Honeywell RedLINK User manual

RedLINK™Wireless System
With Equipment Interface Module
® U.S. Registered Trademark.
Copyright © 2008 Honeywell International Inc.
All rights reserved.
Wireless control for up to 3 Heat/2 Cool heat pump systems or up to
2 Heat/2 Cool conventional systems.
DISCONNECT POWER BEFORE BEGINNING INSTALLATION. Can cause electrical
shock or equipment damage.
MERCURY NOTICE: If this product is replacing a control that contains mercury in a
sealed tube, do not place the old control in the trash. Contact your local waste
management authority for instructions regarding recycling and proper disposal.
Must be installed by a trained, experienced technician. Read these instructions
carefully. Failure to follow these instructions can damage the product or cause a
hazardous condition.
System
Installation
Guide
Español: vea la página 20 • Français : voir la page 39
Installation guide for:
• Wireless equipment interface module
• FocusPRO®wireless thermostats
• Wireless remote control
• Wireless outdoor air sensor
• Return air sensor

RedLINK™ Installation Guide (EIM)
2
System installation at a glance
The THM5320R equipment interface module (EIM) provides control of all
heating and cooling equipment from any FocusPRO wireless thermostat.
Thermostat
Outdoor
air sensor
Remote
control EIM
Installation procedure
Mount and wire EIM ....................................................Pages 3-4
Install batteries in wireless devices ................................Page 5
Link all devices to wireless network ..........................Pages 5-7
Exit wireless setup ............................................................Page 8
Customize thermostat (installer setup) ....................Pages 8-12
Mount thermostat and outdoor sensor..........................Page 13
To replace system components if needed, see page 15
For system-specific wiring guides, see pages 16-17
4
6
5
3
2
1
DISCONNECT POWER BEFORE BEGINNING INSTALLATION. Can cause electrical
shock or equipment damage.
HVAC equipment
If you have more than one Equipment Interface Module (EIM): Thermostats are
linked to specific EIMs. Optional accessories must be linked to each EIM separately.

Español: vea la página 20 • Français : voir la page 39
3
Mount and wire EIM
1
Mount EIM on wall near HVAC equipment, or on the equipment itself.
Do not install inside HVAC equipment. Use screws & anchors as appropriate
for mounting surface.
EIM wiring
Wiring must comply with local electrical codes.
Strip 1/4” insulation, then insert wires
as shown.
Press tabs only to remove wires from
terminal block if necessary.
Continued on next page >>
Install EIM Install return air sensor (optional)
Install sensor on return air duct at least 12”
(305mm) upstream from ventilator, humidifier
or dehumidifier (do not mount downstream)
Drill 1/4” hole
(6.4mm)
The return air sensor maintains safe indoor
temperature if thermostat power is lost.

EIM wiring guide
Stage 1 heat
FURNACE
Transformer
Stage 2 heat
Fan
24Vac 120Vac
Air conditioning
Compressor
(stage 1)
Compressor
(stage 2)
Return
air sensor
Changeover
relay
Backup heat
(gas/electric)
Relay **
Fan relay
Compressor
(stage 1)
Compressor
(stage 2)
Return
air sensor
EQUIPMENT INTERFACE MODULE
CONVENTIONAL SYSTEMS
EQUIPMENT INTERFACE MODULE
HEAT PUMP SYSTEMS AIR HANDLER
Transformer
24Vac 120Vac
A/B/C/D unused
(reserved for future use)
A/B/C/D unused
(reserved for future use)
See detailed wiring guides for specific system
types on pages 16-17.
4
RedLINK™ Installation Guide (EIM)
** L terminal sends continuous output when thermostat is
set to EmHeat. L terminal is for use with zone panels.

Install batteries in wireless devices
2
When system wiring is complete, install batteries in all devices. Make sure
batteries are inserted properly (see polarity marks on illustrations below).
Link all devices to wireless network
3
Restore AC power, then press the CONNECT
button at the EIM and wait for green
flashing light to begin linking devices to
the wireless network (see pages 6-7).
If the light stops flashing before you
have linked all devices, press CONNECT
again.
Press CONNECT
Thermostat
Install quick reference cardInstall 2 fresh AA
batteries
Remote control (optional) Outdoor air sensor (optional)
Install 3 fresh AA
batteries
Install 2 fresh AA
lithium batteries
Flashing status light times out after 15
minutes of inactivity. Press CONNECT again if
necessary.
5
Español: vea la página 20 • Français : voir la page 39
Programmable models only
Continued on next page >>
If light does not flash, another EIM/wireless
adapter may be in wireless setup mode. Exit
wireless setup at the other EIM/wireless
adapter.

