manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Monitor
  8. •
  9. Honeywell Multi-Mon User manual

Honeywell Multi-Mon User manual

INSTALLATION INSTRUCTIONS
31-00035-01
Multi-Mon
MULTIPLE CIRCUIT ENERGY MONITOR
SECTION 1:
GENERAL INFORMATION
The Multi-Mon is a 3-phase, multi-channel, multi-function
energy meter suitable for use in single-phase and multi-phase
electrical networks.
Meter highlights
• Multi-channel submetering – up to 36 single-phase or 18
two-phase or 12 three-phase submeters in a single device.
Any combination of single-, two-, and three-phase
consumers can be chosen up to a total of 36 current inputs.
• Automatic totalization energy from different sub-consumers
FEATURES
• Calibrated to meet Class 0.5S active energy and Class 1
reactive energy meter accuracy
• 3-phase/2-phase/single-phase meters (true RMS, volts,
amps, power, power factor, neutral current)
• Ampere/Volt demand meter
• Time-of-Use, 4 energy/demand registers x 6 tariffs1, 4
seasons x 4 types of days, 8 tariff changes per day, easy
programmable tariff schedule
• Import/export energy and power demands
• Automatic 120–day daily profile for import/export2 energy
and maximum demand readings (total and tariff registers)
separate for each submeter
• Event recorder for logging internal diagnostic events and
setpoint operations
• Data recorders; programmable periodical data logs
separate for each submeter
• Embedded programmable controller (4 control setpoints,
programmable thresholds and delays) separate for each
submeter
• Easy to read 2-row x 16 characters LCD display with
backlight (Multi-Mon only)
• 50/60 Hz operation
• Internal clock, keeping the clock running over one week
without external power
• Highly Accurate Current Transformer with overvoltage
protection diodes to avoid any damage while disconnecting
the primary current sensor
• Standard RS-485 serial port
• Optional second communication port. Communication
options available:
— RS-232
— RS-422/485
— 56K Dial-up modem
— Ethernet 10/100BaseT
• Modbus RTU and Modbus ASCII communication protocols
• Easy field upgrading device firmware through any
communication port
MULTI-MON
31-00035—01 2
THIS PACKAGE CONTAINS
Multi-Mon
Highly Accurate Current Sensors
(HACS), according to your request.
HACS - 100A – (solid core) Internal Hole 12 mm (0.47")
HACS - 100A – (solid core) Internal Hole 23 mm (0.91")
HACS - 400A – (solid core) Internal Hole 26 mm (1.02")
HACS - 100A – (solid core) Internal Hole 16 mm (0.63")
Designator Label Sets
Labeling
Fig. 1. Device label - Wye wiring configuration.
Fig. 2. Device label - Wye/Delta wiring configuration.
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
1
2
3
4
5
6
7
8
9
M35306
HACS DESIGNATOR LABEL SET - TO ATTACH TO THE HACS
CABLE DESIGNATOR TIE-MARKER
ENERGY METER
36FZ
MEASUREMENT VOLTAGES :
(115) 88-138VAC OR (230/277) 176-320VAC
50/60 Hz 10VA
COM1
RS-485
COM2:
S/N
RS-232 RS-485
MODEM ETHERNET
RF
USE ONLY WITH THE SUPPLIED
CURRENT TRANSFORMERS !
M35315
MEASUREMENT VOLTAGES :
(115) 88-138VAC OR (230/277) 176-320VAC
50/60 Hz 10VA
COM1
RS-485
COM2:
S/N
RS-232 RS-485
MODEM ETHERNET
RF
USE ONLY WITH THE SUPPLIED
CURRENT TRANSFORMERS !
480V
M35316
MULTI-MON
331-00035—01
LIMITED WARRANTY
The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship or parts from date
of dispatch from the distributor. In all cases, this warranty is valid for 36 months from the date of production. This warranty is on a
return to factory basis.
This warranty is only applicable to Multi-Mon instruments using Multi-Mon current transformers.
The manufacturer does not accept liability for any damage caused by instrument malfunction. The manufacturer accepts no
responsibility for the suitability of the instrument to the application for which it was purchased.
Failure to install, set up or operate the instrument according to the instructions herein will void the warranty.
Only a duly authorized representative of the manufacturer may open your instrument. The unit should only be opened in a fully
anti-static environment. Failure to do so may damage the electronic components and will void the warranty.
The greatest care has been taken to manufacture and calibrate your instrument. However, these instructions do not cover all
possible contingencies that may arise during installation, operation or maintenance, and all details and variations of this
equipment are not covered by these instructions.
For additional information regarding installation, operation or maintenance of this instrument, contact the manufacturer or your
local representative or distributor.
WARNING
WARNING
Read the instructions in this manual before performing installation and take note of the following precautions:
Multi-Mon is intended for measurements performed in building installations, relating to measurement category III
(UL61010-1, 6.7.4).
Ensure that all incoming AC power and other power sources are turned OFF before performing any work on the
instrument. Failure to do so may result in serious or even fatal injury and/or equipment damage.
Before connecting the instrument to the power source, check the labels at the front of the instrument to ensure that your
