
1. About the Controller
HMpro controllers operates 24volt AC solenoid valves. The HM12pro can operate a maximum of 12
valves, the HM16pro a maximum of 16 valves. The HM144pro can operate 16 valves as standard and
up to 144 valves with the addition of expansion cards.
The controller will run the valves for the length of time, and in the order you specify. This sequence of
running solenoid valves is known as an irrigation program.
Irrigation programs can be started automatically at pre-set start times. Alternatively, an irrigation
program, a single solenoid valve or the pump, can be started manually at any time.
2. Installation
WARNING Installation should be carried out by a qualified Electrician.
Mounting the Controller
The controller should be mounted on a wall using four screws, one screw through each corner lid
bolthole.
Warning: Additional holes should not be drilled through the controller casing.
Do not mount the controller in direct sunlight. Do not mount the controller where it can be exposed to
temperatures above 45 deg C.
Wiring Up Your Controller
The HM12pro, HM16pro and HM44pro controllers should be wired up as shown in Fig 1.
For an HM144pro with more than 16 valves, connect the output expansion box to the expansion box
connectors. You can use either connector.
Connecting Mains Supply
IMPORTANT. Switch off the mains supply before connecting the controller.
Check that the MAINS SUPPLY VOLTAGE IS THE SAME AS THE VOLTAGE OF THE
CONTROLLER. The controller voltage is displayed on the inside the controller casing.
The mains supply should be fused with a 3-amp fuse and be connected via a Residual Current Circuit
Breaker as per any equipment used in damp conditions.
Connect the mains supply to the three terminals inside the IEC plug Live to L, Neutral to N and Earth
to E as shown in Figs 1 and 2.
Wire the controller directly back to the main distribution panel. This is particularly important when
large pumps or inductive electrical loads are also used.
Connecting Solenoid Valves
Connect each solenoid valve to the appropriate output as shown in Figs 1 and 2. The common wire
from each solenoid valve should be connected to the "C1" terminal. Valves can be connected in
parallel provided the maximum valve output current does NOT exceed the output current rating of the
controller.