Hisense Hi-Dom Quick guide

Hi-Dom
Installation Configuration and
Maintenance Manual

Preamble
●This product is air-conditioning centralized monitoring and management system Hi-Dom. The
system includes air-conditioning adapter, meter concentrator and service software.
●This air-conditioning adapter requires server (server installed with software which should be
bought from field sales) in concert with Ethernet or Internet for use.
●Do not install the machine in the following locations, such as the places filled with gas or oil
droplets, prone to cause fire, deformation, corrosion and damage to the machine.
○Places with oil (including machine oil) splashes and steam.
○Places such as springs with sulfide gas
●Do not install in the following locations, as this may cause corrosion.
○coastal place with high salinity
○acidic or alkaline environment○areas with high humidity
●Do not install in the following locations, as this may cause a malfunction or fault.
○Exposure to direct sunlight.
○places at high temperature.
○places flooded with water.
○places with poor ventilation
●When installed near the machine emitting electromagnetic waves, note that the electromagnetic
wave emitting surface of the machine should not directly face this unit.
●To avoid the influence of electromagnetic waves, make sure the machines generating
electromagnetic waves, such as radio, etc are kept 3m or more away from this unit.

1. System Components
1.1 Connection scheme
The connection scheme of this system is shown in Figure 1.1. This manual only describes the
installation and configuration of Hi-Dom system, for other units in the system, please refer to the
respective operating instructions supplied.
Figure 1.1 Connection scheme
※One air-conditioning management server can connect up to 32 air-conditioning adapters.
※One air-conditioning adapter can connect 128 indoor air conditioners (the number of outdoor
units linked should not be bigger than 64,the united outdoor device composed of more modules
is also treated as 1 outdoor unit).
※A single system can connect 4096 indoor units.
1.2 Name of aircondition adapter parts

Figure 1.2 LED indicators
1.2.1 Description of LED indicators
POWER
Power display LED (red)
it is on when the unit is power-on
H-NET
Air-condition side communication
display LED (yellow)
flashing when a signal is transmitted
from H-NET system
RUN
working status display (green)
it is on when initialization and flashing
during normal operation
485TX
RS485 signal output(yellow)
flashing when this unit has signal
transmitted from RS485 interface
485RX
RS485 signal output(yellow)
flashing when there is signal transmitted
from RS485 interface to the unit
STAT
status indicator (green)
it is on when completing factory reset
/without H-NET access
RESET
reset button

Figure 1.3 Terminal marking diagram
1.2.2 Terminal marking instruction
①: Power input(DC12V)-------------Non-polarized
②: Power input(DC12V)-------------Non-polarized
③: H-NET signal input ---------------Non-polarized
④: H-NET signal input ---------------Non-polarized
⑤: RS485 A ----------------------------positive
⑥: RS485 B ----------------------------negative
⑦:USB(DC5V)
⑧: LAN interface
※DC12V and DC5V power supply can not simultaneously access.
1.3 Specifications of aircondition adapter
The hardware specifications of this unit are shown in Table 1.1; communication specifications are
shown in Table 1.2 and Table 1.3.
Table 1.1 Hardware Specifications
Item
Specification
Power Supply
DC 12V
Power consumption
Below 1.5W
Environmental conditions
Ambient temperature:0~40℃
Ambient humidity:20~85%( non-condensing)
Dimensions
Length:180mm Width:110mm Height:40mm
Weight
0.55kg
Installation conditions
Using screws or guide rail for indoor installation
Horizontal (installation) / vertical (wall-mounted)
Table 1.2 H-NET (communication wiring) Communication specifications
Item
Specification

