T6376/T6377 THERMOSTATS HEATPUMPS & SMALL AIR CONDITIONERS
EN0R8405 R13
Sensing element
The thermostat sensing element comprises two circular,
flexible metal plates welded together at the rims and
encapsulating a gas/liquid combination whose pressure
changes in response to variations in temperature. This dual-
diaphragm expands and contracts with ambient temperature
changes to operate a snap-acting switch which controls the
heating or cooling circuit.
Heat anticipator
It is recommended that the heat anticipator is always
connected for both heating and cooling operation.
Location
The XE70 Series thermostat is the temperature control
element in the fan-coil or air-conditioning system, and must
be located in a position with good air circulation, on an inside
wall about 1.5 m above the floor to sense the average
temperature. Do not position the thermostat in draughts,
near hot or cold air sources or where it will be affected by
radiant heat from the sun or other appliances.
Mounting the thermostat
Any XE70 Series thermostat can be directly mounted on the
wall or on a conduit box (see diagram). Mounting screws are
supplied for both alternatives.
Wiring the thermostat
The standard wiring access is via a hole in the base of the
thermostat, near the top edge.
IMPORTANT
1. The installer must be a trained service engineer
2. Disconnect the power supply before beginning
installation
Switches
All switches are slide switches for ease of operation.
The ON/OFF switch is a system on/off switch, as it removes
power from the thermostat.
The FAN SPEED switch allows selection of 3 different fan
speeds, 1 (low), 2 (medium), and 3 (high).
The FAN AUTO/CONT switch allows The choice of 2 different
operating modes for the fan - either continuously (cont), or
cycled by the thermostat (auto)
The DPTT HEAT/OFF/COOL and HEAT/FAN/COOL switches
allow selection of either heating or cooling operation, but also
have an additional selection position which disables all the
outputs except that of the fan. In both these cases the fan
can be controlled separately, either by the system ON/OFF
switch or by the FAN AUTO/CONT switch.
T6376B T6377B T6377B T6377B
1004 1003 1011 1045
Ventilation
2-pipe fan-coil
Application 4-pipe fan-coil
Heatpump FFF
Air-conditioner F F
Heat or Cool
Heat/cool FFFF
Control Changeover (auto or manual) manual manual manual manual
Capability Fan control (auto or cont) either cont either either
Fan speed control FFF
Valve control FFFF
Compressor control FFFF