Link thermostat to wireless network
Wireless Setup
00
NextBack
Wireless Setup
36 52
Back Next
Wireless SetupWireless Setup
Back
Press NEXT (always leave zone number set
to zero).
Press NEXT (or see page 11 to change the
zone name if needed).
Press CONNECT to establish a link to the
wireless network.
After a brief pause, the confirmation
screen at left should be displayed, to
verify that the wireless connection has
been established.
Press DONE to display the home screen.
Wireless SetupWireless Setup
Connected
Done
Zone number
Zone name
Connect
6
RedLINK™ Installation Guide (EIM)
Zone numbers 1-4 are for use with TrueZONE
panels only.
If E1 appears, see error codes on page 14.
Change zone name only if you have more than
one thermostat and EIM.

Link remote control to wireless network (optional)
1Make sure the Connected light on the
EIM is flashing (see page 5).
2Press CONNECT at the remote. There will
be a short delay as the remote seeks
a signal from the wireless network.
3When the screen displays
“Connected,” press DONE.
4Press NO at the next screen to save
and exit. (Or press YES and repeat
steps 1-4 to link another EIM.)
WIRELESS SETUP
CONNECT
Link outdoor sensor to wireless network (optional)
1Make sure the Connected light on the
EIM is flashing (see page 5).
2Press the CONNECT button on the back
of the sensor.
3Check thermostat to verify that the
outdoor sensor is working. After
about 15 seconds, the thermostat
should display outdoor temperature
and humidity.
(If you are installing more than one EIM,
repeat steps 1-3 for each.)
Press and release
7
Español: vea la página 20 • Français : voir la page 39
YES NO
CONNECT MORE?
If E1 appears, see error codes on page 14.
The linking procedure may time out if there is
no keypress within 30 minutes. To begin again,
press and hold the blank space (or arrow if
present) in the lower right corner of the screen
until the display changes (about 3 seconds)
Press to link
another EIM
Press to save
and exit

Customize thermostat (installer setup)
5
Function Setting
Press ▲or ▼to change setting
(see tables on pages 9-11)
Press NEXT to display next
function screen
Press DONE to save & exit.
Follow the steps below to begin installer setup. At each function screen,
press ▲or ▼to change the setting as desired, then press NEXT to advance to
the next function screen.
See tables on pages 9-11 for a description of options for each function.
Exit wireless setup
4
Press CONNECT at the EIM to exit wireless setup (light should stop flashing).
10
Back NextDone
00
BackDone Next
To begin, press and hold the FAN and ▲buttons
until the display changes (about 3 seconds).
8
RedLINK™ Installation Guide (EIM)
FAN
Note: The EIM will automatically exit wireless setup after 15 minutes of inactivity.
Note: If installing more than one thermostat and EIM, you must exit wireless setup before
installing an additional thermostat and EIM.

Installer setup tables
0
1
2
3
5
6
7
8
9
10
12
13
14
Zone number
System type
Changeover valve
(O/B terminal)
Fan control
(conventional heat)
Stage 1 heat cycle
rate (CPH= cycles
per hour)
Stage 2 heat
cycle rate (CPH)
Stage 3 heat
cycle rate (CPH)
Emergency heat
cycle rate (CPH)
Stage 1 compres-
sor cycle rate
Stage 2 compres-
sor cycle rate
Manual/Auto
changeover
Adaptive Intelligent
Recovery
Temperature
display
0No zoning (single thermostat used with THM5320R EIM)
[Options: select zone 1, 2, 3 or 4]
0 1 heat/1 cool conventional
1 1 heat/1 cool heat pump (no aux. heat)
2 Heat only (includes Series 20)
3 Heat only with fan
4 Cool only
5 2 heat/1 cool heat pump
6 2 heat/2 cool conventional
7 2 heat/1 cool conventional
8 1 heat/2 cool conventional
9 2 heat/2 cool heat pump
10 3 heat/2 cool heat pump
0 O/B terminal controls valve in cooling
1 O/B terminal controls valve in heating
0 Gas/Oil heat (equipment controls fan)
1 Electric furnace (thermostat controls fan)
5 Gas or oil furnaces (less than 90% efficiency)
1 Steam or gravity systems
3 Hot water systems & furnaces of over 90% efficiency
9 Electric furnaces
[Cycle rate options: 1 to 12 CPH]
5 Gas or oil furnaces (less than 90% efficiency)
1 Steam or gravity systems
3 Hot water systems & furnaces of over 90% efficiency
9 Electric furnaces
[Cycle rate options: 1 to 12 CPH]
5 Gas or oil furnaces (less than 90% efficiency)
1 Steam or gravity systems
3 Hot water systems & furnaces of over 90% efficiency
9 Electric furnaces
[Cycle rate options: 1 to 12 CPH]
9 Electric furnace
[Cycle rate options: 1 to 12 CPH]
3 Recommended cycle rate
[Cycle rate options: 1 to 6 CPH]
3 Recommended cycle rate
[Cycle rate options: 1 to 6 CPH]
0 Manual (User options: Heat/Cool/Off)
1 Automatic (User options: Heat/Cool/Auto/Off)
Applies only to Model TH6320
0Off
1On
0 Fahrenheit
1 Celsius
Setup functions Settings & Options (factory default in bold)
9
Español: vea la página 20 • Français : voir la page 39

