HMS Networks Intesis IN700485 0000 Series Assembly instructions

© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Version 1.3
1 / 2
IN700485***0000
Protocol Translator with Serial and IP support
Order Code: IN700485***0000
** stands for the Intesis gateway capacity and varies depending on the specific gateway acquired
Installation Sheet version 1.3
HMS Industrial Networks S.L.U ©
SAFETY INSTRUCTIONS
!WARNING
Follow carefully this safety and installation instructions.
Improper work may lead to serious harmful for your health
and also may damage seriously the Intesis gateway and/or
any other equipment connected to it.
The Intesis gateway must be installed by accredited electrician or
similar technical personnel, following all the safety instructions given
here and in accordance always with the country legislation for
installation of electric equipment.
The Intesis gateway cannot be installed outdoors or exposed to direct
solar radiation, water, high relative humidity or dust.
The Intesis gateway must only be installed in a restricted access
location.
In case of wall mount, fix firmly the Intesis device on a not vibrating
surface following the instructions next.
In case of DIN rail mount fix the Intesis device properly to the DIN rail
following the instructions below.
Mounting on DIN rail inside a metallic cabinet properly connected to
earth is recommended.
Disconnect always power of any wires before manipulating and
connecting them to the Intesis gateway.
A power supply with an NEC Class 2 or Limited Power Source (LPS)
and SELV rated is to be used.
Respect always the expected polarity of power and communication
cables when connecting them to the Intesis gateway.
Supply always a correct voltage to power the Intesis gateway, see
details of voltage range admitted by the device in the technical
characteristics below.
CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type.
Dispose of Used Batteries according to the instructions. Battery
replacement shall be done by an authorized installer.
CAUTION: The device is to be connected only to networks without
routing to the outside plant, all communication ports are considered for
indoor only and can be connected SELV circuits only.
This device was designed for installation in an enclosure. To avoid
electrostatic discharge to the unit in environments with static levels
above 4 kV, precautions should be taken when the device is mounted
outside an enclosure. When working in an enclosure (ex. making
adjustments, setting switches etc.) typical anti-static precautions
should be observed before touching the unit.
Safety instructions in other languages can be found at:
https://intesis.com/docs/manuals/v6-safety
INSTALLATION
Follow instructions next to properly install the gateway.
Disconnect from mains the power supply before connecting it to the
Intesis gateway.
Disconnect power of any bus or communication cable before
connecting it to the Intesis device.
Mount the Intesis gateway on the wall or DIN rail following the
instruction given below, respectingthe safety instructions given above.
Connect a NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply to the Intesis gateway, respect the polarity if DC
power or Line and Neutral if AC power. Apply always a voltage within
the range admitted by the Intesis device and of enough power (see
technical characteristics).
Circuit-breaker must be used before the power supply. Rating 250V-
6A.
Connect the communication cables to the Intesis gateway, see details
on the user's manual.
Power the Intesis device and the rest of devices connected to it.
NOTE: The device cannot be installed in air-handling space.
DIN Rail Mount
With the clips of the box in their original position, insert first the box
in the upper edge of the DIN rail and later insert the box in the down
part of the rail, using a small screwdriver and following the steps in
the figure below.
CONFIGURATION
Use the Configuration Tool to configure the gateway.
See instructions to download and install the latest version at:
https://www.intesis.com/products/intesis-maps#download
Use the Ethernet connection or the Console Port (mini USB type B
connector included) for communication between the gateway and the
configuration tool. See CONNECTIONS below and follow instructions
of user’s manual for more details.
Owner’s Record
The serial number is located at the rear of the gateway.
Record this information in the space provided below.
Refer to it whenever you contact upon your gateway
dealer or support team regarding this product.
Serial No.

© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Version 1.3
2 / 2
Enclosure
Plastic, type PC (UL 94 V-0)
Net dimensions (dxwxh): 90x88x56 mm
Recommended space for installation (dxwxh): 130x100x100 mm
Color: Light Grey. RAL 7035
Battery
Size: Coin 20 mm x 3.2 mm
Capacity: 3 V / 225 mAh
Type: Manganese Dioxide Lithium
Mounting
Wall
DIN rail EN60715 TH35
Console Port
Mini Type-B USB 2.0 compliant
1500 Vdc isolation
Terminal Wiring
(for power supply and
low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with
ferrule)
1 core: 0.5 .. 2.5 mm2
2 cores: 0.5 .. 1.5 mm2
3 cores: not permitted
If cables are more than 3.05 meters long, Class 2 cable is required.
USB port
Type-A USB 2.0 compliant
Only for USB flash storage device
(USB pen drive)
Power consumption limited to 150 mA
(HDD connection not allowed)
Power
1 x Plug-in screw terminal block (3 poles)
9 to 36 Vdc, 2.4W
24 Vac +/-10 %, 50-60Hz, 2.4W
Recommended: 24Vdc
Push Button
Button A: Check the user manual
Button B: Check the user manual
Operation
Temperature
0°C to +60°C
Ethernet
1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
Operational
Humidity
5 to 95 %, no condensation
Port A
1 x Serial EIA-485 Plug-in screw terminal block (2 poles)
A, B
1 x Plug-in screw terminal block green (2 poles)
SGND (Reference ground or shield)
1500 Vdc isolation from others ports
Protection
IP20 (IEC60529)
LED
Indicators
10 x Onboard LED indicators
2 x Run (Power)/Error
2 x Ethernet Link/Speed
2 x Port A TX/RX
2 x Port B TX/RX
1 x Button A indicator
1 x Button B indicator
Switch A & B
(SW A & SW B)
1 x DIP-Switch for serial EIA485 configuration:
Switch 1:
ON: 120 Ω termination active
Off: 120 Ω termination inactive
Switches 2-3:
ON: Polarization active
Off: Polarization inactive
PORT B
1 x Serial EIA-232 (SUB-D9 male connector)
Reserved for future use
1 x Serial EIA-485 Plug-in screw terminal block (3 poles)
A, B, SGND (Reference ground or shield)
1500 Vdc isolation from other ports
(except PORT B: EIA-232)
CONNECTIONS
ELECTRICAL & MECHANICAL FEATURES
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV rated power supply.
If using DC power supply:
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted.
If using AC power supply:
Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals of the
AC power supply to earth, and make sure the same power supply is not supplying any other device.
Ethernet / BACnet IP (UDP) / Console (UDP & TCP)
Use an Ethernet CAT5 cable. Contact the network administrator to ensure traffic is allow on the respective LAN.
OOB After power up the IP would be DHCP for 30 seconds, if no IP is assigned then then it would be set to
192.168.100.246
Configuration
Port A
EIA485
Port B
EIA485
Port B
EIA232
Ethernet
IN-BAC-MBM
Modbus RTU
BACnet MSTP/
Modbus RTU*
NA
Modbus TCP/ BACnet
IP & Console
IN-MBS-BAC
BACnet
MSTP
Modbus
RTU
Modbus
RTU
Modbus TCP/ BACnet
IP & Console
IN -ASCII-BAC
BACnet
MSTP
ASCII
ASCII
BACnet IP/ASCII TCP
& Console
Pin Out
Port A
EIA485
Port B
EIA485
Scan here for
configuration
details
B-
A4
B1
A+
A3
B2
SNGD
A1&A2
B3
Note for PortA and PortB; standard EIA485 bus: maximum distance of 1200 meters, maximum 32 devices
connected, and in each end of the bus a 120 Ω resistor. Bus biasing and termination resistor for EIA485 can be
enabled for PortA and PortB in the DIP switch –see table below.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow communication between the
Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check the user
manual for more information.
USB
Connect a USB storage device (not a HDD) if required. Check the user manual for more information.
100 mm
100 mm
130 mm
(d)
This marking on the product, accessories, packaging or literature (manual) indicates that the product contains electronic
parts and they must be properly disposed of by following the instructions at https://intesis.com/weee-regulation
Other HMS Networks Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Edge Technologies
Edge Technologies Minuteman 320 SE Operation manual

SMC Networks
SMC Networks IDUS Series manual

Big Daishowa
Big Daishowa FCR16 Operation manual

IBAIONDO
IBAIONDO CRB AUTOMAT Touch Screen manual

HyQuest Solutions
HyQuest Solutions TB1L instruction manual

Komfovent
Komfovent PPU-LCHX Series manual

Wavetronix
Wavetronix Click 222 quick start guide

Nord Drivesystems
Nord Drivesystems B 1000 Operating and assembly instructions

Cascade TEK
Cascade TEK SVO-10-VC Installation and operation manual

Renishaw
Renishaw Primo quick start guide

Engcon
Engcon SG03 user manual

Reliable
Reliable F1FR56 quick start guide