Communication objects
Air-condition outdoor unit and indoor unit
Communication wiring
Non-polarized 2 core wire
Communication mode
Half-duplex communication
Communication synchronous
mode
asynchronous communication
Communication speed
9600 bps
Wiring distance
Total length less than 1000m
Number of air conditioners
connected
128 indoor units
Table 1.3 LAN(Ethernet) Communication Specification
Item
Specification
Communication objects
air conditioning management server, switch
Communication wiring
LAN(Ethernet)
Communication mode
IEEE802.3 standard(10BASE-T/100BASE-TX)
Wiring distance
100m
2. Air-conditioning adapter installation and wiring
2.1 Installation site
Please choose a place that meets the following conditions to install the unit.
○Please choose the site as specified in the [preamble] of this installation manual.
○This unit is to be mounted in the weak current control box.
Figure 2.1 Installation diagram

2.2 Installation and wiring instructions
(1) Air Conditioning adapter and meter adapter needs to be installed in the weak current control
cabinet with screws for vertical mounting and guide rail for horizontal installation, in case of
vertical installation with screws, certain gap is to be left for 30~50mm wiring around the adapter.
(2) Communication and power supply terminals are barrier terminal blocks, rotate the terminals
counterclockwise with appropriate Phillips screwdriver, then insert the wire into the terminal and
rotate the terminal clockwise, wire installation is complete.
(3) Refer to the air-conditioning wiring requirements for the wiring of air conditioner side.
(4) LAN interface is RJ45 interface, insert it directly into LAN interface.
Figure 2.2 Wiring diagram of air condition adapter
For wiring specifications of air condition adapter in Figure 2.2 Wiring diagram, see Table 2.1
Wiring Specification of air condition adapter
Table 2.1 Wiring Specification of air condition adapter
No.
Wiring type
Voltage
specification
between lines
Usage of wiring
Distance
of wiring
Cable
Specification
1
power supply
wiring
DC 12V
For power supply to
air conditioning
adapter, a must-have
——
0.75~1mm2
2
H-NET wiring
DC 5V
For communication
with
air-conditioning, a
must-have
Within
1000m
0.75~1mm2
3
RS485
communications
wiring
DC 5V
For communication
with ModBus and
other external
communication
control equipment,
optional
Within
1000m
0.75~1mm2

4
micro USB
wiring
DC 5V
For power supply to
Data Collector,
optional
Within
1m
5
LAN wiring
IEEE 802.3
standard
For communication
with management
server, a must-have
Within
100m
LAN(UTP-five)
3. System installation configuration and debugging
3.1 Service software installation
※service software latest version can be downloaded from the website www.achelp.cn,
username: admin, password: admin.
One-click installation, double-click the installation package, as shown in Figure 3.1:
Figure 3.1 Installation start interface
Click “Next” until the end of the installation, as shown in Figure 3.2:

Figure 3.2 Installation completion interface
After installation is completed, login screen is automatic pop-up as shown in Figure 3.3, click on
<Set the default browser> in the page, this browser is set as the default browser, a shortcut login
system will be automatically created on the desktop. The default username of this system is admin,
password is admin.
When first installed, the page pop-up takes 1 to 2 minutes, please be patient.
Figure3.3 Login screen
3.2 IP address setting
3.2.1 Air-conditioning centralized management server IP address setting
Due to different operating system of air conditioning centralized management server, refer to the
IP address setting instructions of relevant operating system for its IP setting, but the IP address of
the server must be in the same network segment with the IP address of air conditioning adapter.

The so-called same network segment refers to the first 3 segments of the IP address are the
same(subnet mask: 255.255.255.0 is supposed),, for example, the first three segments of
192.168.1.2 and 192.168.1.101 are “192.168.1”, so 192.168.1.101 and 192.168.1.2 are in the same
network segment.
3.2.2 Air-conditioning adapter IP address setting
The factory default IP of air conditioning adapter is set as:
IP address:192.168.1.101
Subnet mask: 255.255.255.0
Default adapter: 192.168.1.1
When used on site, the IP address of the air conditioning adapter is re-set according to network
configuration on the site.
How to set the IP of air conditioning adapter:
1. First, prepare a server for air conditioning adapter IP address setting (laptop of debugging
personnel or air conditioning centralized management server), set “Local IP” address of the server
to:
IP address: 192.168.1.2
Subnet mask:255.255.255.0
Default adapter:192.168.1.1
2. Power on the adapter to be set, waiting for the adapter getting into working state (“RUN”
indicator flashes, without considering other indicators),
3. Connect the server for setting directly to the air-conditioning adapter with a network cable,
enter the IP address of the air-conditioning adapter in the server web browser address bar:
192.168.1.101, press carriage return, the browser displays the login screen as shown in Figure 3.4:
Figure 3.4 Setting and debugging login screen
4. Enter the user name: admin, with no password, click on the login, the interface appears
after login as shown in Figure 3.5.