instrument is equipped with the appropriate rating input voltages and currents.
Under no circumstances should the instrument be connected to a power source if it is damaged.
To prevent potential fire or shock hazard, do not expose the instrument to rain or moisture.
While installing Multi-Mon CTs to the secondary of an external third party current transformer, the external current
transformer secondary output must never be allowed to be open circuit when the primary is energized. An open circuit
can cause high voltages, possibly resulting in equipment damage, fire and even serious or fatal injury. Ensure that the
current transformer wiring is secured using an external strain relief to reduce mechanical strain on the screw terminals,
if necessary.
Only qualified personnel familiar with the instrument and its associated electrical equipment must perform setup
procedures.
Do not open the instrument under any circumstances when it is connected to a power source.
Do not use the instrument for primary protection functions where failure of the device can cause fire, injury or death. The
instrument can only be used for secondary protection if needed.
Read this manual thoroughly before connecting the device to the current carrying circuits. During operation of the
device, hazardous voltages are present on input terminals. Failure to observe precautions can result in serious or even
fatal injury or damage to equipment.
MULTI-MON
31-00035—01 4
SECTION 2:
INSTALLATION
Mechanical Installation
Fig. 3. Multi-Mon dimensions.
M35317
5-1/16 (129)
2-13/32 (61)
4-35/64 (116)
2-9/32 (58)
27/64
(11)
17/32
(14)
13/32
(10)
4-1/4 (108)
49/64
(20)
11-19/64
(287)
13-3/64
(331)
11-31/32
(304)
21/32
(17)
Ø7/32
(6)
MULTI-MON
531-00035—01
Fig. 4. Wall mounting.
Fig. 5. DIN rail mounting.
M35318
M35319
MULTI-MON
31-00035—01 6
Fig. 6. Single HACS dimensions.
Electrical Installation
Multi-Mon offers maximum flexibility of current connections by using the variety of Highly Accurate Current Transformer (HACS)
options and by wiring any Highly Accurate Current Transformer to any current input of the device. The following drawings present
applications serviced by the Multi-Mon.
Fig. 7. Typical electrical installation - Wye wiring.
M35320
Ø15/32
(12)
1-27/64
(36)
2-3/64
(52)
55/64 (22)
55/64
(22)
98-27/64
(2,500)
Ø9/64
(3)
1-45/64
(43)
M35217
LINE
A B C N
A
B
C
N
LOAD 1
...............
HACS1
+
+
HACS2 LOAD 6
+HACS3
+
+
+
N
C
B
A
LOAD 7
...............
+
+
+
LOAD 12 +
+
+
SW1
6A
HACS16
HACS17
HACS18
HACS19 HACS21
HACS20
HACS34 HACS36
HACS35
MULTI-MON
731-00035—01
Fig. 8. Typical electrical installation - Delta wiring.
Fig. 9. Single highly accurate current transformer wiring and labeling.
M35321
LINE
A B C
A
B
C
LOAD 1 ...............
HACS1
+
+
HACS2 LOAD 6
+HACS3
+
+
+
C
B
A
LOAD 7 ...............
+
+
+
LOAD 12 +
+
+
SW1
6A
HACS16
HACS17
HACS18
HACS19 HACS21
HACS20
HACS34 HACS36
HACS35
M35218
HACS (SPLIT
CORE) K
L
LO
BLACK
WHITE
–
+
R
L
l
s
HACS (SOLID CORE)
SECONDARY
WIRE
RED ORANGE
+–
STICKERS TO HACS
I1
I2
I3
I4
I5
I6
I7
I8
I9
I10
I11
I12
I13
I14
I15
I16
I17
I18
I19
I20
I21
I22
I23
I24
I25
I26
I27
I28
I29
I30
I31
I32
I33
I34
I35
I36
17
17
17
MULTI-MON
31-00035—01 8
WARNING
Before installation ensure that all incoming power
sources are shut OFF. Failure to observe this
practice can result in serious or even fatal injury
and damage to equipment.
IMPORTANT
USE ONLY WITH SUPPLIED BFM CURRENT
TRANSFORMERS.
Connect the wires to the + and - inlets according to the
following polarity colors:
It is recommended to mark the cables and CTs with the
supplied tie markers.
CTs stickers I1 through I36 correspond to the Multi-Mon
current inputs with matching labels. Cable stickers 1 through
12 correspond to the Multi-Mon current terminal blocks with
matching labels.
Use the table from Appendix B to annotate your input
assignments and wiring connections.
LABELING EXAMPLE:
Assume you want to connect three HACSs to the device
terminal block 3 so these three HACSs would be connected to
the device inputs I7, I8, and I9 respectively:
1.
Take a CT connection cable, attach a tie wrap marker to
each side of the cable and mark them as 3 to indicate
that it should be connected to the device terminal block 3.
2. Put the CT label stickers I7, I8, and I9 directly on
HACSs to indicate that these HACSs will be associated
with the device current terminals I7, I8, and I9.
Safety Requirements
To ensure safety requirements the Multi-Mon must be
grounded - the protective ground terminal should be
connected to protective earth with a copper conductor or strap
with minimal length (less than 1 m desirable) and cross-
section 5.3 mm2(AWG10) at least.
The properly marked external 3-pole disconnect device with
circuit-breaker and a fuse 6 A, 600 V in every pole should be
installed between voltage measurement terminals and power
lines, located as close as possible (less than 2 m
recommended) to the Multi-Mon, as shown in figure 2-5.
Fig. 10. External CT connection to meter CT.
Polarity
Solid Core Current
Transformer secondary
Split Core Current
Transformer secondary
+RED WHITE
- ORANGE BLACK
M35322
P1
S1
200/5
S2
LOAD
HIGH CURRENT
DIRECT CT
NOTE:
5 TURNS
SETUP=2X CT PRIMARY E.G. 200/5=400
