if your hand is wet. Never operate your generator if the weather
conditions call for any type of precipitation such as rain, snow, or fog. To
prevent electrical shocks, the generator should be grounded. Use a lead to
connect the grounding end of the generator to the grounding surface of choice.
Please refer to Fig. 2-1 before beginning to use the electric generator.
Fig. 2-1
Note: When connecting devices to
the generator, make sure all
other devices are rated lower
than the generators output.
Any generator socket should
not be overloaded over its
regulated limit.

OPERATING THE DIESEL GENERATOR
6
2-1.5 Other safety points
Before operating this generator, all operators should have a good knowledge of
how to break the circuit if any accidents occur. Also, all operators should be
familiar with all the switches and functions of the generator before using this
machine. While operating the generator, wear safe shoes and suitable clothes
during operation. Always keep children and animals away from the generator.
2-1.6 Battery
The electrolytic liquid of the battery also known as battery acid contains sulfuric
acid. In order to protect your eyes, skin, and clothing, wears protective gear
when working with the battery. If you come in contact with the electrolytic liquid,
wash it immediately with clean water. Also, if the electrolytic liquid comes in
contact with your eyes, see a doctor immediately.
2-2 Preparation before operation
2-2.1 Fuel choices and fuel treatment
Fuel tank
Use only light diesel fuel. The fuel should be filtered clean. Never let dust and
water mix with fuel in the fuel tank. Otherwise it will clog the fuel lines and oil
nozzles. It may also damage your pressure pump.
Note: It is dangerous to overfill the fuel tank. Never exceed the red
piston in the filter.
Type HDI 7000RWB HDI 7000RWB
The effective volume of
fuel tank: (L)(US. gal)
14.5
(3.8)
14.5
(3.8)
a. After purchasing fuel, put it into a drum and let it sit for 3-4 days.
b. 3-4 days later, insert half of the fuel sucker into the drum, (water and
impurities stay in the lower portion of the drum)
Air filter element
Do not wash the air filter. The element is
made of dry material, which does not permit
washing. When the output of the diesel
engine is bad or the color of the exhaust gas
is abnormal, replace the air filter element.
Never start the diesel engine without the air
filter.
NOTE: Never smoking near the
opening of the fuel tank. Do
not let sparks get near the
fuel or fuel tank and do not
overfill tank. After filling,
tighten the fuel cap.
A
ir filter

OPERATING THE DIESEL GENERATOR
7
2-2.2 Filling engine oil
Remove the dipstick from the engine
Make sure the generator is on level ground, and fill the engine with 15W40
engine oil. Put the dipstick back into the hole to check the engine oil level.
Engine oil is the most important factor in determining the life of your generator
engine. If you use poor engine oil or if you don’t change the oil regularly, the
piston and cylinder will wear easily or seize up. Also, the life of the other parts
in your engine such as bearings, and other rotating parts will shorten
considerably.
Although there is an alarm system to check for low oil pressure, it is always a
good idea to check the amount of oil inside the engine. If the oil level is low, fill
it before starting the engine. A good time to drain the oil from the engine is
when the diesel engine is still hot. If the engine is fully cooled, it is more difficult
to drain all the oil out or some impurities will remain in the engine.