Figure3.5 Setting and debugging
Click <Network Settings> into the IP settings interface, as shown in Figure 3.6 (other options have
nothing to do with IP address setting, do not change, otherwise it will lead to consequences of
unable to return!)
Figure 3.6 Network Settings screen
5. According to the site conditions, it only needs to change <LAN IP Address> and <Remote
Server IP Address> to change the settings of the IP address, <Remote Server IP Address> is the
server IP address for installing air-conditioning system management software. Click <Change>
button, as shown in Figure 3.7, the system prompts to confirm the information. Click <OK>, the
air conditioning adapter IP address change is completed.
Figure 3.7 Network settings confirmation interface
Note:
※If in need of check settings or re-set, enter the new set IP address in the browser address
bar to enter the setting interface, or it cannot be logged in, for example, if the IP address
is changed from factory setting of 192.168.1.101 to 192.168.1.105, it will display a
prompt of inability to log in when entering 192.168.1.101 in the address bar, you need to
enter the new address 192.168.1.105 to re-enter the adapter setting interface, so after

setting the IP address, the new IP address must be marked on a tag attached to the adapter
to facilitate future maintenance.
※Pay attention to the sequence of this operation, first set the computer’sLocal IP, then
wait until the adapter is in the normal working state (“RUN”indicator flashes, without
considering other indicators), then connect the computer to the air conditioning adapter
with a network cable. Otherwise, if connect the computer to the adapter, then power on
the adapter and set the computer’s Local IP, it may not enter the setting interface.
3.3 Check the air conditioning connection of each adapter
If the air conditioning adapter has been connected with H-NET communication wire, when the
adapter is powered on, it will automatically start searching for the air conditioning connected to it
(in this case the “RUN” indicator is on), after the search is completed, “RUN” indicator starts
flashing, the adapter is in the normal working state, if the “STAT” indicator is on at this time,
indicating that no air conditioning is found, and if flashing, it indicates the adapter has found at
least one air conditioner. Click <Aircondition Management> in the main interface of adapter, enter
the air conditioning management interface, as shown in Figure 3.8:
Figure 3.8 Air conditioning connection information
The interface shows the number of the indoor air conditioners connected and their addresses, as
well as working condition of indoor air conditioners, as shown above, the “red flag”indicates air
conditioning switched on, “Heat” means heating, “26 ℃” indicates set temperature, “0-0”means
air conditioning address. (“Refrigeration System number - address Number”). By pressing “ON”,
“OFF”, “COOL”and other buttons, the air-conditioning can be controlled, “Refresh”button is to
refresh and get the latest state of air conditioning (Note: Only by pressing this button, the latest
status of air conditioner can be obtained)
When "Operate Selected" is selected, you need to check the indoor unit you want to control, and
then press the button you want to control, the indoor unit selected will respond as per the specified
button action.
+
When “Operate All”is selected, press the control button, all indoor units connected to this adapter
will act correspondingly as per the specified button action.