15
16
26
27
28
32
33
35
Compressor off
time (minimum)
Schedule format
Auxiliary heat
control
Maximum heat
setpoint
Minimum cool
setpoint
Temp. display
offset (indoor)
Temp. display
offset (outdoor)
Humidity display
offset (outdoor)
5 5 minutes (Heat On/Cool On flashes during off time)
[Options: 0 to 4 minutes]
Applies only to Model TH6320
0 Weekday/weekend program schedule
1 Weekday/Saturday/Sunday program schedule
Applies only to Model TH5320
0 Comfort **
1 Economy
90 Max. heat temperature setting is 90°F (32°C)
[Options: 40 to 90°F (4.5 to 32°C)]
50 Min. cool temperature setting is 50°F (10°C)
[Options: 50 to 99°F (10 to 37°C)]
0 Thermostat displays actual temperature
[Options: -3 to +3°F offset (-1.5 to +1.5°C)]
0 Thermostat displays actual temperature
[Options: -5 to +5°F offset (-2.5 to +2.5°C)]
3 Thermostat displays actual humidity
[Other options: 0 = -15%, 1 = -10%, 2 = -5%,
4 = 5%, 5 = 10%, 6 = 15% offset]
** See page 11
Installer setup tables
Setup functions Settings & Options (factory default in bold)
10
RedLINK™ Installation Guide (EIM)

36
39
90
Zone name
Wireless setup
RESET
52 Thermostat
Installer setup tables
Setup functions Settings & Options (factory default in bold)
0 Disconnect thermostat from wireless system
1 Thermostat is connected to wireless system
0Noreset
1 Reset installer options & program schedule to factory
default settings
1 Basement
2 Bathroom
3 Bathroom 1
4 Bathroom 2
5 Bathroom 3
6 Bedroom
7 Bedroom 1
8 Bedroom 2
9 Bedroom 3
10 Bedroom 4
11 Boat House
12 Bonus Room
13 Computer Room
14 Den
15 Dining Room
16 Exercise Room
17 Family Room
18 Fireplace
19 Foyer
20 Game Room
21 Garage
22 Great Room
23 Guest Room
24 Gym
25 Kid’s Room
26 Kitchen
27 Kitchen 1
28 Kitchen 2
29 Laundry Room
30 Library
31 Living Room
32 Lower Level
33 Master Bath
34 Master Bed
35 Media Room
36 Music Room
37 Nursery
38 Office
39 Office 1
40 Office 2
41 Pantry
42 Play Room
43 Pool Room
44 Porch
45 Rec Room
46 Sewing Room
47 Spa
48 Storage Room
49 Studio
50 Sun Room
51 Theater
52 Thermostat
53 Upper Level
54 Utility Room
55 Walk In Closet
56 Wine Cellar
57 Workshop
Special functions
Comfort/Economy (Setup Function 26):
If you choose Comfort, auxiliary heat will respond quickly to meet the temperature setpoint. If
you choose Economy, the system will wait longer. Auxiliary heat will be activated only if the
setpoint is not reached within a reasonable time.
11
Español: vea la página 20 • Français : voir la page 39

