250
GENERAL INFORMATION
GENERAL
INFORMATION
© Hammond Power Solutions Inc. Data subject to change without notice.
ACCESSORIES(for transformers listed in sections 3, 4, 7, 8, 9 and 10)
If wall and/or ceiling mounting is desired for a
transformer, optional mounting kits can be ordered
separately. These mounting kits are NOT available for
all enclosure case styles. Therefore, it is important
that you conrm your enclosure case style, then use
the selection table to the right to determine if A) a
mounting kit is available and B) determine the correct
HPS “Mounting Kit” part number that you must order.
One kit is required for each transformer.
Note: Some of the mounting kits can be used for both
wall and ceiling mount, while others are for wall mount-
ing only. The table indicates which mounting methods
are available for each kit. The NW2 wall/ceiling mounting kit also includes a drip plate.
The NW2 wall/ceiling mounting kit is only designed for units up to 750 pounds (341 kg) maximum.
ENCLOSURE MOUNTING KITS
NW2 WALL/CEILING MOUNTING KITS
The following drawings detail the wall and ceiling mounting dimensions required and method by which the
NW2 kits are installed on the NH3 enclosures.
NW2 WALL MOUNT - MOUNTING DIMENSIONS
Part No. Enclosure MAT MAB MC
NW2 NH3 29.375 23.50 36.50
MAT
MAB
MC
1.75
1.75
BOTTOM
DRIP PLATE
MOUNTING
BRACKETS
Rear View Side View
NOTE: Please refer to enclosure dimensional drawings on page 243 for more
detailed dimensional information.
Enclosure Wall Ceiling Hammond
Case Mount Mount Mounting
Style Available Available Kit P/N
L Series Std No -
N1 No No N/A
N2 No No N/A
NH3 Yes Yes NW2
NH5 Yes Yes NH5DP
NH6 Yes Yes NH6DP
NJ Series No No N/A
NQ Series Std No -
NQT2 to NQT6 Std. No -
NQT7 to NQT8 Yes No NQTW1
NQT9 to NQT11 No No -