IN+
OUT–
MULTI-MON CT
RED (+)
ORANGE (–)
TO BFM
MULTI-MON
931-00035—01
Communications
Several communications options are available for the Multi-Mon.
Fig. 11. Communication options.
Fig. 12. RS-485 2-wire connection.
Fig. 13. RS-485 multidrop connection.
RS485
RF
RS485
DIAL-UP
MODEM
TELEPHON
RS485
RS232
RS485
NONE
RS485
ETHERNET
RS485
RS485/422
+
Rx
Tx
M35323
–
+
RS-485
(PLC)
PC
+
M35324
UP TO 31
DEVICES
2R t1
MASTER
RS-232
RXD
TXD
TX ENABLE
RXD
RS-422/ RS-485
TXD
POWER
UP TO 32 POWERMETERS
CABLE MAXIMUM LENGTH 1000M
RS485RS232
RS485/422-232
+
SHLD
-
CONVERTER
SHLD SHLD SHLD
Rt
SUPPLY
COMMUNICATIONCONVERTER
N
L
POWER
-+-+-+
t1,Rt
R 2=200-500 Ohm, 0.5W
+
M35325
MULTI-MON
+
MULTI-MON
+
MULTI-MON
MULTI-MON
31-00035—01 10
Fig. 14. RS-422/485 4-wire connection.
Fig. 15. RS-232 connection.
Fig. 16. RS-232 cable drawings.
+Tx-Tx
-Rx +Rx
RS-422 COMMUNICATION PORT
4 WIRE CONNECTION
SYSTEM
TO COMMUNICATION
Tx
Rx
Tx
Rx
M35326
SG
RX
TX
Rx
Tx
51234
6 87 9
M35327
COMPUTER CONNECTIONS RS-232
MULTI-MON
RS232
MALE CON.
IBM PC/COMPATIBLE
25-PIN DB25
FEMALE CON.
RS-232 SIMPLE 3-WIRE
CONNECTION 25-PIN
RS-232 SIMPLE 3-WIRE
CONNECTION 9-PIN
M35328
MULTI-MON
RS232
MALE CON.
IBM PC/COMPATIBLE
9-PIN DB9
FEMALE CON.
5
2
3
SG
TxD
RxD
GND
RxD
TxD
7
3
2
5
2
3
SG
TxD
RxD
GND
RxD
TxD
5
2
3
MULTI-MON
11 31-00035—01
Fig. 17. Modem connection.
Fig. 18. Ethernet connection.
Controls and Indicators
Fig. 19.
INDICATOR LEDS
The flashing yellow CPU LED shows that the device is
operational and is functioning normally.
The green TX and RX LEDs indicate activity on the COM1
communication port. The LEDs flash when the port is
receiving or transmitting data.
ENERGY PULSE LED
The red “Wh” LED flashes at a user-programmed rate when a
load is applied to the device. In normal mode, the LED pulses
indicate imported Wh for a selected submeter. In energy test
mode, the LED pulses indicate either imported Wh, or
imported (inductive) varh for a selected submeter. Energy test
M35329
MODEM CONNECTION
RS485
ETHERNET
M35330
ETHERNET CONNECTION
M35219
VOLTAGES AND
POWER SUPPLY
TERMINAL
HACS CONNECTOR
WALL MOUNT TAB
ENERGY
PULSE LED
CPU STATUS
LED
COM1
CONNECTOR
COM1
INDICATIONS
KEYPAD
GROUND POST
MULTI-MON
31-00035—01 12
mode is used for testing the device energy measurement
accuracy. In test mode, the energy and demand accumulators
do not account for consumed energy.
See Device Options in Section 3 and General Meter Setup in
Section 4 on how to put the device into energy test mode and
how to select the LED pulse rate and a submeter for testing.
FRONT PANEL DISPLAY
The Multi-Mon is provided with an LCD display and four push
buttons that are used for local meter reading and setup. See
Multi-Mon Display Operations in Section 3 for information on
using the front panel display.
Device Settings
Before operating your Multi-Mon, provide the device with
information about your particular environment. The device
front display (see Display Operations (Multi-Mon)) and the
supplementary Power Software (see Power Software
Application Software) allow you to configure the Multi-Mon for
your particular use.
PASSWORD
The Multi-Mon configuration setups are secured by a factory-
preset password. Contact your dealer for your primary
password. Later, you will be able to change the password via
the device Access Menu (see Meter Security).
SUBMETER SYSTEM
The Multi-Mon provides up to 36 submeters with separate
measurement and energy registers. Each submeter can
service current inputs dedicated to a particular consumer
(metering submeter) or be used as a totalization meter for
automatic totalization of energy from different sub-consumers
(totalization submeter). Additionally, the Multi-Mon provides
four more totalization submeters (37 through 40) that you can
use for totalization purposes when all 36 metering submeters
have been utilized.
A submeter remains inactive while there are no current inputs
associated with the submeter (see Channel Assignments), or
until you link another submeter as a source to its energy
registers making it a totalization submeter (see Setting up
Total and Tariff Registers). The Channel Assignment setup
allows you to link one to three current inputs to each submeter
and to specify the primary rating of the current transformers. A
totalization submeter provides totalization of energy from any
number of metering and totalization submeters.
By default, your device is configured for 12 three-phase
metering submeters with 100 A (maximum) current inputs
(50 A nominal rating).
SUBMETER ADDRESSING
The Multi-Mon uses the Modbus communication protocol for
data transmission and accessing setups through
communications. A full description of the communications
protocol is found in the Multi-Mon Modbus Reference Guide
provided with your device.
Each active submeter in the Multi-Mon is assigned a unique
communication address that allows accessing its private
registers and setups. All submeter addresses are assigned
automatically in a sequential order starting with the device
base address that is programmed through the device
Communication Setup (see Setting Up Communication Ports).
The following table illustrates submeter addressing in the
