HITROL HLC-400 User manual

HLC-400
HITROL CO., LTD. 1
HITROL CO., LTD.
HEAD OFFICE.FACTORY.R&D INSTITUDE
HITROL CO., LTD. 141, Palhakgol-gil, Jori-eup
Paju-si, Gyeonggi-do, Korea
TEL. : (+82)-31-950-9700
FAX. : (+82)-31-943-5600
www.hitrol.com
INSTRUCTION MANUAL
LEVEL CONTROLLER & ALARM UNIT
HLC-400
Doc. no. : HLC300N_IM_Eng_Rev.0.2
Issue date: 2020. 09

HLC-400
HITROL CO., LTD. 2
You should be careful where CAUTION is marked to carry
outthework.
You should be well-informed of the contents where
WARNING is marked before carrying out the work.
.
You should be aware of where NOTICE is marked to carry
outthework.
Table of Contents
Overview ·····························3
Characteristics ·························3
Operating Principle and Composition ·······3
Specifications ·······················4
Dimensions ························4
Wiring ·······················5
Precautions for Installation ·············5
Safety and Environment ·················6
Failure Check and Solution ················6
Marking ························7
Warranty and Contact ··················7

HLC-400
HITROL CO., LTD. 3
Overview
Characteristics
Operating
Principle and
Composition
HLC-400 Body
DIN-Rail Mounting Button
Terminal
Bolt Hole
When the level sensor connected to HLC-400 detects a liquid in the tank, a leakage
current flow and it is sensed by leakage current sensing circuit, and transistor is
activated. Accordingly, relay contact is changed and it can be used for alarm and/or
control signal.
■Easy to install (DIN Rail Type)
■Compact size
■Operating can be checked through LED lamp
HLC-400 is a Level Control & Alarm Unit that controls and alarms by combining with
the level sensor (HE, HQ, HR Type) of the storage of tank. The signal of the level sensor
can function as the upper and lower alarm of liquid through HLC-400, and the product
can be installed inside the control panel.

HLC-400
HITROL CO., LTD. 4
General Spec.
Actual product may have a tolerance slightly.
Specifications
Dimensions
Combination Unit
HE Series (Electrode)
HQ Series (Quick Float)
HR Series (Float Reed Switch)
Mounting
Panel Inside (DIN Rail or Bolting)
Power Source
AC 110V/220V @ 50/60Hz
Standby Power Consumption
AC 110V @ 1.26W / AC 220V @ 1.23W
Active Power Consumption
AC 110V @ 6.8W / AC 220V @ 8W
Relay Contact
Alarm: 2-SPDT
Relay Contact Rated
AC 250V, 10A / DC 30V, 10A
Transmit Signal
E5 (AC 14V @ 50/60 Hz)
LED State
E1 / AL.1 (Red) : H.H Detection
E2 / AL.2 (Red) : H Detection
E3 / AL.3 (Red) : L Detection
E4 / AL.4 (Red) : L.L Detection
Cable & Distance
Def, 1.25 SQ @ Max. 300m
Operating Temperature
-20℃~ +60℃
Housing Material
ABS
Dimensions
145mm x 90mm x 72mm
Weight
325g
Unit: mm

HLC-400
HITROL CO., LTD. 5
Wiring shall be performed considering of below recommendation.
Remove it with the power disconnected.
Wiring
Precautions
for Installation
Alarm
CONTACT 1
CONTACT 2
CONTACT 3
CONTACT 4
LED No.
1
2
3
4
Input
E1, E5
E2, E5
E3, E5
E4, E5
Output
A
N.O, COM
N.O, COM
N.O, COM
N.O, COM
B
N.C, COM
N.C, COM
N.C, COM
N.C, COM
Connection Diagram
■It is recommended to use washers to prevent a loosening when the product is fixed using bolts.
■Wiring shall be performed after checking of wiring diagram described in the manual or sticker.
■Make sure that the power source whether it is AC 110V or AC 220V.
■It is recommended to use AWG 13 or 14 cable between the controller and level sensor, and use
shield cable in case that the distance between the controller and level sensor quite long(several
hundred meters ~ 500m) and for low conductivity medium. (Non-recommendation cables may
result in some differences in operating and level sensing distances.)
■Check the LED color after applying of power.
■Power shall be applied after completing of installation.

HLC-400
HITROL CO., LTD. 6
Safety and
Environment
Failure Check
and Solution
■Precautions for Use
- Do not disconnect the cable during use.
- Do not disconnect the product during use.
- Do not apply high impact to the product.
■Precautions for Wiring
- Make sure to wire contacts correctly. (Refer to Wiring)
- Wire and supply the power to the product after checking the specifications.
- Incorrect power voltage may cause damage to the product.
- Pay attention to prevent electric shock.
■Disposal of Product
- Make sure to separate the PCB and main unit from housing before disposing the products.
No part (ex. Mercury Switch) has influence on the environment, so no special attention is
required.
■Relay contact does not work
- Check whether the LED lamp is on/off.
- Check the cable connection.
- Check the input voltage.
- Check the level sensor wiring cable.
■Controller is normal, but not working
1) Electrode Type Level Switch
- If there is foreign matter or sediment such as lime on the bottom of tank, it may
cause malfunction.
- Too low liquid conductivity can cause malfunction. (ex. Distilled Water)
- When wiring between controller and electrode is far apart, it may cause malfunction.
- Please refer to the cable recommendations between the controller and the sensor for
installation precautions (Page 5).
2) Float Type Level Switch
- Check that the float floats normally.
- Check the signal when the float operates normally.

HLC-400
HITROL CO., LTD. 7
Marking
Warranty
and Contact
■Product Identification
- The product identification mark is attached onto housing and shows the model
name, serial number, input/output and matters regarding quality control. The serial
number is a unique manufacturing number for the identification of products.
- It is attached to the front of the product and the model name and input/output
information are indicated.
- It is attached to the side of the product
and means it has passed the internal
quality system.
- It is attached to the bottom of the product
and the serial number is indicated.
■Warranty and Service
This product is subject to the warranty for 2 years of shipment and unpaid service will be
provided for any damage found under normal operating conditions. If it is not about the failure
of product, the service charge will be payable.
You can request A/S at our website or by contacting our headquarters.
■Headquarters ․Factory ․Laboratory Contact
ADDRESS
: HITROL CO., LTD 141, Palhakgol-gil, Jori-eup, Paju-si, Gyeonggi-do, Korea
T E L : 031-950-9700 (Headquarters & A/S)
F A X : 031-943-5600 (Headquarters & A/S)
This manual suits for next models
1
Table of contents
Popular Controllers manuals by other brands

ETC
ETC Echoflex ELED3 installation guide

Siemens
Siemens RMU7 B Series operating instructions

Panasonic
Panasonic CZ-CAPE2 Installation and service instructions

TBK vision
TBK vision MY-4101KT user manual

Mercoid
Mercoid EDA series Installation and operating instructions

YORKVILLE
YORKVILLE Coliseum CV-1 manual