
CLX-Ex (9/11) Page 4
REV 1.6
3.0 Installation and Commissioning
3.1 Air Supply
This instrument requires Water and oil free air, -40oC (-40oF) Dew Point, Particles <5u, ISA
Grade Hydrocarbon Free. Fulltime clean dry air at 5.5 - 7 bar (80-101.5 PSI) @ 112 SLPM
(4 SCFM) @ 20oC (68oF) Max. is required. This air supply must be provided continuously
from a known safe area.
The air connection requires 6 mm stainless steel tubing. A compression type fitting is
supplied that simply requires the installer to slip the supplied nut and feral over the tubing
and then tighten the nut.
3.2 Electrical Connections
The power cable enters cabinet through a grommet. The power cable diameter must be
selected to ensure that this connection is tight. The grommet can accept cabling from 9 to 17
mm diameter. This grommet must be tightened to maintain cabinet air pressure.
The electrical power for the protective gas supply (blower, compressor, etc.) should be
either taken from a separate power source or taken from the supply side of the electrical
isolator for the pressurized enclosure.
Only qualified electricians should be allowed to perform the installation of the
instrument as it involves a line voltage that could endanger life.
3.3 System Power
The Purge Control X-Purge controller requires 220-240
VAC 47-63 HZ.
A total power requirement of 250VA; please verify that the
line voltage falls within these specifications. A circuit
breaker must be placed prior to the power connection in
close proximity and within easy reach to allow for service.
This circuit breaker must be marked to indicate that it is a
disconnecting means for the instrument.
Supply power connections are made ONLY to the back of
the Purge Control X-Purge controller:
Terminal 1: Line or Hot connection
Terminal 2: Neutral
Terminal 3: Ground
Suitable wire would be stranded, 3 conductors 18-12 AWG
copper or tin plated copper with a voltage rating of
600VAC with a temperature rating of 90 ˚C or higher.
Common earth bond points are provided both inside the
enclosure on the chassis and outside of the enclosure.