device with the base address N.
Your device is factory preset to address 1 and occupies the
range of addresses 1 through 12, configured for 12 three-
phase submeters.
NOTES:
1. Device setup settings, excluding the alarm set-
points and data log setup,are shared across all
submeters. Though you can read or write them
using any submeter address, your changes affect
all submeters in the device.
2. When using the ExpertPower client, submeter
address 99 on the Ethernet port COM2 is
reserved for the Multi-Mon router and must not fall
inside the range of the submeter addresses for
this port.
Select your submeters (both metering and totalization) in a
sequence without gaps so that your device does not occupy
unnecessary network addresses.
If you connect a number of devices to a serial network,
allocate a range of addresses for each device so that they do
not overlap. For example, if you use three devices with 12
submeters in each one, assign the base address 1 to the first
device, the address 13 to the second, and the address 25 to
the third device so that they will occupy three non-overlapped
address ranges 1 through 12, 13 through 24, and 25 through
36.
BASIC DEVICE SETTINGS
For proper device operation, select the correct power
frequency (see Basic Device Settings) and set the correct
primary ratings for device current inputs (see Channel
Assignments) before you connect the device to your network.
ENERGY/TOU SYSTEM
The Multi-Mon provides 4 separate billing energy (total/
summary and parallel tariff and maximum demand) registers
for each individual submeter. Each register can be linked to
any internal energy source or another submeter. The first
billing register in your meter is linked to the kWh accumulator
by default. Other registers are not operational unless you
configure them through the Energy/TOU Setup (see
Configuring Billing Energy and TOU Registers).
Device Diagnostics
Device diagnostic messages may appear as a result of the
Multi-Mon built-in diagnostic tests performed during start-up
and device operation. See Device Diagnostic Codes in
Appendix F for the list of diagnostic codes and their meanings.
Device Base
Address Submeter Number Submeter Address
NSM1 N
SM 2 N+1
…
SM 36 N+35
SM 37 N+36
…
SM 40 N+39
MULTI-MON
13 31-00035—01
The device diagnostics status is stored in a non-volatile
register, which may be inspected and cleared via Power
Software, from the meter display or from a user application. All
diagnostic events with time stamps are also recorded in the
device Event log and can be inspected via Power Software
(see Retrieving the Event Log in Section 4).
See Diagnostics Display and Reset in Section 3 on how to
inspect and clear the device diagnostics status from the
display. See Viewing and Clearing Device Diagnostics in
Section 4 on how to inspect and clear the device diagnostics
status via Power Software. Refer to the Multi-Mon Modbus
Reference Guide for the diagnostic register address and
layout.
In the event of a device fault, check the fault reason and clear
the device diagnostics. In the event of a time fault, update the
device clock. In the event of a configuration reset, check the
setup affected by the fault via the device Event log, and then
verify the setup data.
Hardware failures are normally non-critical recoverable faults
that do not cause a system failure but may cause data loss.
Hardware failures are often caused by excessive electrical
noise in the region of the device.
If the device continuously resets itself, contact your local
distributor.
SECTION 3:
MULTI-MON DISPLAY OPERATIONS
Startup Diagnostics
After applying power to the meter, a start-up diagnostic
message is displayed for one second. “Power Up” indicates a
normal power-up sequence. You can observe the list of device
diagnostic codes recorded during restart and device operation
via the Status Display.
See Device Diagnostic Codes in Appendix F for the list of
diagnostic messages.
Display Features
The multifunctional 2x16 alphanumeric LCD display with
backlight allows easy read outs of the measurement
parameters both in the dark and under sunlight. The menu-
driven multi-page display allows viewing numerous
measurement parameters by scrolling through display screens
and pages.
SUBMETER DISPLAYS
In display mode, the display shows readings for the currently
selected submeter. Its number is indicated at the upper-left
corner of the display. To scroll through active submeters, press
and hold the SELECT button, and then use the UP/DOWN
buttons to move to another submeter.
DISPLAY UPDATE
The display is updated by default once per second; you can
adjust the display update rate via the Display Setup Menu.
AUTO RETURN
If no buttons are pressed for 5 minutes and the display Auto
Return option is not disabled, the display will automatically
return to the real-time screen mode from any other
measurement display or programming mode. The Auto Return
option can be disabled through the Display Setup Menu.
AUTO SCROLL
If no buttons are pressed for 30 seconds while the display is in
the real-time screen mode, and the Auto Scroll option is
enabled in the Multi-Mon, the measurement display will scroll