3.4 Adding adapters and basic configuration table export
※if the air conditioning configuration information table has been completed, all operations in
3.4 can be omitted
3.4.1 Adding air conditioning adapter
View Hi-Dom system login page and log into the system to enter <check debugging> ->
<air-condition adapter maintenance>, click <add records> button to add air conditioning adapters,
after adding and editing is completed, click <save added records> to save, for changes,
double-click the left mouse button to modify the content, and click <to save the change record> to
save, as shown in Figure 3.9
Figure3.9 Air conditioning adapter maintenance interface
※Air-conditioning bus number is the actual H-NET line number, and the numbering of air
conditioning adapter or it can be numbered as 1, 2, 3…, it is permitted as long as it is not repeated.
※Air conditioning adapter ID is the unique identification for air conditioning adapter, consisting
of a total of 32 letters or numbers set during the production, it is not changed after leaving factory
and can be obtained from the nameplate on the back of the adapter or from WEB configuration
page inside it, the access method to the WEB configuration page is as follows:
In the Adapter Configuration main interface, click <Production Information> to enter the factory
information interface, as shown in Figure 3.10:

Figure3.10 Factory information interface of air condition adapter
“MAC ”here is “air conditioning Adapter ID”, it can be copied for use.
Repeat this operation to add all air conditioning adapters into Hi-Dom system
After all adapters are added and saved successfully, click <read time> to read adapter time, and
click <timing> for revision of adapter internal time. if air conditioning adapter is connected to the
computer properly, and “air conditioning adapter ID”is correct, <connection status> will display
<connected>, <timing result> will display <normal>; otherwise it will display <not connected>
and <abnormal>, in this case, please check the IP address settings, cable connections, switch
power supply and air conditioning adapter ID, etc.
3.4.2 Adding meter reading adapters
Enter <Check debugging> -> <electricity and gas meter adapter maintenance> page, as shown in
Figure 3.11, for the configuration process, please refer to air conditioning adapter adding.
Figure 3.11 Metering adapter maintenance interface
※The bus line number of meter reading is the actual wire number of electricity meters, i.e. the
numbering of the meter reading adapter, NOTE: the meter reading bus number shall not replicate
the bus number of air conditioning.
※Meter reading adapter ID is the unique identification for meter reading adapter, consisting of a

total of 32 numbers, which is not changed after leaving factory. In the Adapter Configuration main
interface, click <Production Information> to enter the factory information interface, as shown in
Figure 3.12:
Figure3.12 Factory information interface of M-Concentrator
3.4.3 Air conditioning connection search and save
After all air-conditioning adapters and meter reading adapters are added, click <Search> button in
<check debugging> -> <Connection Search and Save> page, as shown in Figure 3.13, to search
the air conditioning connection information. After the search is completed, all air-conditioning
connections can be shown, click on <Save> and then click on <Download air conditioning
connection information table> to export the basic configuration information table.
Figure 3.13 Connection search interface
3.5 Edit and lead in basic configuration table
Edit the basic configuration table according to actual location for the air conditioner and electricity
meter. See Table 3.1 for header and meaning of the configuration information table.
Table 3.1 Header and Meaning of Configuration Information Table
Name of Column
Meaning
Remarks