OPERATING THE DIESEL GENERATOR
8
2-2.3 Checking the air filter
(1) Loosen the butterfly nut, take the cover
of the air filter off and take the air filter
element out.
Do not use detergent to wash the air filter
element. When the performance of the
engine decreases or when the color of the
exhaust gases is bad, exchange the filter
element. Never start the engine without
the air filter as foreign objects may enter
the intake and damage the engine.
(2) After replacing the air filter element,
replace the cover and tighten the
butterfly nut firmly.
Use dry compressed air (with pressure about 1.96 x 105 Pa) to blow the dust
out in the electric control cabinet and at the surface of the generator. Check to
see how clean the surface of the sliding ring is. Check the pressure of the
carbon brush. Also, check whether the position of the carbon brush at the slide
ring is correct and the fixture is reliable with a good contact.
According to the electric wiring diagram, check to see whether the connecting
wire is correct and the connected place is firm.
Use a 500 M Ωmeter to measure the insulation resistance of the electrical part.
The resistance should be no less than 5M Ω. When measuring devices, make
sure the AVR is turned off. Otherwise, it will burn the AVR. (For the low noise
set, the inspection may not be performed).
2-2.4 The fuel and oil in a new engine is drained before sold. Before you start
the engine, please fill the fuel tank and engine oil first. Then, check to see
if there are air bubbles in the engine. If there are, follow these procedures.
Loosen the connecting nut between the fuel injector pump and fuel pipe.
Bleed the air from the system until there are no more bubbles. Then
replace the connecting nut and tighten it.
Air filter
Air filter cover

OPERATING THE DIESEL GENERATOR
9
2-3 Checking the operation of the diesel engine
2-3.1 Low-pressure alarm system.
H.D diesel engines have a low-pressure sensor system where if the oil pressure
drops too low, the sensor will shut the engine off. The purpose of having this
system is to ensure that the engine does not seize up. If there is not enough oil
in the engine, the temperature of the oil will be raised too high. On the contrary,
if there is too much oil in the engine, the engine oil can slow the engine down
considerably.
2-3.2 How to open the case door/cover
(1) Open the case door: Pull the
handle outward and open the
door. Do these checks daily.
(2) Loosen the outer cover bolt of
the air filter and outer cover of
the oil nozzle, and then check
the air filter.
(3) Check the outer cover of the
oil nozzle. Loosen the butterfly
nut and open the outer cover.
2-3.3 Engine break in
When you purchase a brand new engine, the engine must be properly broken
in. The break in period is about 20 hours.
(1) Avoid overloading the engine when brand new
(2) Change the engine oil according to specifications. An oil change for a brand
new engine is about 20 hours or every month, an older engine, the oil
change is about 100 hours or three months.
2-4 Starting the generator set
2-4.1 Starting.
Start the engine in accordance with procedures below:
(1) Open the front door to put the speed handle
to right side, namely “on” position.
(2) Turn the ignition switch of the engine to the
“Start” position for 1~2 seconds.
(3) After starting the engine, loose the ignition
switch and it will return to “On” position
automatically, the engine start to work.
(4) If fail to start, please restart the engine as
above steps after 15 seconds.
Knobhandle

OPERATING THE DIESEL GENERATOR
10
2-4.2 Battery
1. Insert key into ignition and put it in the “off” position.
2. Put the speed handle in the “Run” position.
3. Turn the start switch clockwise to the “START” position.
4. After the diesel engine is started, remove your hand from the switch handle;
the switch will automatically reset itself to the “ON” position.
5. If the engine is not starting after 10 seconds of cranking, wait about 15
seconds before trying it again. If you crank too long, the voltage of the
battery will drop. This can lead to improper ignition. When the diesel engine
is operating, let the ignition retain on the “ON” position.
Note: If you crank the starter too long, the battery may be drained too
much to provide enough energy for proper engine ignition.
Also, when the diesel engine is operating, let the key retain in
the “ON” position.
Important Notice:
All of our units come with a
maintenance free battery. You do not
need to add any battery acid.
2-5 Proper operation of the generator set
2-5.1 Operating the diesel engine
1. Pre-heat the diesel engine for 3 minutes under
no load conditions.
2. First check the height of the lubricating oil level,
if it is low, refill it. Our diesel engines are
equipped with an alarm system that will notify
you if the oil pressure is too low. The alarm
system will shut down the engine if the oil
pressure is too low.