System test
02 0
BackDone Next
To begin, press and hold the ▲and ▼buttons
until the display changes (about 3 seconds)
Press ▲or ▼ to check system status
Press NEXT to advance to next test
Press DONE to terminate system test
02
04
10
20
30
40
70
Wireless test
Return air sensor
Heating system
Emergency
heating system
Cooling system
Fan system
Thermostat
information
(for reference only)
0Off
1 Test radio signal (after a brief pause, screen displays 1-10
to show signal strength; 5 or higher recommended)
Screen displays return air temperature if device is installed
and working properly
0 Heat and fan turn off
1 Heat turns on
2 Stage 2 heat turns on
3 Stage 3 heat turns on
0 Heat and fan turn off
1 Heat and fan turn on
0 Compressor and fan turn off
1 Compressor and fan turn on
2 Stage 2 compressor turns on
0 Fan turns off
1 Fan turns on
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)
System Test System Status
Follow the procedure below to test for proper operation.
System test
number
System
status
12
RedLINK™ Installation Guide (EIM)
CAUTION: EQUIPMENT DAMAGE HAZARD. Compressor protection (minimum off time)
is bypassed during testing. To prevent equipment damage, avoid cycling the compressor
quickly.

Outdoor sensor (optional)
Place sensor securely
in bracket, facing
away from wall
Mount the sensor on a
vertical exterior wall, at
least 6 inches below
any overhang. Choose
a location protected
from direct sunlight.
Mount thermostat & outdoor sensor
6
3/16” holes for drywall
7/32” holes for plaster
Wall anchor
Mounting screw
Detach wallplate
Wallplate
13
Español: vea la página 20 • Français : voir la page 39
To check location before mounting: Restore
thermostat Home screen, then hold the sensor
where you intend to install it and press the CONNECT
button. If sensor is working properly, thermostat will
switch to display outdoor temperature and humidity.
Press and release

Error codes (thermostat & remote control)
If E1 appears during setup, check error code number (right side of screen):
29 Attempting to connect incompatible wireless devices.
30 Invalid zone number. Zone number must be set to zero (see page 6).
33 Faulty return air sensor. Check wiring or replace sensor as needed.
34 Low signal strength. Move wireless device to a different location and try again.
38 Make sure Connected light on EIM is flashing and you are 2+ feet away from EIM.
EIM status lights
System status lights
•Power: EIM is working properly.
•Heat: Heating system is on.
•Cool: Cooling system is on.
•Fan: Fan is on.
Wireless status light
•Solid green: EIM is working properly
and communicating with wireless
devices.
•Flashing green: Linking to wireless
devices (light flashes for 15 minutes
after you press CONNECT).
•Solid red: Communication problem.
Check EIM and wireless devices.
When installation is complete, check the status lights on the equipment
interface module to verify proper operation.
14
RedLINK™ Installation Guide (EIM)
Note: If Connected light is flashing, press
CONNECT button to turn off flashing light, then
recheck status lights.

15
Español: vea la página 20 • Français : voir la page 39
Replacing system components
Thermostat
To replace a thermostat, install batteries and follow the procedures on
pages 5-6 to link it to the wireless network. If necessary, modify settings as
needed (see tables on pages 9-11).
Remote control & outdoor sensor
To replace a remote control or outdoor air sensor, install batteries and
follow the procedures on pages 5-7 to link it to the wireless network.
Equipment interface module (EIM)
After installing a new EIM, you must re-set the thermostat and remote
control to communicate with the new EIM, as described below.
At the thermostat:
1 Press and hold the FAN and ▲buttons for 3 seconds.
2 Press BACK twice to display Function 39 (wireless setup).
3 Press ▼to change Function 39 setting to 0 (disconnect from old EIM).
4 Follow the procedures on pages 5-6 to link to new EIM.
At the remote control:
1 Press and hold the blank space (or arrow if present) in the lower right
corner of the screen until the display changes (about 3 seconds).
2 Press REMOVE , then YES to disconnect from old EIM.
3 Follow the procedure on page 7 to link to new EIM.
Press and hold for
about 3 seconds