automatically through all submeters. The scroll interval can be
adjusted through the Display Setup Menu. To stop auto
scrolling, press any button.
BACKLIGHT
If no buttons are pressed for 1 minute, the Multi-Mon turns the
backlight off. To restore the backlight, press any button briefly.
Navigation Buttons
The Multi-Mon has four push buttons that are normally used to
navigate between screen modes and pages. In programming
mode, the buttons allow you to navigate through device setup
menus and to change the device settings.
The SELECT button functionality:
• In display mode:
Hold down the SELECT button, and then
use the UP or DOWN button to scroll
through the submeters.
Press the SELECT button for more than
5 seconds to enter programming mode.
• In programming mode:
Press briefly the SELECT button to
highlight/activate a menu item or to
highlight a digit for changing when
entering numbers.
The UP and DOWN buttons functionality:
• In display mode:
Press briefly the UP or DOWN button to scroll through the
display pages.
Hold down the SELECT button and then press briefly the
UP or DOWN button to scroll through the submeters.
Press the UP and DOWN buttons together to move to the
default display page.
• In programming mode:
Use the UP and DOWN buttons to scrolls through the
menu options or to change a selected digit when entering
numbers.
The ENTER button functionality:
• In display mode:
Press briefly the ENTER button to scrolls through the
different screen modes
• In programming mode:
Press briefly the ENTER button to select a highlighted
menu item and to enter a submenu, or to store a changed
item.
Display Views
The Multi-Mon display has 5 multi-page screen modes for
viewing numerous measurement parameters shown in the
following tables. Scroll through the screen modes by briefly
MULTI-MON
31-00035—01 14
pressing the ENTER button. Scroll through the display pages
within the selected mode by briefly pressing the UP and
DOWN buttons.
Summary/TOU Energy
Page # Page content Description
1 Reg.1 kWh
Trf.1 32.535
KWH
Ta r if f 1
2 Reg.1 kWh
Trf.2 7.465
KWH
Ta r if f 2
3 Reg.1 kWh
Trf.3 0.535
KWH
Ta r if f 3
4 Reg.1 kWh
Trf.4 0.465
KWH
Ta r if f 4
5 Reg.1 kWh
Trf.5 0.777
KWH
Ta r if f 5
6 Reg.1 kWh
Trf.6 1.535
KWH
Ta r if f 6
7 Reg.1 kWh
Tot. 43.312
KWH
To t a l
8 Reg.2 kvarh
Trf.1 0.100
kvarh
Ta r if f 1
9 Reg.2 kvarh
Trf.2 0.117
kvarh
Ta r if f 2
10 Reg.2 kvarh
Trf.3 0.235
kvarh
Ta r if f 3
11 Reg.2 kvarh
Trf.4 0.050
kvarh
Ta r if f 4
12 Reg.2 kvarh
Trf.5 0.235
kvarh
Ta r if f 5
13 Reg.2 kvarh
Trf.6 0.050
kvarh
Ta r if f 6
14 Reg.2 kvarh
Tot. 0.787
Kvarh
To t a l
15 Reg.3 kVAh
Trf.1 32.535
kVAh
Ta r if f 1
16 Reg.3 kVAh
Trf.2 7.469
kVAh
Ta r if f 2
17 Reg.3 kVAh
Trf.3 0.584
kVAh
Ta r if f 3
18 Reg.3 kVAh
Trf.4 0.468
kVAh
Ta r if f 4
19 Reg.3 kVAh
Trf.5 0.584
kVAh
Ta r if f 5
20 Reg.3 kVAh
Trf.6 0.468
kVAh
Ta r if f 6
21 Reg.3 kVAh
Tot. 42.575
kVAh
To t a l
Real Time Measurements
Page
# Page content Description
1 V1 120.5 V Volts
2 V2 120.5 V Volts
3 V3 120.5 V Volts
4 V L12 208.1 V Line to line volts
5 V L23 208.1 V Line to line volts
6 V L31 208.1 V Line to line volts
7 I1 neg 5.58 A Amps. The neg label appears in
the case of a reverse current
connection.
8 I2 neg 7.70 A Amps. The neg label appears in
the case of a reverse current
connection.
9 I3 neg 5.58 A Amps. The neg label appears in
the case of a reverse current
connection.
10 Tot. kW 1.558 Total kW
11 Tot.PF 0.997 Total power factor
12 Tot. kVA 1.601 Total kVA
13 Tot. kvar 0.097 Total kvar
14 Freq. 60.00 Hz Frequency
15 V1.Ang 0.0
I1. Ang 0.0
Phase 1 angles
16 V2. Ang -120.0
I2. Ang -120.0
Phase 2 angles
17 V3. Ang 120.0
I3. Ang 120.0
Phase 3 angles
MULTI-MON
15 31-00035—01
Summary/TOU Max. Demands
Page
# Page content Description
1 Reg.1 MD kW
Trf.1 32.535
KW maximum demand
Ta r if f 1
2 Reg.1 MD kW
Trf.2 7.465
KW maximum demand
Ta r if f 2
3 Reg.1 MD kW
Trf.3 0.535
KW maximum demand
Ta r if f 3
4 Reg.1 MD kW
Trf.4 0.465
KW maximum demand
Ta r if f 4
5 Reg.1 MD kW
Trf.5 0.535
KW maximum demand
Ta r if f 5
6 Reg.1 MD kW
Trf.6 0.465
KW maximum demand
Ta r if f 6
7 Reg.1 MD kW
Tot. 42.000
KW maximum demand
To t a l
8 Reg.2 MD kvar
Trf.1 0.100
kvar maximum demand
Ta r if f 1
9 Reg.2 MD kvar
Trf.2 0.117
kvar maximum demand
Ta r if f 2
10 Reg.2 MD kvar
Trf.3 0.235
kvar maximum demand
Ta r if f 3
11 Reg.2 MD kvar
Trf.4 0.050
kvar maximum demand
Ta r if f 4
12 Reg.2 MD kvar
Trf.5 0.235
kvar maximum demand
Ta r if f 5
13 Reg.2 MD kvar
Trf.6 0.050
kvar maximum demand
Ta r if f 6
14 Reg.2 MD kvar
Tot. 0.787
kvar maximum demand
To t a l
15 Reg.3 MD kVA
Trf.1 32.535
kVA maximum demand
Ta r if f 1
16 Reg.3 MD kVA
Trf.2 7.469
kVA maximum demand
Ta r if f 2
17 Reg.3 MD kVA
Trf.3 0.584
kVA maximum demand
Ta r if f 3
18 Reg.3 MD kVA
Trf.4 0.468
kVA maximum demand
Ta r if f 4
19 Reg.3 MD kVA
Trf.5 0.584
kVA maximum demand
Ta r if f 5
20 Reg.3 MD kVA
Trf.6 0.468
kVA maximum demand
Ta r if f 6
21 Reg.3 MD kVA
Tot. 42.575
kVA maximum demand
To t a l
Total Energy and Maximum Demand Registers
Page # Page content Description
1 Total kWh
124100.0
Total kWh
2 Total kvarh
124.0
Total kvarh
2 Total kVA
124100.0
Tot al k VAh
3 Max.Dmd kW
25.588
Total kW maximum demand
4 Max.Dmd kvar
4.709
