RT226-F8 FCU THERMOSTAT
Function Description
Cooling mode:Heating mode:
The relationship between the output PI and temperature difference ( room temperature and setting
temperature)
If we set the P-band is 2℃, when the room temperature is higher 2℃than the setting temperature, the terminal 11
will 100% output, the cooling equipment actuator will 100% open; when the room temperature is equal or lower
than setting temperature, the terminal 11 will stop output(0% output), the cooling equipment actuator will fully
close. The LCD will display the current output PI value.
Fan and the first section mark show 10-40%, fan and the second section mark show 41-70%, fan and the third
section mark show 71-100%.
The operation mode is total three: cooling, heating, auto。
After connecting the external sensor, in the auto mode, when the difference of the inlet air temperature and room
temperature is 5℃, the mode automatically switch。When the inlet air temperature is high 5℃than the room
temperature, it will switch to heating, if lower than 5℃, it will switch to cooling.
When in the auto mode, if the external sensor is not connected, it will switch to other mode forced(room
temperature is high than 25℃, it will be heating mode. Otherwise, it will be cooling mode)。
Room card function
When the terminal 12 and 13 connect with the room card input signal, the room card input signal control the
thermostat into the economical mode, show 。When in the economical operate mode, the setting
temperature is depended on the 8 item and 9 item in the initialize menu. The room card ON or OFF is still
depended on the 10 item of the initialize menu. The input of the room card is node signal, the maximum voltage is
5V DC。
Analog output choose the wire jumper
Open the thermostat,the cover of the wire jumper lie the below of the thermostat
As the following figure show,the analog output of the wire jumper’s choose.
0~10V output 4~20mAoutput