
NQ9F
Locate the first detector in the immediate area of the bedrooms.
Try to protect the exit path as the bedrooms are usually farthest
from an exit. If more than one sleeping area exists, locate
additional detectors in each sleeping area.
Locate additional detectors to protect any stairway as stairways act
like chimneys for smoke and heat.
Locate at least one detector on every floor level.
Locate a detector in every room where electrical appliances are
operated (i.e. portable heaters or humidifiers).
Locate a detector in every room where someone sleeps with the
door closed. The closed door may prevent the alarm from waking
the sleeper.
Smoke, heat and other combustion products rise to the ceiling and
spread horizontally. Mounting the detector on the ceiling in the
center of the room places it close to all points in the room. Ceiling
mounting is preferred in ordinary residential construction.
For mobile home installation select location carefully to avoid
thermal barrier that may form at the ceiling.
When mounting detector on the ceiling locate it at a minimum of
4" (10cm) from the side wall and 2 feet (60.96cm) from any corner
(See Diagram).
If ceiling mounting is not possible and wall mounting is permitted
by your local and state codes, put wall-mounted detectors
between 4 and 6 inches (10 and 15 cm) from the ceiling (see
Diagram).
Put heat detector at both ends of a bedroom hallway if the hallway
is more than 30 feet long.
Kitchen or garage where smoke detector is not applicable.
RECOMMENDED LOCATION OF DETECTORS
IMPORTANT : READ ALL INSTRUCTIONS
BEFORE INSTALLATION
SINGLE STATION
HEAT DETECTOR
Files Number : 1O.NQ9F0.M01
version A 2014.05.21
OWNERS MANUAL
Power 9V battery
Thermal Setting 70℃
Sound 90dB / M and above
Ambient Temperature -10℃ ~ +55℃
Standby: flash every 40 seconds
Indicator Alarm: flash and beep continuously
Battery abnormal: beeps and flash intermittently
- 1 - - 2 - - 3 -
AVOID THESE LOCATIONS
Do Not Locate Your Detector in :
STORE KITCHEN
DINING ROOM
LIVING ROOM
BEDROOM GARAGE
BEDROOM
KITCHEN
BEDROOM
BEDROOM
FAMILY ROOM
BASEMENT
DINING
ROOM
BEDROOM GARAGE
HEAT DETECTOR FOR
MINIMUM SECURITY
HEAT DETECTOR FOR
MORE SECURITY
DEAD AIR AREA
BEST IN CEILING CENTRE
NOT CLOSER THAN 10 CM
FROM WALL
MOUNT ON WALL AT LEAST 10 CM
FROM CEILING. NOT MORE THAN
15 CM FROM CEILING
ACCEPTABLE LOCATION
in front of forced air ducts used for heating and air conditioning
and other high air flow areas.
in the peak of an "A" frame type of ceiling.
in areas where temperatures may above 100 F.
in very humid areas or near a bathroom, moisture can cause false
alarm.
Near electrical lights-Electrical "Noise" from electrical lights may
cause nuisance alarms. Put up smoke detectors at least 5 feet (1.5
meters) from such lights.
The heat alarm is designed to minimize false alarms.
If the detector does alarm, check for fires first. If a fire is discovered,
get out and call the fire department. If no fire is present, check to see
if one of the reasons listed above may have caused the alarm.
FALSE ALARMS
INSTALLATION
OPERATION : The heat alarm is operating once the battery is
connected. When products of combustion are sensed, the unit
sounds and indicator flashes continuously.
OPERATION, TESTING & MAINTENANCE
Remove the mounting base from the detector. Mount heat alarm
base onto mounting surface and drive the screws into the surface.
Remove the plastic film from battery and reinsert battery into
battery holder.
Replace detecor head by twisting it until it latches onto base.
TESTING : Test by pushing test button on cover and holding button
down. This will sound alarm if all electronic circuitry, horn, and battery
are working. If no alarm sounds, the unit may has a defective battery
or other failure. You can also test alarm by blowing smoke into it.
Erratic noise or low sound from alarm may indicate a defective
detector.And if the alarm fails to operate correctly please return it for
service.
MAINTENANCE : The heat detector is virtually maintenance free.
The heat alarm is powered by one 9V battery. The battery should
provide operation for at least one year under normal operating
conditions. The heat alarm has a low battery monitoring indicator
which will flash and unit beeps intermittently.
Test the alarm for correct
operation using the test facility, whenever the battery is replaced.
BATTERY REPLACEMENT
There are situations where detector may not be effective to protect
against fire as stated in the NFPA standard 74. For instance:
a) smoking in bed.
b) leaving children home alone, and.
c) cleaning with flammable liquids, such as gasoline.
GOOD SAFETY HABITS
HORING LIH INDUSTRIAL CO.,LTD.