Total kvar maximum demand
5 Max.Dmd kVA
26.017
Total kVA maximum demand
6 Max.Dmd I1, A
15.58
Ampere maximum demand
7 Max.Dmd I2, A
15.58
Ampere maximum demand
8 Max.Dmd I3, A
15.58
Ampere maximum demand
9 Max.Dmd V1, V
120.5
Volt maximum demand
10 Max.Dmd V2, V
120.5
Volt maximum demand
11 Max.Dmd V3, V
120.5
Volt maximum demand
Service Display
Page # Page content Description
1 Diagnostics
3
Device diagnostics. See
Diagnostics Display below.
2 S/N 956456 Device serial number
3 S/W V18.5.1
Boot: V1.2.1
Software version
Boot loader version
4COM1:
A1, Bd19.2
COM1 port:
address and baud rate
5 COM2: Ethernet
192.168.0.203
COM2 port: node address and
net ID, or IP address
6 Ph1 Ph2 Ph3
I1 I2 I3
Submeter phase current
assignments
MULTI-MON
31-00035—01 16
Diagnostics Display
The diagnostics display shows a list of the device diagnostic
codes recorded as a result of the meter self-test diagnostics.
The diagnostics page is only displayed if errors were detected.
See Device Diagnostic Codes in Appendix F for the list of
diagnostic codes and their meanings. See Device Diagnostics
in Section 2 for more information on the Multi-Mon built-in
diagnostics. See Reset in Section 3 on how to clear the device
diagnostics status from the display.
Navigating in Menus
The Multi-Mon setup is menu-driven. To enter the setup
menus, press the SELECT button for more than 5 seconds.
Entering Numbers
Each digit in numbers is adjusted separately with the UP/
DOWN buttons. A brief press on the button increments or
decrements the highlighted digit by one. A highlighted digit is
flashing twice per second. To move to the next digit, press
briefly the SELECT button.
When the number is set to a desired value, press briefly the
ENTER button to store your new setting.
Entering a Password
The setup menus are secured by an 8-digit user password. If
the password entered is correct, you will move to the main
menu, otherwise you will return to the display mode.
Selecting Menus
The main menu is represented by two entries; the left item shows a menu list, while the right item is an
assisting exit window that allows easy returning to the display mode. Flashing highlights a currently
active menu item (in the following diagrams, a highlighted item is pointed out by using a bold font). To
highlight a desired menu item, press briefly the SELECT button.
To select a menu entry from the menu list:
1. Highlight the left item by briefly pressing the SELECT button if it is not highlighted yet.
2. Scroll through the menu list by briefly pressing the UP and DOWN buttons until the desired menu
entry appears.
3. Press the ENTER button.
To exit the main menu:
1. Highlight the Exit item by briefly pressing the SELECT button.
2. Press the ENTER button.
MULTI-MON
17 31-00035—01
Viewing and Changing Setup Items
A second level menu normally consists of three items: the upper-left static item indicates the menu
name, while the upper-right item represents a list of setup parameters you can scroll through, and the
lower item shows the present parameter value.
To select a parameter you want to view or change:
1. Highlight the upper-right item by briefly pressing the SELECT button if the item is not highlighted
yet.
2. Scroll through the parameter list with the UP/DOWN buttons until the desired parameter name
appears.
To change the selected parameter:
1. Press the SELECT button briefly to highlight the lower item.
2. If a number represents the parameter value, highlight a desired digit by briefly pressing the
SELECT button, then adjust the digit to the desired value by the UP and DOWN buttons.
3. If a name represents the parameter value, select the desired value by the UP and DOWN buttons.
4. Press the ENTER button to store your selection. You return to the parameter list to select another
parameter or return to the main menu.
To exit the menu:
1. Highlight the menu name (upper-left item) by pressing briefly the SELECT button.
2. Press the ENTER button.
MULTI-MON
31-00035—01 18
MENU OPERATIONS
Submeter Channel Assignments
This menu allows you to link the device current terminals to submeters so they can monitor them.
Additionally, the menu allows you to specify the primary current rating of the current transformers
connected to the device terminals. The number of the selected current inputs for a submeter specifies
if it will be a single-, two-, or three-phase meter.
Always select your submeters in a sequence without gaps so that your device does not occupy
unnecessary network addresses.
To enter the menu, select the SubMeter entry from the main menu, and then press the ENTER button.
To select a parameter you want to view or change:
1. Highlight the upper-right item by using the SELECT button.
2. Select the submeter you wish to configure with the UP/DOWN buttons.
3. Highlight the lower-left item by briefly pressing the SELECT button.
4. Scroll through the parameter list with the UP/DOWN buttons until the desired parameter name
appears.
To change the selected parameter:
1. Highlight the lower-right item by using the SELECT button.
2. To link a current input to a submeter, select the desired input ID with the UP/DOWN buttons.