OPERATING THE DIESEL GENERATOR
11
3. Do not adjust the speed limit regulation bolt or
the fuel adjustment bolt. These bolts have been
set by the factory already, changing them will
affect the properties of the engine performance.
2-5.2 Checks during engine operation
1. Check to see if there are abnormal noises.
2. Check to see if the performance is good or bad
3. Check the color of the exhaust gases (whether it is too black or too white).
If any of these conditions exist, stop the engine and find the cause of the
problem. If no problems are found, please contact your local dealer or our
nearest company branch.
2-6 Loading
2-6.1 Load conditions
Exert loads in accordance with the specified parameters.
2-6.2 Output of electricity
1. Raise the revolutions per minute (turn the speed handle to the max setting)
of the generator to get the maximum power out of the generator. If not, the
automatic voltage regulator device will excite and doing this for long periods
of time will cause the AVR to burn. For the rated speed of the generator,
please refer to Chapter 1, item 1-1 technical specification and data.
2. Observe the pointer of the voltmeter; it should point to 240 V 5% (60Hz).
Meanwhile put the switch in the GEN (generator) position. The AC voltage
from the socket of the power supply can be output.
3. When connecting devices to the generator, make sure to connect these
devices in order. Connect the large loads onto the generator first. If
everything is functional, smaller loads can then be added. If the generator
shuts off, it may be because the load being drawn by all the various devices
are too high. In this event, decrease the number of small devices until
everything is functional. The total drawn power should not exceed the
maximum output power of the generator. Please see Table 1-1 for technical
specifications of what the generator can output. In order to reset the
generator after overdrawn power, let it sit for several minutes. If the
indication of the voltmeter is too high or too low, adjust the speed
accordingly. If there are problems, stop the generator immediately and fix
the issue.
4. During operation, the generator should be in a place that has very good
ventilation. Never cover the engine to solve a ventilation problem, as this
will damage your equipment.
Note: Do not start more than two devices simultaneously. Each
device should be started one by one to prevent overloading the
generator.
The generator should be running at 3600 revolutions per minute
in order to achieve the (60 Hz) frequency. The speed of the
engine can be adjusted from the speed governor.

OPERATING THE DIESEL GENERATOR
21
2-6.3 Charging the battery
1. For the electric starter on the generator sets, the 12V battery is automatically
charged through the regulator on the side of the engine when it is running.
2. If the generator is not used for long periods of time, the battery should be
disconnected to avoid energy loss from the battery.
3. Do not connect the negative and positive terminals of the battery together at
any time. Doing so will damage the battery and cause serious injuries.
4. Do not reverse the polarities when attaching the battery cables to the battery.
Doing so will damage both the battery and the electric starter.
5. When charging the battery, the battery produces flammable gases. Do not
smoke, let flames, and sparks get near the battery while it is charging as
this may cause a fire.
To avoid sparking while connecting the cables to the battery, first, connect the
cables to the battery then to the motor. To disconnect battery cables, first
disconnect the motor end of the cable.
2-7 Stopping the generator
1. Take the electrical load off the generator.
2. Put the speed handle in the “RUN” position and let the engine run for 3
minutes after unloading. Do not stop the diesel engine immediately let it
warm down. Stopping the diesel engine suddenly may raise the
temperature of the engine abnormally and lock the nozzle and damage the
diesel engine.
Note:
1. If you cannot stop the engine with a
load on it, then remove the load first
than stop the engine.
2. Press down on the brake handle.
3. If equipped with an electric starter, turn
the key to the “Off” position.
4. Put the fuel handle to the “S” position.

