INSTALLATION
INSTRUCTIONS
DIFFERENTIAL PRESSURE SWITCHES
DPI Series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
SPECIFICATIONS
ThankyouforchoosinganHKInstrumentsDPIserieselectronicdif-
ferenalpressureswitch.TheDPIseriesisintendedforuseincom-
mercialenvironments.Itcombinestheadvantagesofanelectronic
dierenal pressure switch (on-o relay) and a mul-funconal
dierenal pressure transmier to meet your applicaon require-
ments.
The DPI series is comprised of the DPI±500 with bi-direconal
measurementrangesfrom±100to±500PaandtheDPI2500with
measurementrangesfrom100to2500Pa.
AllDPIseriesdevicesincludeonerelay,display,manualpushbuon
zeropointcalibraonandspanpointcalibraon.Oponalfeatures
includeasecondrelayandautozerocalibraon.
DPIseriesdevicesarecommonlyusedinHVAC/Rsystemsfor:
•fan,blowerandltermonitoring
•staircasepressuremonitoringandalarm
•pressuremonitoringincleanrooms
•boilerpressuremonitoringandalarm
SPECIFICATIONS
Performance
Accuracy:
±1.5%(±0.7%*)
%FSfromhighestpressurerange(including:
generalaccuracy,temperaturedri,linearity,hysteresis,
andrepeonerror)
*Canbeachievedwithspanpointcalibraon
Long term stability:
Typical1year
Withautozero:±1Pa
Withoutautozero:±8Pa
Thermal eects:
Temperaturecompensatedacrossthefullspectrumof
capability
Overpressure:
Proofpressure:25kPa
Burstpressure:30kPa
Zero point calibraon:
Automacwithautozero(-AZ)circuitor
Manual via menu
Response me:
0.5–10s,selectableviamenu
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
Pa,kPa,mmWC,inWC,mbarselectableviamenu
Measuring element:
Piezoresisve
Environment:
OperangTemperature:
Withoutautozero:-10...50°C
Withautozero:-5...50°C
Storagetemperature:-20...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:89x86.5x37.1mm
Weight:
150g
Mounng:
Case:2each4.3mmholes
Lid:2each4.3mmholes
Materials:
Case:ABS
Lid:PC
Ductconnectors:ABS
Tubing:PVC
Protecon standard:
IP54
Touchsensivebuonsonthelid:
Menu,Back,OK,downarrow,uparrow
Display:
31/2digitLCDbacklitdisplay
Size:46.0Wx14.5Hmm
Electrical connecons:
n/out:
Terminalblock(24V,GND,0–10V)
Wire:0.2–1.5mm2(12–24AWG)
Relay1:
Terminalblock(NC,COM,NO)
Wire:0.2–1.5mm2(12–24AWG)
Relay2:
Terminalblock(NC,COM,NO)
Wire:0.2–1.5mm2(12–24AWG)
Cable entries:
Strainrelief:M16&M20
Knockout:16mm
Knockout:20mm
Pressure ngs:
5.2mmbarbedbrass
+Highpressure
−Lowpressure
Electrical
Circuit:3-wire(24V,GND,0–10V)
Input:
Withoutautozero:21–35VDC/24VAC,±10%
Withautozero:24VACorVDC,±10%
Output:
Analog:0–10V
Relay1:250VAC/30VDC/6A
Relay2:250VAC/30VDC/6A
Adjustableswitchingpointandhysteresis
Zero/Spanoutputcalibratedwithin±0.025V
Resistanceminimum:1kΩ
Currentconsumpon:
35mA+relays(7mAeach)+AZcircuit(20mA)
+0–10Voutput(10mA)
Conformance
MeetsrequirementsforCEmarking:
EMCDirecve2014/30/EU
RoHSDirecve2011/65/EU
LVDDirecve:2014/35/EU
WEEEDirecve2012/19/EU
INTRODUCTION
APPLICATIONS
WARNING
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =
RoHS 2
2011/65/EU

Copyright HK Instruments 2019 www.hkinstruments. Installaon version 7.0 2019
SCHEMATICS
DIMENSIONAL DRAWINGS
INSTALLATION
Figure 1a - Surface mounng
STEP 1: MOUNTING THE DEVICE
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Openthelidandroutethecable(s)throughthestrainrelief(s)and
connectthewirestotheterminalblock(s)(seestep2).
3)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
1)Selectthemounnglocaon(duct,wall,panel).
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountwithappropriatescrews.
Figure 1b - Mounng orientaon
Figure 1c - Applicaon connecons
24 V GND 0–10 V
Terminal block Terminal block for relays
NC COM NO NC COM NO
37.1
89.0
86.5
74.5
64.5
52.5
4.2
YES NO NO
Stac pressure Filter/Damper
monitoring
Fan/Blower
monitoring
Not
connected