3. To change the CT primary rating, highlight desired digits by briefly pressing the SELECT button,
then adjust them to the desired value with the UP/DOWN buttons.
4. Press the ENTER button to store your selection. You return to the parameter list to select another
parameter or return to the main menu.
To exit the menu, highlight the menu name (upper-left item) with the SELECT button, and then press
the ENTER button.
The following table lists available options.
1The device is pre-configured for twelve three-phase submeters.
2Specify the CT ratings assuming a ×200% device inputs overrange. The device inputs are preset for 100A current
transformers with a 50A primary rating.
Label Parameter Options Default Description
Phase L1
Phase L2
Phase L3
Phase current input
terminal number
I1–I36,
None = not
connected
See note1Links a current input terminal
to the corresponding
submeter’s phase voltage
input V1, V2 or V3
CT CT primary
current 2
1-10000 A 50 A Specifies the primary rating of
the submeter current
transformers
MULTI-MON
19 31-00035—01
Reset
This menu allows you to reset maximum demands in each submeter and to clear the device
diagnostics.
To enter the menu, select the Reset entry from the main menu, and then press the ENTER button.
To reset the desired registers:
1. Highlight the upper-right item by briefly pressing the SELECT button.
2. Select the submeter you are going to clear with the UP/DOWN buttons.
3. Highlight the lower-left item by pressing the SELECT button.
4. Scroll through the list with the UP/DOWN buttons until the desired entry appears.
5. Press the SELECT button to highlight the lower-right item.
6. Press and hold the ENTER button for 5 seconds. The “Do” entry is replaced with “Done” showing
the operation is complete.
To exit the menu, highlight the menu name (upper-left item) with the SELECT button, and then press
the ENTER button.
The following table lists reset options.
Real Time Clock Setting
This menu allows you to adjust internal real time clock.
To enter the menu, select the RTC entry from the main menu, and then press the ENTER button.
To adjust the clock:
To enter the menu, select the Reset entry from the main menu, and then press the ENTER button.
To reset the desired registers:
1. Highlight a time or date item you want to change item by briefly pressing the SELECT button.
2. Adjust the selected item with the UP/DOWN buttons.
3. Highlight the next item you want to change and adjust it in the same manner.
4. To store your new date and time, press the ENTER button. If you confirm the time change while
the seconds item is highlighted, the seconds’ reading will be zeroed, otherwise seconds stay
unchanged.
To exit the menu, highlight the menu name (upper-left item) with the SELECT button, and then press
the ENTER button.
Label Parameter
Diag. Clears device diagnostics status
Pow.Dmd Clears maximum power demands
Amp.Dmd Clears maximum ampere and volt demands
Max.Dmd Clears all maximum demands
MULTI-MON
31-00035—01 20
Basic Device Settings
This menu allows you to define the general characteristics of the electrical network.
To enter the menu, select the Basic entry from the main menu, and then press the ENTER button.
For instructions on navigating in the menu, see Viewing and Changing Setup Items.
The following table lists available options.
Transformer Correction
Transformer correction allows you to compensate ratio and phase angle inaccuracies of the user voltage and current instrument
transformers. To enter the menu, select the T.Corr. entry from the main menu, and then press the ENTER button. For instructions
on navigating in the menu, see Viewing and Changing Setup Items.
The following table lists available options.
Label Parameter Options Default Description
PT Pt Ratio 1.0-6500.0 1.0 The phase potential transformer’s
primary to secondary ratio
Frequency Nominal frequency 50, 60 Hz 60 Hz The nominal power frequency
PowDmdPer Block power demand
period
1, 2, 5, 10,
15, 20, 30,
60 min
30
The length of the demand period
for power demand calculations
Num.Per. The number of blocks
in the sliding window 1-15 1
The number of blocks to be
averaged for sliding window
demands
VDmnPer. Volt demand period 0-9000 sec 900 The length of the demand period
for volt demand calculations
ADmdPer. Ampere demand
period 0-9000 sec 900 The length of the demand period
for ampere demand calculations
Label Parameter Options Default Description
Ratio V1-V3 V1-V3 voltage transformer
ratio correction factor 0.700 to 1.300 1.000 The ratio of the true transformer ratio to the marked
ratio.
Angle V1-V3 V1-V3 transformer phase
angle error, minutes -600 to 600 0
The phase displacement, in minutes, between the
primary and secondary values. The phase angle of
a voltage transformer is positive when the
secondary value leads the primary value.
Ratio I1-I36 I1-I36 current transformer
ratio correction factor 0.700 to 1.300 1.000 The ratio of the true transformer ratio to the marked
ratio.
Angle I1-I36 I1-I36 transformer phase
angle error, minutes -600 to 600 0
The phase displacement, in minutes, between the
primary and secondary values. The phase angle of
a current transformer is positive when the
secondary value leads the primary value.