Conventional systems
System-specific wiring guides
Cool Only System [5]
C24VAC common
RPower [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
YCompressor contactor
GFan relay
1H/1C System (2 transformers)
C24VAC common
RPower [1]
Rc Power (cooling) [1, 2]
Rh Power (heating) [1, 2]
WHeat relay
YCompressor contactor
GFan relay
2H/2C System (1 transformer) [6]
C24VAC common
RPower [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
WHeat relay (stage 1)
W2 Heat relay (stage 2)
YCompressor contactor (stage 1)
Y2 Compressor contactor (stage 2)
GFan relay
2H/2C System (2 transformers) [6]
C24VAC common
RPower [1]
Rc Power (cooling) [1, 2]
Rh Power (heating) [1, 2]
WHeat relay (stage 1)
W2 Heat relay (stage 2)
YCompressor contactor (stage 1)
Y2 Compressor contactor (stage 2)
GFan relay
1H/1C System (1 transformer)
C24VAC common
RPower [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
WHeat relay
YCompressor contactor
GFan relay
Heat Only System [3]
C24VAC common
RPower [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
WHeat relay
Heat Only System (Series 20) [3]
C24VAC common
RSeries 20 valve terminal “R” [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
WSeries 20 valve terminal “B”
YSeries 20 valve terminal “W”
Heat Only System
(Normally open zone valve) [3]
C24VAC common
RPower [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
YNormally open zone valve
Heat Only System With Fan [4]
C24VAC common
RPower [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
WHeat relay
GFan relay
See [notes] on next page.
16
RedLINK™ Installation Guide (EIM)

17
Español: vea la página 20 • Français : voir la page 39
System-specific wiring guides
Heat pump systems
2H/2C Heat Pump [10]
C24VAC common
RPower [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
O/B Changeover valve [7]
YCompressor contactor (stage 1)
Y2 Compressor contactor (stage 2)
GFan relay
3H/2C Heat Pump [11]
C24VAC common
RPower [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
O/B Changeover valve [7]
Aux Auxiliary heat relay
YCompressor contactor (stage 1)
Y2 Compressor contactor (stage 2)
GFan relay
LRelay [12]
[1] Power supply. Provide disconnect means and overload protection as required.
[2] Remove jumper (Rc to Rh) for systems with two transformers.
[3] In Installer Setup, set system type to Heat Only.
[4] In Installer Setup, set system type to Heat Only with Fan.
[5] In Installer Setup, set system type to Cool Only.
[6] In Installer Setup, set system type to 2 Heat/2 Cool Conventional.
[7] In Installer Setup, set changeover valve to O or B.
[8] In Installer Setup, set system type to 1 Heat/1 Cool Heat Pump.
[9] In Installer Setup, set system type to 2 Heat/1 Cool Heat Pump.
[10] In Installer Setup, set system type to 2 Heat/2 Cool Heat Pump.
[11] In Installer Setup, set system type to 3 Heat/2 Cool Heat Pump.
[12] “L” terminal sends a continuous output when thermostat is set to Em. Heat.
Connect to zoning panel and switch to Emergency Heat.
1H/1C Heat Pump [8]
C24VAC common
RPower [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
O/B Changeover valve [7]
YCompressor contactor
GFan relay
2H/1C Heat Pump [9]
C24VAC common
RPower [1]
Rc [R+Rc+Rh joined by jumper]
Rh [R+Rc+Rh joined by jumper]
O/B Changeover valve [7]
Aux Auxiliary heat relay
YCompressor contactor
GFan relay
LRelay [12]
See [notes] below.