Copyright HK Instruments 2019 www.hkinstruments. Installaon version 7.0 2019
STEP 2: WIRING DIAGRAMS CONFIGURATION CONTINUED
ForCEcompliance,aproperlygroundedshieldingcableisrequired.
1)Unscrewthestrainreliefandroutethecable(s).Useseparatestrain
reliefforthe0–10Voutputcableandtherelaycable(s).
2)Connectthewiresasshowningure2aand2b.
3)Tightenthestrainrelief.
Figure 2a - Wiring diagram 0–10 V output
Figure 2b - Wiring diagram relay(s)
STEP 3: CONFIGURATION
1)Selectthedesiredmeasurementunit.
2)Selectthedesiredmeasurementrange.
3)Selectthedesiredresponseme.
4)Conguretherelay(s).
5)Zerothedevice.
6)Calibratethespanpoint.
7)Connectthepressuretubes.Connectposivepressuretoport
labeled"+"andnegavepressuretoport"-".
Thedeviceisnowreadytobeused.
24 V
GND
P out
Power supply
24 VDC / 24 VAC
+
Output 0...10 V
V
+
SPAn
ZEro
rEL1/2
rESP
PSEL
UnIt
Pa, kPa, mmH2O, inchWC, mbar
Pressure range selecon
Response me
Relay menu(s)
Zero point calibraon
High point calibraon menu
rES
AdJ
High point calibraon
Reset high point calibraon
HYS
SP
dir
Relay acvaon menu
Relay setpoint
Relay hysteresis 0–50 % of range
FALL
rISE
Relay acvaon on increasing pressure
Relay acvaon on decreasing pressure
NC
COM
NO
Relay 1
NC
COM
NO
Relay 2
With the MENU buon you can enter the menu by pressing the buon for
3 seconds. You can exit the menu without making any
changes.
With the BACK buon you can return without making changes.
With the OK buon you can open new opons or confirm changes and return
to previous display.
With the buons you can scroll the menus.

Copyright HK Instruments 2019 www.hkinstruments. Installaon version 7.0 2019
NOTE! Always zero the device before use.
Tozerothedevicetwooponsareavailable:
1)Manualzeropointcalibraon
2)Autozerocalibraon
Does my transmier have an autozero calibraon? See the product
label.Ifitshows-AZinthemodelnumber,thenyouhavetheautozero
calibraon.
1)Manualzeropointcalibraon
NOTE:Supplyvoltagemustbeconnectedatleastone hourpriorto
zeropointadjustment.
a)Disconnectbothpressuretubesfromthepressureportslabeled+
and–.
b)Pushbotharrowbuonsontopofthelidshortlyorgoto
conguraonmenuandselect“Zero”.
c)Thezeroingofthedevicewillproceedautomacallywhenthe
greenledontopofthelidturnsoand“Zero”textfollowedby
acounterfrom3to0secondsappearsonthedisplay.Thezeroing
iscompletewhenthegreenledturnsonagain.
d)ReinstallthepressuretubesensuringthattheHighpressuretube
isconnectedtotheportlabeled+,andtheLowpressuretubeis
connectedtotheportlabeled−.
NOTE:Thezeropointshouldbecalibratedviamanualzeropoint
calibraononehouraerinstallaonandatleastevery12months
duringnormaloperaons.
2)Autozerocalibraon
If the device includes the oponal autozero circuit, no acon is re-
quired.
Autozerocalibraon(-AZ)isanautozerofunconintheformofanauto-
maczeroingcircuitbuiltintothePCBboard.Theautozerocalibraon
electronicallyadjuststhetransmierzeroatpredeterminedmeinter-
vals(every 10minutes).Thefuncon eliminates all outputsignaldri
due to thermal, electronic or mechanical eects, as well as the need
fortechnicianstoremovehighandlowpressuretubeswhenperform-
ing inial or periodic transmier zero point calibraon. The autozero
adjustmenttakes4secondsaerwhichthedevicereturnstoitsnormal
measuring mode. Duringthe 4 secondadjustment period, the output
anddisplayvalueswillfreezetothelatestmeasuredvalue.
Transmiers equipped with the autozero calibraon are virtually
maintenancefree.
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsidered tostart on thedeliverydate of theproduct.If a defect
in raw materials ora producon aw is found,the seller is obligated,
whentheproductissenttothesellerwithoutdelayorbeforeexpira-
onofthewarranty,toamendthemistakeathis/herdiscreoneither
byrepairingthedefecveproductorbydeliveringfreeofchargetothe
buyeranewawlessproductandsendingittothebuyer.Deliverycosts
fortherepairunderwarrantywillbepaidbythebuyerandthereturn
costsbytheseller.Thewarrantydoesnotcomprisedamagescausedby
accident, lightning, ood or other natural phenomenon, normal wear
andtear,improperorcarelesshandling,abnormaluse,overloading,im-
properstorage,incorrectcareorreconstrucon,orchangesandinstal-
laonworknotdonebythesellerorhis/herauthorizedrepresentave.
Theseleconofmaterialsfordevicespronetocorrosionisthebuyer’s
responsibility,unlessotherwiseislegallyagreedupon.Shouldtheman-
ufactureralterthestructureofthedevice,thesellerisnotobligatedto
makecomparablechangestodevicesalreadypurchased.Appealingfor
warranty requiresthat the buyer has correctly fullled his/her dues
arisenfromthedeliveryandstatedinthecontract.Thesellerwillgive
anew warrantyforgoods thathavebeenreplacedorrepaired within
thewarranty,howeveronlytotheexpiraonoftheoriginalproduct’s
warrantyme.Thewarrantyincludestherepairofadefecvepartor
device, or if needed, a new part or device, but not installaon or ex-
change costs. Under no circumstance is the seller liable for damages
compensaonforindirectdamage.
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
STEP 4: ZEROING THE DEVICE WARRANTY POLICY