Other Honeywell Monitor manuals

Honeywell S7999D1048 User manual

Honeywell

Honeywell S7999D1048 User manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell 7561-PSDS User manual

Honeywell

Honeywell 7561-PSDS User manual

Honeywell HMLCD17L User manual

Honeywell

Honeywell HMLCD17L User manual

Honeywell ZA-56025-000 User manual

Honeywell

Honeywell ZA-56025-000 User manual

Honeywell HMLCD19 User manual

Honeywell

Honeywell HMLCD19 User manual

Honeywell SC500 User manual

Honeywell

Honeywell SC500 User manual

Honeywell NOTIFIER NCD User manual

Honeywell

Honeywell NOTIFIER NCD User manual

Honeywell 7800 SERIES Operation manual

Honeywell

Honeywell 7800 SERIES Operation manual

Honeywell HMC14HR User manual

Honeywell

Honeywell HMC14HR User manual

Honeywell Bendix/King KMD 550 Installation and operating instructions

Honeywell

Honeywell Bendix/King KMD 550 Installation and operating instructions

Honeywell IAQPoint2 User manual

Honeywell

Honeywell IAQPoint2 User manual

Honeywell HMLCD19L User manual

Honeywell

Honeywell HMLCD19L User manual

Honeywell RDD100 User manual

Honeywell

Honeywell RDD100 User manual

Honeywell Notifier LCD2-80 User manual

Honeywell

Honeywell Notifier LCD2-80 User manual

Honeywell Bendix/King KMD 550 Installation and operating instructions

Honeywell

Honeywell Bendix/King KMD 550 Installation and operating instructions

Honeywell IAQPoint2 User manual

Honeywell

Honeywell IAQPoint2 User manual

Honeywell HMLCD19e2 User manual

Honeywell

Honeywell HMLCD19e2 User manual

Honeywell 315-080 Technical manual

Honeywell

Honeywell 315-080 Technical manual

Honeywell HMC21 User manual

Honeywell

Honeywell HMC21 User manual

Honeywell HMLCD17L User manual

Honeywell

Honeywell HMLCD17L User manual

Honeywell HMLCD17E2 User manual

Honeywell

Honeywell HMLCD17E2 User manual

Honeywell RDD100 User manual

Honeywell

Honeywell RDD100 User manual

Honeywell S7999B User manual

Honeywell

Honeywell S7999B User manual

Popular Monitor manuals by other brands

AG Neovo SX-15 Specifications

AG Neovo

AG Neovo SX-15 Specifications

Philips 105S51 Specifications

Philips

Philips 105S51 Specifications

Panasonic TH-47LFT30W brochure

Panasonic

Panasonic TH-47LFT30W brochure

Daisy 4823DH user manual

Daisy

Daisy 4823DH user manual

NEC MultiSync V651 installation guide

NEC

NEC MultiSync V651 installation guide

ViewSonic VA2251m-LED user guide

ViewSonic

ViewSonic VA2251m-LED user guide

Eneo VM-UHD32M Quick installation guide

Eneo

Eneo VM-UHD32M Quick installation guide

HP f2304 user guide

HP

HP f2304 user guide

LG IPS236VX owner's manual

LG

LG IPS236VX owner's manual

Planar PL1700M-WH user guide

Planar

Planar PL1700M-WH user guide

Jedia JMU-307B operating instructions

Jedia

Jedia JMU-307B operating instructions

Philips 190E1SB Specifications

Philips

Philips 190E1SB Specifications

Samsung 400FP-2 - SyncMaster - 40" LCD Flat Panel... user manual

Samsung

Samsung 400FP-2 - SyncMaster - 40" LCD Flat Panel... user manual

ViewSonic VS15023 user guide

ViewSonic

ViewSonic VS15023 user guide

Eizo FlexScan T965 Specifications

Eizo

Eizo FlexScan T965 Specifications

Nano Vision UM-710 user manual

Nano Vision

Nano Vision UM-710 user manual

Aplex ADP-1XX0A Series user manual

Aplex

Aplex ADP-1XX0A Series user manual

Ludlum Measurements 240 Series user manual

Ludlum Measurements

Ludlum Measurements 240 Series user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.