manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Hochiki
  6. •
  7. Accessories
  8. •
  9. Hochiki ALG-E Service manual

Hochiki ALG-E Service manual

2-3-0-246/ISS10/NOV09
HOCHIKI ESP SENSOR & BASE RANGE
INSTALLATION INSTRUCTIONS
Products Covered: ALG-E, ALG-E(NP), ALG-EN, ALG-ENM / AIE-E,
AIE-E(NP) / ACA-E / ACB-E, ACB-EM, ACB-EW / YBN-R/3, YBN-R/3M
Introduction
The analogue Sensors listed above can all use a Common Mounting Base (YBN-R/3 or YBN-R/3M in the case of marine
approved sensors), which is electronics free, the Base Sounder (YBO-BS), the Base Sounder Beacon (YBO-BSB) and
the Short Circuit Isolator Bases (YBO-R/SCI or YBO-R/SCIM in the case of marine approved sensors) except the ACB-
EW, which utilises flying leads. Please note that a sensor suffixed by NP is a non-pulsing type and the LED’s will not
flash when polled, but the LED’s will illuminate when the sensor is in a fire condition. The ACA-E, ACB-E, ACB-EM,
ALG-EN, ALG-ENM and ACB-EW polling LED can be turned off at the Control Panel (Control Panel compatibility needs
to be checked to verify if this facility is supported). Follow the guidelines below before installation and maintenance.
Hochiki cannot guarantee a sensor’s performance if these guidelines are not followed.
Caution
Hochiki ESP range sensors cannot be used to prevent fire itself, they are only intended to detect a certain characteristic
of fire. The ACA-E (Heat mode only), ACB-E, ACB-EM and ACB-EW sensors are used to detect conditions and changes
in temperature and cannot detect smoke and other phenomena. When installing the sensor, check that the location of
each one has been planned according to appropriate fire regulations or recommendations. Please note that the ACA-E
Multi-Sensor default mode is optical/heat, if this sensor is to be programmed to change modes i.e.: - optical to heat then
the ACA-E should be spaced as a standard Heat Sensor.
The sensor and base combination should be installed to the following guidelines:
Ensure the Sensor and Base are installed in accordance with Local Standards or Regulations.
Sensor and Base combinations should only be installed where ambient temperatures are between -10°C to +50°C
and where the condensation and moisture levels are between 10% to 95% RH – Non-condensing (at 40°C).
Only install in suitable environments, the following should be avoided.
Situations in which condensation exists.
Situations in which corrosive gases exist.
Situations in which dust or steam exists.
Situations in which obstacles exist, which could impede airflow to the sensor.
Hazardous areas.
Do not use a high voltage tester on any Sensor or any Base with electronics (YBO-BS, YBO-BSB, YBO-R/SCI &
YBO-R/SCIM).
Certain actions can cause permanent damage to the sensor. If the sensor is subjected to any of the following it should
not be used:
Disassembly and re-assembly.
Impact or shock.
Touching the thermistor (ACB-E, ACB-EM, ACB-EW) Heat sensors and ACA-E Multi-Sensor only).
If damage is suspected after a fire has occurred, the sensor should be replaced. After installation, all sensors on the fire
alarm system should be tested to confirm correct operation. Installation and maintenance should only be carried out by
suitably trained engineers. Sensor operation should not be tested with a naked flame or open fire. Operation should
only be checked by equipment that is capable of exceeding the required detection threshold.
The sensor must be subject to periodic maintenance during regular service visits. This period should be outlined in the
appropriate standards or recommendations. If there are no such standards existing, Hochiki recommend that the
minimum period of maintenance should be 1 year and that the following should be taken into account:
A regular operation test should be performed.
A visual check for staining and mechanical damage should be made.
A dust cover is included with the sensor to prevent contamination during installation. The dust cover must be removed
for the sensor to operate.
Setting the Address
Each sensor must have its address set before system operation. Using the installation plan that shows the proper
location for each sensor, find the address for the sensor to be installed. Check that the address and location on the plan
match correctly. Address is any number from 1 to 127. For address setting, use the address programmer and write the
2-3-0-246/ISS10/NOV09
number on the label of the sensor after setting. When address changing, renew the number on the label. See the
instruction of the appropriate address programmer TCH-B100 about detail of setting method. Note that to program the
ACB-EW with the TCH-B100 address programmer, a programming lead (PL-2) must be used (jack plug to croc-clips).
Wiring and Head Locking Mechanism
The bases should be wired as shown in figure 1
below. Note that the ACB-EW features flying leads
for connection to the loop and is supplied with its
own fixing base. The ESP range of Sensors can
also be locked onto the relevant bases by removing
a plastic lug on the underside of the sensor, please
refer to figure 1. The Sensor can then only be
removed by using a special removal tool, which is
available from Hochiki Europe (UK) Ltd.
A: Loop (+) B: Loop (-) C: Cable Screen
ACA-E 0832-CPD-0114 05
EN54-5 Point type heat detectors
EN54-7 Point type smoke detectors
ACB-E 0832-CPD-0122 05 EN54-5 Point type heat detectors
ACB-EW 0832-CPD-0123 05 EN54-5 Point type heat detectors
AIE-E, AIE-E(NP) 0832-CPD-0124 05 EN54-7 Point type smoke detectors
ALG-EN 0832-CPD-0612 08 EN54-7 Point type smoke detectors
Protocol specified in TI/006 ALG-E, ALG-E(NP) 0832-CPD-0110 05 EN54-7 Point type smoke detectors
Fig.1
Remove tab carefully
using a pair of pliers
NOTE:
Maximum current for remote
indicator is 10mA.
Base fixing centres are 48mm to
74mm
Maximum wire thickness is
2.5mm2/terminal
Fig.2
NOTE:
Suitable
waterproof
crimps MUST
be used
between flying
leads and loop
cables.
2-3-0-246/ISS10/NOV09
Hochiki Europe (UK) Ltd
Grosvenor Road, Gillingham Business Park,
Gillingham, Kent, ME8 0SA, England Telephone:
+44(0)1634 260133 Facsimile: +44(0)1634 260132
Email: sales@hochikieurope.com
Web: www.hochikieurope.com
Hochiki Europe (UK) Ltd. reserves the right to alter the
specification of its products from time to time without notice.
Although everyeffort has been made to ensure the accuracy of
the information contained within this document it is not warranted
or represented by Hochiki Europe (UK) Ltd. to be a complete and
up-to-date description. Please check our web site for the latest
version of this document.