18
RedLINK™ Installation Guide (EIM)
Specifications & replacement parts
Operating Ambient Temperature
Thermostat: 32 to 120° F (0 to 48.9° C)
Remote control: 32 to 120° F (0 to 48.9° C)
EIM: -40 to 165° F (-40 to 73.9° C)
Outdoor air sensor: -40 to 140° F (-40 to 60° C)
Return air sensor: 0 to 200° F (-17.8 to 93.3° C)
Operating Relative Humidity
Thermostat: 5% to 90% (non-condensing)
Remote control: 5% to 90% (non-condensing)
EIM: 5% to 95% (non-condensing)
Outdoor air sensor: 0% to 100% (condensing)
Physical Dimensions (height, width, depth)
Thermostat: 3-9/16 x 5-13/16 x 1-1/2 inches (91 x 147 x 38 mm)
EIM: 8-1/8 x 8 x 1-7/8 inches (206 x 203 x 47 mm)
Outdoor air sensor: 5 x 3-1/2 x 1-11/16 inches (127 x 89 x 43 mm)
Return air sensor: 3-7/8 x 4-1/8 x 1-1/4 inches (77 x 102 x 25 mm)
Sensor probe is 3-3/4 inches long (77 mm)
Electrical Ratings (EIM)
Terminal Voltage (50/60 Hz) Running Current
W(heating) 18 to 30 VAC 1.00A
Y(cooling) 18 to 30 VAC 1.00A
G(fan) 18 to 30 VAC 0.60A
O/B (changeover) 18 to 30 VAC 0.60A
W2 (heating) 18 to 30 VAC 0.60A
Y2 (cooling) 18 to 30 VAC 0.60A
Aux/E (Auxiliary) 18 to 30 VAC 1.00A
L(Output) 18 to 30 VAC 0.60A
Accessories & Replacement Parts
Item Part Number
Equipment Interface Module (EIM) THM5320R1000
Wireless adapter THM4000R1000
FocusPRO®wireless thermostat (programmable) TH6320R1004
FocusPRO®wireless thermostat (non-programmable) TH5320R1002
Remote control REM5000R1001
Outdoor air sensor C7089R1013
Return air sensor C7735A1000
Battery holder 50007072-001
Cover plate (covers marks left by old thermostats) 50002883-001

19
Español: vea la página 20 • Français : voir la page 39
Regulatory information
FCC Compliance Statement (Part 15.19) (USA only)
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions:
1 This device may not cause harmful interference, and
2 This device must accept any interference received, including interference that may cause
undesired operation.
FCC Warning (Part 15.21) (USA only)
Changes or modifications not expressly approved by the party responsible for compliance
could void the user’s authority to operate the equipment.
FCC Interference Statement (Part 15.105 (b)) (USA only)
This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates
uses and can radiate radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct the interference by one of
the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
• Consult the dealer or an experienced radio/TV technician for help.
EIM, thermostats and outdoor sensor
To comply with FCC and Industry Canada RF exposure limits for general population/ uncon-
trolled exposure, the antenna(s) used for these transmitters must be installed to provide a sep-
aration distance of at least 20 cm from all persons and must not be co-located or operating in
conjunction with any other antenna or transmitter.
Remote control
This portable transmitter with its antenna complies with FCC and Industry Canada RF
exposure limits for general population/uncontrolled exposure.
Section 7.1.5 of RSS-GEN
Operation is subject to the following two conditions:
1 this device may not cause interference, and
2 this device must accept any interference, including interference that may cause undesired
operation of the device.

Sistema inalámbrico RedLINK™
Con módulo de interfaz del equipo
® Marca registrada de los EE. UU.
Copyright © 2008 Honeywell International Inc.
Todos los derechos reservados.
Control inalámbrico para sistemas de bomba de calor de hasta 3 calentadores/2
refrigeradores o sistemas convencionales de hasta 2 calentadores/2 refrigeradores.
DESCONECTE LA ENERGÍA ANTES DE COMENZAR LA INSTALACIÓN. Puede
causar una descarga eléctrica o daños al equipo.
AVISO SOBRE MERCURIO: si este producto reemplaza un control que contiene mer-
curio en un tubo sellado, no coloque el control anterior en la basura. Comuníquese
con la oficina de gestión de residuos de su localidad para obtener instrucciones sobre
cómo reciclar o desechar el producto de manera adecuada.
La instalación debe ser realizada por un técnico capacitado y experimentado.
Lea detenidamente estas instrucciones. Si no sigue estas instrucciones, corre el riesgo
de dañar el producto o de provocar una situación peligrosa.
Guía de
instalación
del sistema
Español: vea la página 20 • Français : voir la page 39
Guía de instalación para:
• Módulo de interfaz inalámbrico del equipo
• Termostatos inalámbricos FocusPRO®
• Control remoto inalámbrico
• Sensor de aire exterior inalámbrico
• Sensor de aire de retorno
Other manuals for RedLINK
4
Table of contents
Languages:
Other Honeywell Microphone System manuals
Popular Microphone System manuals by other brands

Audio Technica
Audio Technica 5000 Series user manual

Alfa Fiber System, Inc.
Alfa Fiber System, Inc. Series AFS2300 Installation & operation instructions

Chord
Chord HU6 user manual

Audio Technica
Audio Technica ATW-1101 Installation and operation

Audio Technica
Audio Technica ATW-601 Installation and operation

Toa
Toa WT-4800 Specifications