ID
Increase progressively according to the
table (figure larger than 1)
Required
GW_ID
Air conditioner adapter mac address (32
digits) can be obtained from nameplate on
back of the adapter or form the adapter’s
inner web configuration page
Required
GW_Line NO.
Adapter Serial No. (Figure Larger than 1)
Required
OU_ address
Address of Outdoor unit (Figure Larger
than 1)
Required
IU_ address
Address of Indoor unit (Figure Larger than
1)
Required
Building
Building Catalog Level I, Such as:
Building A
Required
Floor
Building Catalog Level II, Such as: F3
Required
Room
Building Catalog Level III, Such as: Room
202
Required
Tenant
Lessee Using Air Conditioner
Required
Tenant_NO.
Lessee Serial No.; Be use for ordering the
billing statement (Figure Larger than 1)
Required
IU_model
Model of indoor unit
Required
IU_capacity
Capacity of indoor unit (Figure Larger
than 1)
Required
OU_Alias
Alias of outdoor unit (Letters and Figures;
Mark installation position or service area
of outdoor unit)
Required
OU_model
Model of outdoor unit
Required
OU standby Power
(×1W)
Spare (Figure Larger than 1); Blank space
is not allowed.
Required
Meter GW_ID
Meter Reading Adapter mac Address (32
Digits) can be obtained from nameplate on
back of the adapter or form the adapter’s
inner web configuration page
Optional (Fill when
connecting electricity meter)
Meter GW _
line_NO
Meter Reading Adapter Serial No. (Figure
Larger than 1. Note: It shall be not the
same with other meter reading adapter line
numbers or air conditioner adapter line
numbers)
Optional (Fill when
connecting electricity meter)
OU_meter1
Electricity Meter Add. (Figure of 8~10
Digits)
Optional (Fill when
connecting electricity meter)
Meter current
transformer
coefficient
If electricity meter is connected with
current transformer, it shall indicate ratio
of transformation for current transformer
(Figure Larger than 1)
Optional (Fill when
connecting electricity meter)
Actual electricity
consumption is number of
degree obtained by meter

reading multiplied by
multiple of ratio of
transformation.
Meter GW_ID
Meter Reading Adapter mac Address (32
Digits) can be obtained from nameplate on
back of the adapter or form the adapter’s
inner web configuration page
Optional (Fill when
connecting electricity meter)
Meter GW _
line_NO
Meter Reading Adapter Serial No. (Figure
Larger than 1. Note: It shall be not the
same with other meter reading adapter line
numbers or air conditioner adapter line
numbers)
Optional (Fill when
connecting electricity meter)
OU_meter2
Electricity Meter Add. (Figure of 8~10
Digits)
Optional (Fill when
connecting electricity meter)
Meter current
transformer
coefficient
If electricity meter is connected with
current transformer, it shall indicate ratio
of transformation for current transformer
(Figure Larger than 1)
Optional (Fill when
connecting electricity meter)
Actual electricity
consumption is number of
degree obtained by meter
reading multiplied by
multiple of ratio of
transformation.
Meter GW_ID
Meter Reading Adapter mac Address (32
Digits) can be obtained from nameplate on
back of the adapter or form the adapter’s
inner web configuration page
Optional (Fill when
connecting electricity meter)
Meter GW _
line_NO
Meter Reading Adapter Serial No. (Figure
Larger than 1. Note: It shall be not the
same with other meter reading adapter line
numbers or air conditioner adapter line
numbers)
Optional (Fill when
connecting electricity meter)
OU_meter3
Electricity Meter Add. (Figure of 8~10
Digits)
Optional (Fill when
connecting electricity meter)
Meter current
transformer
coefficient
If electricity meter is connected with
current transformer, it shall indicate ratio
of transformation for current transformer
(Figure Larger than 1)
Optional (Fill when
connecting electricity meter)
Actual electricity
consumption is number of
degree obtained by meter
reading multiplied by
multiple of ratio of
transformation.
※In actual configuration table, <Meter GW_ID>, <Meter GW _ line_NO>, <OU_meter> and
<Meter current transformer coefficient> can have repeated multi columns for the united

outdoor device composed of more modules,one electricity meter for each module.
Figure 3.14 is a configuration information example for reference.
When editing is completed, enter into the <Configuration Information>-><Installation
Information Import>Page, as shown in Fig. 3.15. Click <Select Document> to select edited
configuration document, then click <Upload> to lead in the configuration document.
Fig. 3.15 Installation Information Import Page
Note:
If air conditioner connection information table is prepared and perfected before installing
Hi-Dom system, all steps in 3.4 can be directly skipped and it just needs to lead in the installation
information configuration table from here.
3.6 Issue electricity meter address
Enter into the <Inspection and Debugging>-><Electricity Meter and Gas Meter
Maintenance> page as shown in Fig. 3.16. Before issuing address, the page matching status
displays <Require Matching>, then click <Issue Address> to issue electricity meter address. When
electricity meter address is issued, the page matching status will display <Matching Successful> as
shown in Fig. 3.17, and the system matching is completed.