MAINTENANCE
31
CHAPTER 3 MAINTENANCE
3-1 Maintenance schedules
Keeping your generator well maintained will prolong the life of your generator. Everything
needs tobecheckedincludingthe diesel engine, generator,controlcabinet, andframe. For
overhauling procedures, please refer to the instruction manual of the relative subassembly.
Ifyouneedthesemanuals,pleasecallourcompanyandwewillsendyouone.
Before starting the maintenance, make sure the diesel engine is off.
Please refer to the Table 3-1 for the proper maintenance schedule.
Table 3-1. Maintenance schedule for diesel generator set
Time
Item Everyday After 1 month
or 50hours Every3month
or 200 hours Every 6 month
or 400hours Every 1year
or 1000hours
Check the fuel
level and refill ○Before
starting
Drainthefueltank ○
Check and fill
enoughengineoil ○
Cleanthefuel filter ○
Check fuel oil
leakage ○after every
operating
Check and
screw each
fastened part ○●screw the
bolt of
cylinder head
firmly
Check injector ●
Check injection
pump ●
Check fuel pipe ●If necessary
exchangeit
Check the lube.
oil level in the oil
pan and refill
○before
starting
Replace the
lube. oil ○the first time ○the second
time and
afterward
Clean lube. Oil
filter ○the first time ○the second
time and
afterward
Check the air
cleaner element ○the first time ○the second
time and
afterward
Change the
core of air filter If damaged or smeary , change it in time
Check the
battery liquid
level and refill ○
Adjustingthe intake
and exhaust valve
clearance ●the first time ●the second
time and
afterward
Grindairintakeand
airexhaustedgate ●
Exchange piston
ring ●
Check electric
brushandslidering ●
Check insulation
resistance The time of stop is over 10 days ○
Note: the quality period of the injector and injection pump is 1500 hours
or two years. Thereinto,●meansitshouldoperatewithspecialtools,orcan
becheckedbydealer.

MAINTENANCE
41
3-1.1 Changing the engine oil (every 100 hours)
Take the oil cover off. Remove the oil drain plug
when the diesel engine is still hot. Be careful of
hot oil and hot engine as you may get burned.
The bolt is located at the bottom of the cylinder.
After draining the oil, put the bolt back and
tighten it. Then fill with the proper engine oil to
the proper level.
3-1.2 Air filter maintenance schedule
1. Clean air-filter every 6 months or 500 hours of operation.
2. If necessary, exchange it.
3. Do not use detergent to clean air filter element.
Note: Never start the engine without the air filter. This can cause
serious damage to the engine if foreign objects enter the intake
system. Always change the air filter on time.
3-1.3 Fuel filter maintenance
1. The fuel filter should be cleaned often to keep the engine running at maximum
performance.
2. The recommended time period for cleaning the fuel filter is 6 months or 500
hours of operation.
a. To do this, first drain the fuel from the fuel tank.
b. Loosen the small screws on the fuel switch and remove the fuel filter
from
the port. Use diesel fuel to clean the fuel filter. Also, remove the fuel injector
and clean the carbon deposit around it. The recommended time period for
this is 3 months or 100 hours.
3-1.4 Cylinder head bolt tensions
The cylinder head bolts should be tightened to specifications please refer to the
diesel engine manual for specifications and the special tools required to do this.
3-1.5 Battery check
Make sure the battery acid is full. The engine uses a 12V battery. Due to
numerous starting cycles, the battery acid may be used up. Also, before filling,
verify that the battery is not damaged in any way. Add distilled water to the
battery when filling. Perform checks on the battery once a month.
3-2 Storing for long periods of time
If your generator needs to be stored for long periods of time, the following
preparations should be made.
1. Start the diesel engine for 3 minutes then stop it.
2. When the engine is still hot, change the engine oil with new engine oil of the
proper grade.
3. For electric started generator, press the decompression handle down and
crank the engine for 2-3 seconds. To do this, put the starter switch in the
“Start” position. (Do not start the diesel engine)
4. Clean the engine and store it in a dry place.

