Version1.0asofOctober,2011
0.75 to 5.5 mm2 (AWG18 to 10)
250 VAC, 3 A maximum
or 30 VDC, 3 A maximum
Contact capacity
Applicable electric wire
CtrL control output, alarm output
Time-sharing proportional control (shift
function)
Time-sharing proportional control (F-
zone function)
Temperature alarm output, HOLD
output
FAIL output, Clu output
Kinds of alarms
Contact output
CtrL: Control output
When the measured value is larger than (control value plus
control width x 1/2), the control output is turned ON. When the
measured value is smaller than (control value minus control
width x 1/2), the control output is turned OF
.
(The above case is applicable for the upper-limit operation; the
reversed case is applicable for the lower-limit operation.)
"AL": Alarm output
When the measured value becomes larger than the setting, the
alarm output is turned ON to trigger the alarm after the delay
time. When the measured value becomes smaller than the
setting, the output is immediately turned OFF to cancel the
alarm.
The setting of output delay time (0 to 600 seconds) is also
possible.
(The above case is applicable for the upper-limit operation; the
reversed case is applicable for the lower-limit operation.)
The HP-200 is provided with five contact outputs as standard.
The HP-200 has contact outputs including upper/lower alarm
contact output, error alarm, transmission output hold, and
others.
Major specifications
•The contact capacity is 250 VAC, 3 A maximum or 30 VDC, 3
A maximum for resistance load.
•The terminal screw for the contact output is of M4.
•The applicable electric wire is of 0.75 to 5.5 mm2 (AWG18 to
10).
•If noise is detected from the load, use a varistor or a noise killer.
•Only the CLN output involves voltage from the connected power
source. Others are no-voltage contact output.
•For the FAIL output only, NO and NC are reversed. When the
HP-200 is normal (not in failure), the CF-NOF contact is open
and the CF-NCF contact is short-circuited. When the power is
OFF, the C-NOF contact is short-circuited.
•To connect any load exceeding the contact capacity or any
induction load (e.g., a motor or a pump), be sure to use a power
relay exceeding the load rating.
•When the HP-200 is OFF, the C-NC contact for R1 to R4 is
short-circuited. Therefore, be careful about the connection of
load.
R3 (control output) R4 (control output) CLN (cleaning output) *
output with voltage
R1 (control output) R2 (control output) FAIL (error warning output)
Control value
pH 14
Control width
1/2 diff
Control value
Contact output
(r1 to r4)
Measured value
pH 14
Measured
value
Contact output
(r1 to r4)
Delay time