This manual suits for next models

11

Popular Accessories manuals by other brands

Intelbras IVA 5015 digital user manual

Intelbras

Intelbras IVA 5015 digital user manual

Caremaxx 60101 manual

Caremaxx

Caremaxx 60101 manual

Carefree APEX owner's manual

Carefree

Carefree APEX owner's manual

Tascam FW-1082 How to install

Tascam

Tascam FW-1082 How to install

Proxitron LID 010 user manual

Proxitron

Proxitron LID 010 user manual

Stellarvue F60 Series quick start guide

Stellarvue

Stellarvue F60 Series quick start guide

Siemens 1218RF user manual

Siemens

Siemens 1218RF user manual

Omega Engineering Wet/Wet Differential Sensor PX838 user guide

Omega Engineering

Omega Engineering Wet/Wet Differential Sensor PX838 user guide

Carel DP user manual

Carel

Carel DP user manual

Atmel ATR4262M1 Specification sheet

Atmel

Atmel ATR4262M1 Specification sheet

FlowLine EchoSwitch LU74 Series quick start

FlowLine

FlowLine EchoSwitch LU74 Series quick start

SunnyBAG POWERPACK user manual

SunnyBAG

SunnyBAG POWERPACK user manual

BEA Iris Overhead Safety for Door Technical specifications

BEA

BEA Iris Overhead Safety for Door Technical specifications

De Haardt XTRA.SECTOR user manual

De Haardt

De Haardt XTRA.SECTOR user manual

EKO MS-95S instruction manual

EKO

EKO MS-95S instruction manual

Knightsbridge DC007 Installation & maintenance manual

Knightsbridge

Knightsbridge DC007 Installation & maintenance manual

IQAmerica WD-1020 quick start guide

IQAmerica

IQAmerica WD-1020 quick start guide

Hytronik HIM38/RF installation manual

Hytronik

Hytronik HIM38/RF installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.