TROUBLESHOOTING
51
CHAPTER 4 TROUBLESHOOTING
4-1 Troubleshooting procedures
Causes of malfunction Remedy
Not enough fuel Add enough fuel
The switch of fuel is not at
“OPEN” position. Turn the switch of fuel to “OPEN”
position.
High-pressure pump and nozzle
do not inject fuel or the injected
amount is less.
Disassemble the nozzle and adjust it
at test table.
Speed control lever is not at
“RUN” position. Turn speed control lever to “RUN”
position.
Check level of lubrication oil.
The standard oil amount of
lubricating oil should be between
high graduation “H” and low
graduation “L”.
It is not quick and powerful to pull
reactive starter.
Start diesel engine in accordance
with the requirements of “start
operation procedures”.
Nozzle exist dirt. Clean the nozzle.
Diesel cannot be started.
Accumulator has not electricity. Charge the accumulator or
exchange it.
Master switch (NFB) is not be
switched on. Turn master switch handle to “ON”
position.
Carbon brush of generator was
worn. The contact is bad. Exchange the carbon brush.
The contact of socket is bad. Adjust the contact feet of socket.
The rated revolution of engine
cannot be reached.
Make it reach to the rated revolution
in accordance with the
requirements.
AVRautomaticgovernorisdamaged. Exchange it.
Generator cannot generate
electricity and has not welding
voltage
The potentiometer of current
regulation for electric welding is
damaged. Exchange it.
If you are still having trouble, please contact with your nearest dealer or with
our company directly if necessary.
4-2 Questions and doubts
If you do not understand anything or have any questions, please feel free to
contact your local dealer or with our company directly. Below is a list of some
information you should have ready before contacting your local dealer or us.
1. Model of diesel engine generator and engine model number.
2. State of residency.
3. Number of hours of operating equipment along with the problem that occurred.
4. A detailed condition and time when the problem occurred, in other words,
climate and atmosphere.

GENERATOR PARTS DIAGRAMS AND LISTINGS
61
CHAPTER 5 GENERATOR PARTS
DIAGRAMS AND LISTINGS
Figure 5-1. Overall view of engine generator assembly

GENERATOR PARTS DIAGRAMS AND LISTINGS
71
Table 5-1. Please refer to figure 5-1 for illustration
No Part Description
Quantity
Part Code
1 Silencer cover 1
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
HDI 7000RWB-
2 Silencer bend 1 002
001
3 Left board of cover 1 003
4 Back door of cover 1 004
5 Fixing sleeve for observing bore 1 005
6 Fixing sleeve for input of fuel tank 1 006
7 Main cover 1 007
8 Switch of front door 1 008
9 Air filter baffle 1 009
10 stationary rings of generators 1 010
11 Right board of cover 1 011
12 Output panel assembly 1 012
13 Cover of observing bore for air filter 1 013
14 Cover of fuel tank assembly 1 014
15 Buoy for oil level indication 1 015
16 Fuel tank(not assembly) 1 016
17 Lining of absorbing mat 4 017
18 Shock absorbing mat 4 018
19 Clipφ94 019
20 Clipφ13 4 020
21 Fuel inlet pipeⅠ(φ13) 1 021
22 Fuel filter assembly with cover 1 022
23 Fuel inlet pipeⅡ(φ13) 1 023
24 Fuel leak-off pipe 1 024
25 Cover of U-type chamfer 1 025
26 U- type chamfer 1 026
27 Support of U-type chamfer 1 027
28 Moire output pipe 1 028
29 Gasket of silencer 1 029
30 Upper silencer 1 030
31 Low silencer 1 031
32 Back cover of alternator 1 032
33 Bracket of classis 1 033
34 Shock absorbing mat of generators 4 034
35 Tow structure 1 035
36 Rectify bridge 1 036
37 Wiring seat3×2 1 037
38 Battery cable(set) 1 038
39 Chassis 1 039
40 Rolling wheel on chassis(4 inch) 4 040
41 Flat washer 8 041
042
452×3niP24
43 Motherboard of accumulator 1 043
44 Accumulator (maintenance free) 1 044
45 hook type bolt of battery 2 045
46 Pressing plate of accumulator 1 046
Table of contents
Popular Inverter manuals by other brands

Eaton
Eaton PowerXL DF1 Series user manual

Clenergy
Clenergy PV-ezRack SolarRoof installation manual

SunSynk
SunSynk SUNSYNK MAX user manual

Marconi Instruments
Marconi Instruments 2040 operating manual

Victron energy
Victron energy Phoenix 12/800 user manual

Sherman Workshop
Sherman Workshop MIG 200M user manual