Fig. 3.16 Electricity Meter Maintenance Page
Fig. 3.17 Complete issuing configuration of electricity meter address
4. Air Conditioner Adapter Power Supply Input
4.1 Power Supply Input
(1) Firstly, confirm that power normal (DC 12V),H-NET and LAN connection is normal,
then supply power to the machine.
(2) When power supply is input, POWER light of adapter is lightened normally (power
supply indicator) and RUN light (operation indicator) is lightened normally until air conditioner
searching is completed when the RUN light will start flickering.
(3) When air conditioner searching is completed, the RUN light will start flickering. If the
adapter fails to search out air conditioner, STAT will be lightened normally. If at least 1 air
conditioner is searched out, the STAT light won’t be lightened.
(4) When the machine works normally, POWER light will be lightened normally, H-NET
light will flicker irregularly and RUN light will flicker regularly.
4.2 Reset to Defaults
When it is electrified and RUN light is lightened normally, it can be reset to defaults in the
first 15 seconds. At this time, when long pressing the Reset Button for 4 seconds, the RUN light
will die out. At this time, if stop pressing the Reset Button, the RUN light will flicker, the STST
light will be lighted normally after 2 seconds, and resetting is completed. When electrify again, the
system will be reset to defaults.
※Conduct air conditioner searching after RUN is lighting for 15 seconds. It is invalid
pressing the RESET button at this time.
※Reset to default will only empty information of timer and air conditioner locking, ip
address will be recovered to 192.168.1.101, and billing related information won’t be emptied.

4.3 Normal/Abnormal Display
Refer Table 4.1 for normal/abnormal display of working conditions of the machine
Table 4.1 Normal/abnormal display
LED
Name
Expressed
Item
Lighting Conditions
Lighting-off Conditions
POWER
Power
Power on
Power off
RUN
working
conditions of
the machine
·Often lighting when the
machine implements air
conditioner connection
confirmation
·Lighting and dying
flickering in frequency of 0.5
seconds when the machine is
in normal working
·Lighting and dying
flickering in frequency of 0.5
seconds when the machine is
in normal working
485TX
RS485 sends
out signal status
When sending out data on
RS485
When it fails to send out data
on RS485
485RX
RS485 receives
signal status
When receiving data on
RS485
When it fails to receive data
on RS485
H-NET
H-NET
Communication
Status
·When data has been
received on H-NET
·When data has been sent
out on H-NET
·When data fails to be
received on H-NET
·When data fails to be sent
out on H-NET
STAT
Status Display
·No H-NET system
connection
·Complete resetting
Other conditions
LAN
LAN
Communication
Status
·Light when connection is
confirmed on LAN
·Flicker when data is
received or sent out on LAN
When no connection signal
is received on LAN
5. Maintenance and After-sale Services
5.1 Handling Methods in Abnormalities
Refer to Table 5.1 –Handling Methods in Abnormalities for methods judging and handling
abnormal conditions.
Table 5.1 –Handling Methods in Abnormalities
NO.
Phenomenon
Content of Inspection
Handling Method
1
It cannot
connect air
conditioner and
meter reading
adapter in
Check whether air conditioner
and meter reading adapter mac
address is set correctly in adapter
maintenance.
Log in adapter configuration page
and confirm mac address
configuration.
Check whether ip address of
Set ip address of server and adapter
Other Hisense Controllers manuals
Popular Controllers manuals by other brands

Aqua Computer
Aqua Computer farbwerk nano User and installation manual

Hunter
Hunter ICC2 owner's manual

LSI
LSI MegaRAID SATA150-2 Quick Hardware Setup Guide

NANOTEC ELECTRONIC
NANOTEC ELECTRONIC C5 Operational and programming manual

Redback
Redback A 4595A operating manual

Moore Industries
Moore Industries 535 user manual