
-The display will show the current value or setting of
the parameter.
-Set the reversing sensitivity as required using R10. Do not
leave this adjustment at minimum. Horton recommends setting
the sensitivity so the door will reverse at 28 ft.lb. or less.
-When all adjustments have been made and checked, be
sure the toggle circuit is on.
10th Step -Saving new settings
-While holding the SET button,
press the UP or DOWN button to modify the setting.
-With the display reading 2d or da press and HOLD the
SET button until dS (data save) is displayed. All of the
changes are now stored in the control's memory.
This step must be performed or the control will revert to
the default settings after a power failure.
-When the SET button is released, the display will show
the parameter that was just changed. Another parameter
may be changed, or the toggle circuit turned on to check the
changes just made. In versions 1.10 and up the SET button
may be double clicked to exit the menu (toggle must be on).
1.0014d
10/05
+100
R
SET
UP DOWN
SET
DOWN
R
+100
UP
R
+100
-When the parameter to be changed is found, press
and hold the SET button.
-The display will switch to the menu of adjustable parameters
-In versions 1.08 and up, the right decimal point will be blinking
-Turn the toggle switch OFF
Or for versions 1.10 and up, leave the toggle ON and
double click the SET button.
A chart of preset values is shown to the right.
If any speeds or other settings need to be changed, follow this procedure:
9th Step - Changing parameter settings
3. ADJUSTING PARAMETERS
-Scroll through the parameter list using the UP and
DOWN buttons until the parameter to be changed is
found.
-Refer to the chart in section 4 for a list of codes for
adjustable parameters. UP DOWN SET
R
+100
UP DOWN SET
R
+100
UP SET
DOWN
H201C.3
on (version 1.12 & up only)
oF (lock stays unlocked in day mode)
oF (version 1.02 & up only)
oF(fail-secure) (on fail-safe)
oF (monitored lock)
oF (on if Horton lock is present)
oF (on)(Version1.02 & up only)
oF (on)(Version1.02 & up only)
oF (version 1.16 & up only)
oF (version 1.17 & up only)
oF (version 1.04 and up only)
oF (version 1.17 & up only)
**In versions 1.07 & prior, d1 and d2 adjust from 1-199 seconds.
**Beginning with version 1.08, these parameters may be set to 1-8, 10, 12,14, 16, 20, 25,
30 or 60 seconds.
! Prior to 1.17, sidelite protection device was wired to 10 & 11 of CN2. 1.17 and later
is wired to 6 &7.
-A double dash (--) is a reserved parameter that is not implemented.
*Caution: very light doors may require a lower speed setting
Lock present
brake on recycles
fail-SAfe lock
Close braking
no Adjustment permitted
Power fail Night mode
Apex Enable
Longer Timeouts
Sidelite Protection
daytime Lock
daytime 1-way Lock
Unmonitored Lock
!
oF/on
oF/on
oF/on
oF/on
oF/on
oF/on
oF/on
oF/on
oF/on
oF/on
oF/on
oF/on
3
4
4
10
3 (factory set - do not change)
1 (factory set - do not change)
1 sec
1 sec
3
12*
FACTORY PRESET VALUE
20
The chart below shows all the adjustable parameters for version 1 software.
Follow the procedure outlined in step 9 to make any necessary changes.
3 (factory set - do not change)
oF (no)
OP (power fail OPen)
oF (no)
oF (no)
4.ADJUSTABLE PRESET PARAMETERS
delay time 2 (partial open)
delay time 1 (full open)
Close cUshion
Open cUshion
Power Fail
Heavy-duty door/motor
cycle test
Auto Seal
brake time
CloseCheck
Close Speed
Open Speed
PARAMETER
Open Check
CODE
0-100
oF/on
OP/CL
oF/on
oF/on
0-15
1-60**
0-15
1-60**
0-15
0-15
ADJUSTS
0-15
0-15