Huazheng Electric Manufacturing HZTR-1000 User manual

Huazheng Electric Manufacturing Co.,ltd
HZTR-1000 infrared quantitative SF6 gas Leak detector

1
Content
1. Summary ............................................................................................................1
2.Technical data and founction ............................................................................3
3.User instruction .................................................................................................4
4.Shut down ..........................................................................................................8
5.Equipment calibration time and safty measures ...............................................7
6.The operator's requirements for using this device..............................................8
7.After sale service and warranty .......................................................................9

2
Terms and Conditions
※You must read this manual carefully when operating this equipment.
※The company shall not be liable for any damage or other damages resulting from negligence or
failure to understand this manual. The text or illustration in the manual does not correspond to a
1:1 ratio.
※The user has the right to claim compensation for any errors or accidents caused by equipment
malfunction.
※All data, plans, signs and others in the manual are the patents of the company. No one can imitate
or infringe on the company's logo without the permission of the company. Once discovered, the
company has the right to appeal the relevant legal department and request punishment and
compensation. The company's copyright may not be infringed.
※If the equipment is faulty, it must be returned to the company's maintenance or the company's
authorization to a certain maintenance point. The user must not open it without authorization and
bear the consequences.
※When the goods arrive, that is, they are checked out according to the checklist in the box. If any
loss or damage is found in the inspection process, the relevant agreement may be rejected or
economic compensation may be required.
※The product must have a special protection box, which should be protected from violent vibration,
inversion, rain, and sun exposure.
※The product should be packed according to the prescribed box.
※After the equipment is used, it should be put back into the protection box. Do not leave it
anywhere to avoid premature damage.
※Do not store products in the open air.
※The product should be placed in a dry and dust-free environment.
※The product should avoid strong mechanical oscillations.
※The product should not be placed in a corrosive medium.
※This product is a special leak detection equipment for SF6 gas. Do not use it randomly.
※The product should be regularly cleaned and maintained.
※When the product is clean, corrosion and acidic solvents should not be used.
※Consult the company's professional engineers before servicing the equipment.

3
HZTR-1000 SF6 infrared quantitative detector
HZTR-1000 SF6 infrared quantitative detector uses high-speed embedded MCU, English touch
human-machine interface, the operation is simple and clear. The sensor is based on the technical
principle of the dual-wave non-dispersive infrared spectrometer (NDIR) imported from Germany.
The complete hardware and software design of SF6 gas leakage infrared leak detector provides
reliable and high-precision performance and maintenance-free features. At the same time, it also
provides functions such as data saving, USB data export, stable and reliable operation of the
equipment, and high-precision performance.
1.technical parameters:
(1) Minimum detection value: 0.1ppm
(2) Detection range: 0 to 1000ppm
(3) Response time: <3 seconds
(4) Recovery time: <5 seconds
(5) Citation error: ≤±1%[0~1000] ppm ≤±5%[1000~5000] ppm
(6) Repeat error: ≤2%
(7) Display mode: 3.5-inch color touch screen display
(8) Probe Detection Length: Straight 130mm
(9) Continuous working time: ≥8 hours
(10) Instrument power: four-cell lithium battery
(11) Charging voltage: 8.4 volts Photoelectric time 5 hours (continuous charge no more than 12
hours)
(12) Operating Environment: Temperature: -10°C to 50°C
Relative humidity: ≤95%
(13) Total weight: 0.3 kg
(14) Volume: length ×width ×height = 230mm ×120mm ×60mm
(15) Outer box: length ×width ×height = 450 mm ×230 mm ×130 mm

4
2. Product features:
※The first domestic company adopts infrared double spectrum principle to replace
imported infrared detector;
※With original wrist strap, one-handed operation.
※The first flashlight function is convenient for on-site inspection under low light conditions.
※It has special programs for anti-jamming on site and data protection functions;
※Imported infrared sensors, quantitative detection, high precision;
※8000 sets of test data can be saved and exported via USB interface;
※four-cell lithium polymer battery, reliable explosion-proof;
※First machine temperature control system;
※With advanced power management system, automatic standby and shutdown;
※compact structure, beautiful appearance, concise content, simple operation;
3.operation instructions:
Starting-up
Press the power key, the display is on, and the interface of figure 1 appears:
SF6 红外检测:SF6 infrared detection
Figure 1
(Attention!! After each measurement is completed, the power must be turned off manually.
Otherwise, the battery will run out.At this point, the left indicator light is bright (bright), the
right indicator light flashes, after 5 seconds, the interface of Figure 2 appears:
Firgure 2
SF6Gas concentration
O ppm

5
After 5 seconds, the display backlight is automatically extinguished, the left indicator light is on
(bright on), and the side indicator is on. This is the standby state
A shortcut key operation
After the interface of Figure 2 appears after power on, press the measurement key and the
interface in Figure 3 appears:
Firgure 3
Preheating is automatically delayed for 90 seconds (countdown, the sensor itself requires. In order to
enter a stable operating state, it must be warmed up.)
Hours 0 seconds, built-in air pump work, the left indicator, Figure 4 interface appears:
Firgure 4
SF6Gas concentration
O ppm
SF6 sensor warming up for 90 seconds
<
SF6Gas concentration
O ppm

6
The ">, <" sign rotation changes appear on the interface, indicating that you can enter the
measurement state, you can measure, after measuring a set of data, press the measurement key, the
machine air pump stops, if you need to test the next data, press Measure the key, start the air pump in
the machine and start the measurement again. (Attention!! Do not turn off the power switch during
the entire measurement cycle. Since this key is operated, it must be warmed up for another 90
seconds before measurement can be performed.)
The entire measurement time can be set at the initial time, and the measurement will be
automatically stopped at that time.
In the measurement process, according to the user-defined concentration alarm limit, the screen will
appear: SF6 gas high-risk concentration alarm voice prompts, while the buzzer sounds an alarm.
After the measurement is completed, you need to save the measured data and press the save key
(Note!! This save key only saves the data to the memory, the shutdown is lost, and it needs to be
permanently saved. Enter the menu map and select the permanent save. The data will be
automatically Reading into memory, the data can save up to 8000 groups.
B touch key operation
After booting, after the interface in Figure 2 is displayed, touch the screen at any place, the
interface of Figure 5 appears:
Figure 5
The user presses the self-desired button and operates on the touch key. After 5 seconds, the backlight
is automatically extinguished. The right red indicator light flashes to indicate the standby status.
SF6Gas concentration
O ppm
Measure Set Display Save Backlight Send

7
After touching the screen, the screen is restored.
Touch the measurement key: The measurement can be performed. The operation procedure is the
same as the shortcut key measurement program.
Touch the Settings button: The interface of Figure 6 appears:
图六
Figure 6
Users can make initial settings according to their own needs. The settings are as described above.
Touch the display button: a few screens appear in Figure 7 (below:)
system program
System calibration
Working paramerter
save setting

8
Firgue 7—1 Firgue 7—4
Firgue 7—2 Firgue 7—5
Figure—3 Firgue 7—6
Touch the backlight key: can change the brightness of the backlight, there are five levels of
adjustment (Note!! Not in the measurement state, fast save key, you can also change the brightness of
the backlight) After the backlight automatically goes out, press the shortcut key and the screen can be
restored at any place, In the measurement state, the backlight is not completely turned off and only
the brightness is reduced. When the help key on the touch screen is touched, a simple explanation
of the use of the instrument appears for the user to read.
4. shut down
After the measurement is finished, press the power key, the display screen is not displayed, the touch
screen is not illuminated, the power indicator is off, and the shutdown is completed.
Power status
Battery volatge:7.9V
Power supply volatge:7.9V
SF6 volatge :0 V
Battery tempreture:99℃
A/D conversion value
AD1 AD5
AD2 AD6
AD3 AD7
AD4 AD8
system status
System temperature:27.4℃
System date:
System time:
Measurement data query
Group storage data:
Measurement date:
Meaurement time:
Measurement consentration:
Storage data processing
Press Clear key to clear the stored data
Press save key to save data permanently
Peripheral state
Battery capacity:
Backlight brightness :
Air pump rate:
Meaure Set Display Help Backlight Air pump

9
5. the equipment calibration and safety measures
1) The device need to be calibrated every two years
2) In order to guarantee the personal safety of the operator and the safety of the equipment, the
provisions in the instructions must be followed.
3) This equipment is a special tool for detecting SF6 gas. It is forbidden to detect other gases and
illegal use is strictly prohibited.
4) This equipment cannot be used in work areas that have been proven to have explosive mixtures.
6. the operator's requirements for the use of the equipment
1) The operating instructions must be kept with the equipment at all times and kept by the operator.
2) The operator must be familiar with the technical descriptions and instructions in the manual.
3) The operator must be familiar with the safety measures, safe operation and cleaning and
maintenance of this equipment,
4) Engineers and technicians who must operate this equipment must have certain expertise.
5) The operator must thoroughly read this manual to understand the safety significance of SF6 gas
measurement.
6) The person managing this equipment must be serious, reliable, responsible and have certain
expertise.
7) Persons who drink, interfere with thoughts, or have not received professional training are also
prohibited from operating this equipment.
8) If you change or distort the equipment without authorization, it will not be damaged according to
the operating rules and must be responsible for the consequences.
7. Warranty: 12 months